Development of a hardware-in-the-loop testbed for laboratory performance verification of flexible building equipment in typical commercial buildings

The goals of reducing energy costs, shifting electricity peaks, increasing the use of renewable energy, and enhancing the stability of the electric grid can be met in part by fully exploiting the energy flexibility potential of buildings and building equipment. The development of strategies that exploit these flexibilities could be facilitated by publicly available high-resolution datasets illustrating how control of HVAC systems in commercial buildings can be used in different climate zones to shape the energy use profile of a building for grid needs. This article presents the development and integration of a Hardware-In-the-Loop Flexible load Testbed (HILFT) that integrates physical HVAC systems with a simulated building model and simulated occupants with the goal of generating datasets to verify load flexibility of typical commercial buildings. Compared to simulation-only experiments, the hardware-in-the-loop approach captures the dynamics of the physical systems while also allowing efficient testing of various boundary conditions. The HILFT integration in this article is achieved through the co-simulation among various software environments including LabVIEW, MATLAB, and EnergyPlus. Although theoretically viable, such integration has encountered many real-world challenges, such as: 1) how to design the overall data infrastructure to ensure effective, robust, and efficient integration; 2) how to avoid closed-loop hunting between simulated and emulated variables; 3) how to quantify system response times and minimize system delays; and 4) how to assess the overall integration quality. Lessons-learned using the examples of an AHU-VAV system, an air-source heat pump system, and a water-source heat pump system are presented.

Chen, zhelun↗

Software for Secondary-School Learning About Robotics

The ROVer Ranch is an interactive computer program designed to help secondary-school students learn about space-program robotics and related basic scientific concepts by involving the students in simplified design and programming tasks that exercise skills in mathematics and science. The tasks involve building simulated robots and then observing how they behave. The program furnishes (1) programming tools that a student can use to assemble and program a simulated robot and (2) a virtual three-dimensional mission simulator for testing the robot. First, the ROVer Ranch presents fundamental information about robotics, mission goals, and facts about the mission environment. On the basis of this information, and using the aforementioned tools, the student assembles a robot by selecting parts from such subsystems as propulsion, navigation, and scientific tools, the student builds a simulated robot to accomplish its mission. Once the robot is built, it is programmed and then placed in a three-dimensional simulated environment. Success or failure in the simulation depends on the planning and design of the robot. Data and results of the mission are available in a summary log once the mission is concluded.

Shelton, Robert O.↗

Coupled management of electric vehicle workplace charging and office building loads

Significant building energy savings are realized through heating, ventilation, and air conditioning (HVAC) setpoint adjustment and daylighting control. Workplace charging (WPC) enables colocation of electric vehicles (EVs) with office building loads. We proposed managing energy use of workplace EV charging and the office building and determined the number of EVs that building energy savings can facilitate charging. We simulated building energy savings in typical medium offices in Chicago IL, Baltimore MD, and Houston TX, spanning three US climate regions. Considering the EV hosting capacity of the saved building energy and travel patterns of roundtrip commuting, we minimized EV charging costs under time-of-use electricity pricing. Managed WPC can reduce charging electricity bills compared to first-come, first-served charging. The ratio of EVs to chargers, the coincident period of commuters’ dwell time and lower electricity prices, and the number of EVs in the office impacted the economic benefits achieved through charging management.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Robotic Specialization in Autonomous Robotic Structural Assembly

Robotic in-space assembly of large space structures is a long-term NASA goal to reduce launch costs and enable larger scale missions. Recently, researchers have proposed using discrete lattice building blocks and co-designed robots to build high-performance, scalable primary structure for various on-orbit and surface applications. These robots would locomote on the lattice and work in teams to build and reconfigure building-blocks into functional structure. However, the most reliable and efficient robotic system architecture, characterized by the number of different robotic 'species' and the allocation of functionality between species, is an open question. To address this problem, we decompose the robotic building-block assembly task into functional primitives and, in simulation, study the performance of the the variety of possible resulting architectures. For a set consisting of five process types (move self, move block, move friend, align bock, fasten block), we describe a method of feature space exploration and ranking based on energy and reliability cost functions. The solution space is enumerated, filtered for unique solutions, and evaluated against energy and reliability cost functions for various simulated build sizes. We find that a 2 species system, dividing the five mentioned process types between one unit cell transport robot and one fastening robot, results in the lowest energy cost system, at some cost to reliability. This system enables fastening functionality to occupy the build front while reducing the need for that functional mass to travel back and forth from a feed station. Because the details of a robot design affect the weighting and final allocation of functionality, a sensitivity analysis was conducted to evaluate the effect of changing mass allocations on architecture performance. Future systems with additional functionalities such as repair, inspection, and others may use this process to analyze and determine alternative robot architectures.

Bernus, Borbala↗

Integration and evaluation of a simulator designed to be used within a dynamic prototyping environment

The human computer interface (HCI) prototyping environment is designed to allow developers to rapidly prototype systems so that the interface and functionality of a system can be evaluated and iteratively refined early in the development process. This keeps development costs down by modifying the interface during the requirements definition phase, thus minimizing changes that need to be made during and after flight code development. Problems occur within a system when the user interface is not adequately developed and when designers and developers have an incomplete understanding of the system requirements. A process has been developed for prototyping on-board payload displays for Space Station Freedom. This prototyping process consists of five phases: identification of known requirements, analysis of the requirements, development of a formal design representation and specification, development of the prototype, and evaluation of the prototype. The actual development of the prototype involves prototyping the displays, developing a low fidelity simulator, building of an interface (or communication) between the displays and the simulator, integration of these components, and testing to ensure that the interface does what the developer expects. This research integrates and evaluates a software tool which has been developed to serve as a simulator within the prototyping environment. The tool is being evaluated to determine whether or not it meets the basic requirements which are needed for a low fidelity simulator within this environment. In order to evaluate the architecture and its components, a human computer interface for and a simulator of an automobile have been developed as a prototype. The individual components (i.e., the interface and simulator) have been developed, and the current research was designed to integrate and test the complete working system within the prototyping environment. The following sections will describe the architecture and components of the rapid prototyping environment, the development of a system to assess the environment, and the integration and evaluation of PERCNET.

Moore, Loretta A.↗

Probabilistic Modeling of Commercial Building Occupancy Patterns Using Location-Based Map Data: Preprint

Considering occupancy patterns is crucial to simulate buildings' energy use. Current energy models use inputs that simplify the actual diversity in occupancy into static occupancy patterns and are not able to represent the numerous variations in occupancy patterns between buildings and across different locations. Recently, inferring occupancy schedules from metered electricity consumption data was used to model occupancy in commercial buildings. However, the translation from metered data to occupancy schedules requires many assumptions that might not capture the reality, and the process is hindered by the availability of data from advanced metering infrastructure. With the development of information technologies, occupancy modeling should not be limited to traditional approaches. The prevalence of social networks and location services with real-time user feedback provides publicly accessible data via Maps Application Programming Interfaces (APIs) such as Google Maps, SafeGraph, Mapbox, Foursquare, etc. This paper presents an automated framework for modeling parametric occupancy patterns using such APIs to calibrate commercial district buildings' energy models. This process includes three main steps: data extraction and processing, parametric schedules generation, and schedules integration. We demonstrated this framework in districts where we used maps API to generate more accurate behavioral patterns for operations and electric vehicle charging events. We used these patterns to determine differences in energy use across key sociodemographic and spatial parameters. The presented method has the potential for worldwide applications. Users can utilize this framework to extract data for selected locations of interest to create more realistic behavioral patterns for commercial facilities across different districts.

building energy modeling↗

Performance Assessment of High Efficiency Variable Speed Air-Source Heat Pump in Cold Climate Applications

This project was part of an effort by ComEd's emerging technology program to evaluate the energy saving potential of new energy efficiency technologies. The focus of this technology assessment was to determine energy and peak demand savings potentials of a high efficiency variable speed, air-source, split system heat pump designed for cold climate applications. The results of this technology assessment will be used by CLEAResult to develop a new energy efficiency measure for Commonwealth Edison Company's incentive programs. The project utilized the National Renewable Energy Laboratory's (NREL) Thermal Test Facility to experimentally characterize cooling and heating performance of a high efficiency heat pump split system under varying outdoor climate conditions. The selected climate conditions represented summer and low temperature winter conditions in ComEd's service territory. The laboratory experimentation results were used to develop equipment performance curves required by EnergyPlus hourly simulation engine. Using typical meteorological year 3 weather data for the Chicago O'Hare airport, hourly building simulations (using the EnergyPlus engine) was utilized to estimate the annual energy savings of the high efficiency heat pump in comparison to a standard efficiency unit in the following U.S. Department of Energy (DOE) building codes program energy prototypes: Single-family residence; Strip mall; and Low-rise office.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

ResStock: Annual Baseline Results with Component Loads

The ResStock Analysis Tool was developed by NREL with support from the U.S. Department of Energy to provide a new approach to large-scale residential analysis by combining large public and private data sources, statistical sampling, detailed sub hourly building simulations, and high-performance computing. This combination achieves unprecedented granularity and accuracy in modeling the diversity of the housing stock and the distributional impacts of building technologies in different communities. The annual baseline energy results from a national-scale ResStock run use typical meteorological year 3 (TMY3) files for energy simulations. Results include heating and cooling loads for individual components of each building. Component loads describe the heating/cooling load that can be attributed to specific elements of a home, such as heat transfer through walls or internal gains. Additionally, these results include the standard ResStock outputs for housing characteristics and numerous energy outputs by end-use and fuel. A snapshot of the ResStock version used to produce this data, including a configuration file for the run can be found using the Source Code resource link.

Array↗

Modelica-json: Transforming energy models to digitize the control delivery process

Building simulation models are typically not used to generate the documentation required for bidding and project delivery of commercial building systems, or for their semantic modeling and commissioning. This paper presents a software tool that aids in digitizing the control delivery process, spanning simulation during design to implementation and formal verification during commissioning. The tool can generate from Modelica models digital documentation of control sequences. This digital documentation, along with other project drawings and specifications can be used for project bidding. It can also be used for implementation of control sequences through machineto-machine translation to commercial legacy control products, for which we are currently developing the proposed ASHRAE Standard 231P based on the presented work. Moreover, as-installed control sequences can be formally verified against the design specification, and a semantic model in Brick can be exported to aid in configuration of building analytics and fault detection. The paper presents what we believe is the first translation of a Modelica-implemented control sequence to a native implementation on a commercial control platform, using the webCTRL product line from Automated Logic. The paper also shows how a webCTRL implementation can be formally verified against its Modelica specification. These use cases have all been demonstrated with a prototype implementation that is now being further developed.

Wetter, Michael↗

Performance assessment of a real water source heat pump within a hardware-in-the-loop (HIL) testing environment

Over the last decade, the global fight against climate change through electrification has led to an increase in research on building heating, ventilation, and air conditioning (HVAC) systems that utilize intelligent control algorithms to provide demand-side grid service while also maintaining the thermal comfort of building occupants. As the pivotal point between building electricity consumption and indoor thermal comfort, high-efficiency electrical vapor-compression heat pumps are at the center of these emerging studies, and various grid-interactive and occupant-comfort control algorithms have been developed for them. The impact of these algorithms on heat pump operation and performance when subjected to different weather conditions, building loads, and grid requests calls for investigation and verification via experimental testing with actual heat pumps integrated with real-time building and grid responses. This study introduces a Water-Source Heat Pump (WSHP) Hardware-in-The-Loop (HIL) Test Facility that is the first of its kind. This testbed utilizes a 2-ton variable speed water-to-air heat pump that is capable of interacting with a virtual environment currently comprised of an EnergyPlus (E+) building simulation, an agent-based occupant behavioral model, and a single U-tube ground-loop heat exchanger (GLHE) model. Detailed descriptions of the testbed’s physical design and operation, virtual environment, as well as their mutual communication is provided. An uncertainty analysis is also performed under manufacturer specified heating and cooling design conditions. This analysis shows that the total load across the WSHP’s demand side heat exchanger, i.e., the sum of its latent and sensible components, can be measured with a relative uncertainty of ± 10.4% and ± 3.6% in cooling and heating mode respectively. The WSHP’s coefficient of performance (COP) can be measured with relative uncertainties of ± 10.4% in cooling mode, and ± 3.7% in heating mode. A preliminary 24-h experimental demonstration is then performed utilizing the DOE prototype small commercial office building model in E+. The simulation takes place in Atlanta, GA on the date of 08/26/15 from 12:00 AM to 11:59 PM using TMY3 weather data. Here, the results from this demonstration show that over the course of this experiment the simulated outputs of zone dry-bulb temperature, zone humidity ratio, and WSHP inlet water temperature can be tracked by testbed emulators up to a root mean squared error (RMSE) of ± 0.27 °C, ± 0.376 g/kg, and ± 0.85 °C respectively. The WSHP’s dynamic behavioral characteristics and performance are also captured, and correspond well with the authors’ previous understanding of heat pump efficiency as a function of evaporator and condenser fluid inlet conditions respectively.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Quantifying the effect of multiple load flexibility strategies on commercial building electricity demand and services via surrogate modeling

The expansion of commercial building demand response as a demand-side management resource for the electric grid necessitates new decision support resources for customers seeking to assess the benefit–risk tradeoffs of possible strategies for energy flexible building operations. To address this need, we, in this study, develop surrogate models that predict the impacts of several load flexibility strategies on commercial building electricity demand and indoor temperature, focusing on offices and retail buildings at multiple scales. The surrogate models are fit to a synthetic database generated via whole building simulations, which establish the relationships between the key operational features of a given strategy and potential changes in building demand and temperature across a variety of contexts. The surrogate models are translated to a Bayesian framework to allow straightforward communication of uncertainty and parameter updating given new evidence. We find strong predictive performance across the suite of models, underscoring the usefulness of the approach in guiding decisions about implementing load flexibility strategies under a particular set of operational and environmental conditions.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

An update to the Sandia method for creating Typical Meteorological Years from a limited pool of calendar years

Typical Meteorological Years (TMYs) are essential for the efficient evaluation of energy system performance. Ideally, 30 years of weather data are required to generate TMYs, but significantly fewer years are typically available due to practical limitations. To address this issue, an update to the Sandia method was developed, referred to as the Argonne method, to create TMYs from a limited number of years. Furthermore, this method enhances candidate diversity by systematically shifting original candidate months forward or backward by specific days, creating an expanded pool of candidates. The effectiveness of the Argonne method was validated through statistical testing, comparison of monthly average weather parameters, and numerical simulations. The results demonstrate a high probability of identifying at least one shifted month whose cumulative distribution functions of weather parameters closely align with long-term distributions. In 67 % of all comparisons, the monthly average weather parameters in TMYs generated using the Argonne method exhibit better agreement with long-term averages than TMY3. Moreover, in 74 % of the 318 building simulation cases, the Argonne method outperforms TMY3 in estimating long-term average building heating and cooling demands. Therefore, the Argonne method effectively diversifies the candidate pool and produces typical years that provide more accurate estimations of long-term averages compared to TMY3 when only a limited pool of calendar years (10 years or fewer) is available.

Building energy modeling↗

Development of National New Construction Weighting Factors for the Commercial Building Prototype Analyses (2008-2022)

The U.S. Department of Energy (DOE) tasked Pacific Northwest National Laboratory (PNNL) with updating commercial building construction weights for the purpose of estimating national and state-by-state energy savings impacts of changes made to various commercial energy codes and standards. A similar activity was last completed by PNNL in 2020 using disaggregate construction volume data acquired from the Dodge Data & Analytics database (formerly McGraw Hill) for the years 2003-2018 (Lei et al, 2020). As time passes, changes in economic and social demand reshape construction volume trends. For the current update, PNNL reviewed the same data source with the latest construction data for the years 2008-2022. For commercial building analyses, PNNL typically uses a suite of 16 prototype buildings simulated in the 19 ASHRAE climate zones with 16 of them present in the United States. The 2008-2022 commercial building weighting factors were derived using the same approach employed to develop the 2003-2018 set (Lei et al, 2020). Applying the construction volume data from the database to the prototypes and climate zones resulted in the following new construction area-based weighting factors. Table ES.1 shows the weighting factors including all building categories found in the database, and Table ES.2 shows the weighting factors normalized to include only buildings represented by the 16 prototypes. Section 3.0 also includes national- and state-level weighting factors by area and building count.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

CityBES v2021

City Buildings, Energy, and Sustainability (CityBES) is a web-based data and computing platform, focusing on energy modeling and analysis of a city's building stock to support district or city-scale building energy efficiency programs. CityBES uses an international open data standard, CityGML, to represent and exchange 3D city models. CityBES employs EnergyPlus to simulate building energy use and savings from energy efficient retrofits. Other CityBES features include energy benchmarking, district heating and cooling system modeling, rooftop PV analysis, building performance visualization, heat resilience modeling, as well as urban scale mapping of microclimate and heat vulnerability at census tract level. Different from other tools, CityBES uses integrated open and standard 3D city building data and models each individual building using EnergyPlus. CityBES can be used by urban planners, city energy managers, building owners, utilities, energy consultants and researchers.

Hong, Tianzhen↗

Hygrothermal simulation of exterior retrofits in a cold climate

This work presents results from moisture modeling as part of a project undertaken by Pacific Northwest National Laboratory and its research partners, the University of Minnesota, and the Oak Ridge National Laboratory. The research goal is to identify exterior wall retrofit systems for cold climates that are low cost, energy efficient, and do not result in moisture durability problems. A base case wall was identified representing a typical wood frame construction, circa 1950. Retrofit options were selected based on input from industry, academia, and published work and seven options were constructed and installed at the University of Minnesota’s cold weather exposure facility in Cloquet, MN. Measurements were carried out during winter months and the data was used for model validation. Hygrothermal simulations were then carried out using WUFI (Version 6.4) in accordance with standard ANSI/ASRHAE 160-2016, Criteria for Moisture-Control Design Analysis in Buildings. Simulations were run out to three years and results show that the exterior retrofits improve thermal performance and do not negatively impact moisture durability of the existing wall.

Aldykiewicz Jr, Antonio↗

A Cybersecurity Testbed for Smart Buildings

Smart buildings are equipped with a plethora of cyber-physical systems, such as Internet of Things (IoT) devices and building automation systems. These devices, especially in commercial buildings, use legacy communications and hardware that were not designed with cybersecurity in mind. With increasing cyber threats in recent years, smart buildings have become an increasing target for attacks, but not enough published data are available from these incidents to study or replicate the scenarios to defend buildings. As part of the U.S. Department of Energy-funded project focusing on developing the Building Intelligence with Layered Defense Using Security-Constrained Optimization and Security Risk Detection (BUILD-SOS) platform, we developed a cybersecurity test bed for smart buildings. This test bed includes a building simulation tool, virtual devices, emulated operational technology networks, and remote hardware-in-the-loop. Using this test bed, we performed different cyberattacks on the smart building model and collected both physical building data, to understand the impacts on the building, and network data, to aid in separating mechanical faults from cyberattacks during the detection. This test bed is a significant tool in protecting smart buildings from cyberattacks because it can aid in both cybersecurity analysis and the evaluation of other cyberattack detection tools by testing the tools in a secure environment without impacting the building operations.

cyber-physical systems↗

A Cybersecurity Testbed for Smart Buildings

Smart buildings are equipped with a plethora of cyber-physical systems, such as Internet of Things (IoT) devices and building automation systems. These devices, especially in commercial buildings, use legacy communications and hardware that were not designed with cybersecurity in mind. With increasing cyber threats in recent years, smart buildings have become an increasing target for attacks, but not enough published data are available from these incidents to study or replicate the scenarios to defend buildings. As part of the U.S. Department of Energy-funded project focusing on developing the Building Intelligence with Layered Defense Using Security-Constrained Optimization and Security Risk Detection (BUILD-SOS) platform, we developed a cybersecurity test bed for smart buildings. This test bed includes a building simulation tool, virtual devices, emulated operational technology networks, and remote hardware-in-the-loop. Using this test bed, we performed different cyberattacks on the smart building model and collected both physical building data, to understand the impacts on the building, and network data, to aid in separating mechanical faults from cyberattacks during the detection. This test bed is a significant tool in protecting smart buildings from cyberattacks because they can aid in both cybersecurity analysis and the evaluation of cyberattack detection tools by testing the tools in a secure environment without impacting the building operations.

alfalfa↗

OCHRE

OCHRE™ uses a variety of input data sources to run time-series simulations. Building models can be taken from the ResStock™ database or generated using the Building Energy Optimization Tool (BEopt™) or other OpenStudio-HPXML workflows. EV charging profiles can be taken from datasets used in NLR's 2030 National Charging Network project. Weather data can be taken from the National Solar Radiation Database or EnergyPlus® weather files. There are no public datasets with OCHRE outputs at this time. However, a recent project dataset on water heater and EV demand flexibility can be requested. OCHRE is a Python-based energy modeling tool designed to model flexible loads in residential buildings. OCHRE includes detailed models and controls for flexible devices including HVAC equipment, water heaters, EVs, solar PV, and batteries. It is designed to run in co-simulation with custom controllers, aggregators, and grid models.