Advanced Protection for Microgrids and DER in Secondary Networks and Meshed Distribution Systems

Although there are increasing numbers of distributed energy resources (DERs) and microgrids being deployed, current IEEE and utility standards generally strictly limit their interconnection inside secondary networks. Secondary networks are low-voltage meshed (non-radial) distribution systems that create redundancy in the path from the main grid source to each load. This redundancy provides a high level of immunity to disruptions in the distribution system, and thus extremely high reliability of electric power service. There are two main types of secondary networks, called grid and spot secondary networks, both of which are used worldwide. In the future, primary networks in distribution systems that might include looped or meshed distribution systems at the primary-voltage (medium-voltage) level may also become common as a means for improving distribution reliability and resilience.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Supercapacitor-Based Power Resilience Solutions for Modern Grids, Microgrids, and Facilities

This report summarizes the tests and results of a supercapacitor based energy storage system demonstration project performed in collaboration with Capacitech Energy, Orlando Utilities Commission and Sandia National Labs. This project evaluated a 3.6 farad (F), 720 V rated supercapacitor system in a microgrid environment to study three primary use cases: black start, voltage regulation, and load leveling, and successfully demonstrated the performance for the use cases.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimally sited microgrids for energy resilience in Mount Desert Island, ME

Mount Desert Island (MDI) (≈110 sq mi; ≈10,000 year‑round residents) is located on the eastern coast of Maine. Acadia National Park is located on the island, protecting 47,000+ acres of land which draws millions of visitors annually. The island is divided into four towns (Tremont, Southwest Harbor, Mount Desert, Bar Harbor). The island’s distribution system is supplied by a single 35‑kV mainland feeder and a mix of aging distribution components; outage exposure is not uniform across the island. Residents fear that outage events are starting to exceed resilience expectations. MDI community leaders asked Sandia National Laboratories to characterize energy system vulnerability and to develop conceptual microgrid solutions that improve community resilience while also producing co‑benefits for reliability, access, and sustainable development.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Identifying Parameter Space for Robust Stability in Nonlinear Networks: A Microgrid Application

As modern engineering systems grow in complexity, attitudes toward a modular design approach become increasingly more favorable. A key challenge to a modular design approach is the certification of robust stability under uncertainties in the rest of the network. In this paper, we consider the problem of identifying the parametric region, which guarantees stability of the connected module in the robust sense under uncertainties. We derive the conditions under which the robust stability of the connected module is guaranteed for some values of the design parameters, and present a sum-of-squares (SOS) optimization-based algorithm to identify such a parametric region for polynomial systems. Using the example of an inverter-based microgrid, we show how this parametric region changes with variations in the level of uncertainties in the network.

Kundu, Soumya↗

Distributed Barrier Certificates for Safe Operation of Inverter-Based Microgrids

Inverter-interfaced microgrids differ from the traditional power systems due to their lack of inertia. Vanishing timescale separation between voltage and frequency dynamics makes it critical that faster-timescale stabilizing control laws also guarantee by-construction the satisfaction of voltage limits during transients. In this article, we apply a barrier functions method to compute distributed active and reactive power setpoint control laws that certify satisfaction of voltage limits during transients. Using sum-of-squares optimization tools, we propose an algorithmic construction of these control laws. Numerical simulations are provided to illustrate the proposed method.

Kundu, Soumya↗

Distributed Transient Safety Verification via Robust Control Invariant Sets: A Microgrid Application

Modern safety-critical energy infrastructures are increasingly operated in a hierarchical and modular control framework which allows for limited data exchange between the modules. In this context, it is important for each module to synthesize and communicate constraints on the values of exchanged information in order to assure system-wide safety. To ensure transient safety in inverter-based microgrids, we develop a set invariance-based distributed safety verification algorithm for each inverter module. Applying Nagumo's invariance condition, we construct a robust polynomial optimization problem to jointly search for safety-admissible set of control set-points and design parameters, under allowable disturbances from neighbors. We use sum-of-squares (SOS) programming to solve the verification problem and we perform numerical simulations using grid-forming inverters to illustrate the algorithm.

Bouvier, Jean-Baptiste H.↗

Optimization-Based Resiliency Verification in Microgrids via Maximal Adversarial Set Characterization

Critical energy infrastructures are increasingly relying on advanced sensing and control technologies for efficient and optimal utilization of flexible energy resources. Algorithmic procedures are needed to ensure that such systems are designed to be resilient to a wide range of cyber-physical adversarial events. This paper provides a robust optimization framework to quantify the largest adversarial perturbation that a system can accommodate without violating pre-specified resiliency metrics. We formulate the maximal adversarial set characterization as a bi-level optimization problem which is solved via Lagrangian relaxations.We illustrate the proposed algorithm on an islanded microgrid example: a modified IEEE 123-node feeder with distributed energy resources. Simulations are carried out to characterize the tolerable adversarial perturbations for varying levels of available flexibility (energy reserves).

Nazir, Mohammad Nawaf↗

Optimal Siting of EV Fleet Charging Station Considering EV Mobility and Microgrid Formation for Enhanced Grid Resilience

Coordinating infrastructure planning for transportation and the power grid is essential for enhanced reliability and resilience during operation and disaster management. This paper presents a two-stage stochastic model to optimize the location of electric vehicle fleet charging stations (FEVCSs) to enhance the resilience of a distribution network. The first stage of this model deals with the decision to place an FEVCS at the most favorable and optimized location, whereas the second stage aims to minimize the weighted sum of the value of lost load in multiple potential scenarios with different faults. Indeed, the second stage is a joint grid restoration scheme with network reconfiguration and microgrid formation using available distributed generators and fleet electric vehicles. The proposed model is tested on a modified IEEE-33 node distribution network and a four-node transportation network. Case studies demonstrate the effectiveness of the proposed model.

25 ENERGY STORAGE↗

Design, Detection, and Countermeasure of Frequency Spectrum Attack and Its Impact on Long Short-Term Memory Load Forecasting and Microgrid Energy Management

This paper introduces a frequency-domain false data injection attack called Frequency Spectrum Attack (FSA) and explores its effects on load forecasting and the energy management system (EMS) in a microgrid. The FSA analyzes time-series signals in the frequency domain to identify patterns in their frequency spectrum. It learns the distribution of dominant frequencies in a dataset of healthy signals. Subsequently, it manipulates the amplitudes of dominant frequencies within this healthy distribution, ensuring a stealthy attack against statistical analysis of the signal spectrum. We evaluated the performance of FSA on LSTM, a state-of-the-art network for load forecasting. The results show that FSA can triple the Mean Absolute Error (MAE) of predictions compared to the normal case and increase it by 70% compared to noise injection attacks. Furthermore, FSA indirectly enhances battery utilization in the EMS by 45%. We then proposed a detection method that combines statistical analysis and machine-learning-based classification techniques with features. The model effectively distinguishes FSA from healthy and noisy signals, achieving an accuracy of 98.7% and an F1-score of 98.1% on a load dataset, covering healthy, FSA, and noisy load data. Finally, a countermeasure was introduced based on the statistical analysis of the frequency spectrum of healthy signals to mitigate the impact of FSA. This countermeasure successfully reduces the MAE of the attacked model from 0.135 to 0.053, validating its effectiveness in mitigating FSA.

Nazeri, Amirhossein↗

Microgrid for Lunar Surface Power

Sustained lunar surface operations will require access to continuous and highly reliable power to support mission needs and an ability to evolve and grow over time (years). The first initial loads that arrive on the lunar surface will contain their own dedicated power sources. Over time, as the lunar surface operations and power demands grow, these individual power loads will require more power than can be generated with any single power device. This demand drives the need for inter-connecting loads and power devices to share power between them, resulting in a micro-grid. One advantage of developing a lunar surface micro-grid is that it will allow lunar surface operations to resemble electrical utility operations on Earth; it allows power to be generated where it is convenient and allows power to be consumed where it is convenient and required. The micro-grid concept also provides another benefit of affording the ability to increase overall system reliability by integrating dissimilar power generation and energy storage devices together, for example modifying the power generation strategy to include both solar arrays and nuclear. This talk provides an overview of NASA’s interest in developing a lunar microgrid and provides areas where external entities can play a role in developing futuristic power needs.

Jeffrey Csank↗

Hierarchical Control of Distributed Battery Energy Storage System in a DC Microgrid

This paper presents a novel hierarchical control approach of a DC microgrid (DCMG) which is supplied by a distributed battery energy storage system (BESS). With this approach, all battery units distributed in the BESS can be controlled to discharge with accurate current sharing and state-of-charge (SoC) balancing. Similar to other hierarchical control approaches used in DCMGs, this approach consists of three levels: (1) primary control, (2) secondary control and (3) tertiary control. This work includes defining a unit control error (UCE) at the secondary control level and evaluating current sharing weights at tertiary control level. A centralized controller at secondary control level is designed to detect the UCEs of each battery unit, and to restore the average voltage of a DCMG and control battery current sharing simultaneously. The distributed battery units share the load current in a DCMG based on weights. These weights are evaluated at the tertiary control level based on battery SoCs. The approach’s effectiveness was confirmed in digital simulation tests with the same simulation model as used in the NASA AMPS Modular Hardware Emulator.

Jing Zhang↗

Hierarchical Control of Distributed Battery Energy Storage Systems in a DC Microgrid

Contents - NASA Future Power Systems - DC Microgrid with Distributed Battery Energy Storage - A simplified gateway power system - Droop Control (Primary Control) - Distributed battery units, droop control, and load sharing characteristics - Simulation results - Three-Level Hierarchical Control of Distributed Battery Units During Eclipse - Secondary Control - Objective and definition of unit control error - Implementation of secondary control - Simulation results - Tertiary Control - Schedule BU current sharing with the objective of equal SoC - Simulation results•Conclusions

Jing Zhang↗

Performance Guaranteed Inertia Emulation forDiesel-Wind System Feed Microgrid via ModelReference Control

In this paper, a model reference control based inertia emulation strategy is proposed. Desired inertia can be precisely emulated through this control strategy so that guaranteed performance is ensured. A typical frequency response model with parametrical inertia is set to be the reference model. A measurement at a specific location delivers the information of disturbance acting on the diesel-wind system to the referencemodel. The objective is for the speed of the diesel-wind system to track the reference model. Since active power variation is dominantly governed by mechanical dynamics and modes, only mechanical dynamics and states, i.e., a swing-engine-governor system plus a reduced-order wind turbine generator, are involved in the feedback control design. The controller is implemented in a three-phase diesel-wind system feed microgrid. The results show exact synthetic inertia is emulated, leading to guaranteed performance and safety bounds.

Melin, Alexander M.↗

Emulator apparatus for microgrid testing and design

An emulator apparatus that emulates entities included in a microgrid is described herein. The emulator apparatus emulates a load with time-varying inductance/resistance or an energy storage device or combination of energy storage devices. The emulator apparatus is electrically coupled to a system or device that is desirably tested/maintained/designed. The emulator apparatus emulates a particular device, and response of the system of device to the emulated device is monitored for purposes of design, testing, or maintenance.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Intra-microgrid communication architecture

A microgrid according to an exemplary aspect of the present disclosure includes, among other things, a plurality of intelligent electronic devices configured to communicate directly with one another in a first language. Each of the intelligent electronic devices includes a controller and a gateway. The gateway is configured to convert incoming messages from the first language to a second language native to the controller. The first language is different than the second language. A method is also disclosed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Pumped hydroelectric storage balances a solar microgrid

We consider the problem of reliably operating a microgrid with solar generation and pumped hydroelectric storage. We show that reliable operation is possible if storage equipment is sufficiently flexible and storage control is sufficiently robust to solar variability. Pumped storage flexibility can be achieved through a ternary confi guration; this enables rapid switching between pumping and generating modes. Controller robustness can be achieved through a novel control synthesis method based on convex optimization and resampled historical solar data. The proposed equipment and controller perform well in simulations including twenty months of real solar data at fi ve minute resolution. These results highlight the potential of pumped storage to enable reliable integration of wind and solar power into the grid.

13 HYDRO ENERGY↗

Fuzzified PaCcET for Economic-Emission Scheduling of Microgrids

In this paper, a new approach is proposed to solve a multi-objective economic-emission scheduling problem in microgrids (MGs) by simultaneously minimizing the energy and emission costs of the MG with various distributed energy resources (DERs). The proposed approach is an extension of a computationally effective multiobjective optimization technique, Pareto concavity elimination transformation (PaCcET). The proposed approach, referred to as Fuzzified-PaCcET, employs a fuzzy logic controller to dynamically revise crossover and mutation rates in the original PaCcET leading to the faster convergence of the solution. The proposed approach finds the best Pareto front, also referred to as a Non-dominated set (NDS) of solutions, instead of finding a single optimal solution. In order to find the solutions on concave areas of the Pareto front, an iterative objective space transformation is performed in the PaCcET algorithm to allow a linear combination of objective functions (in the transformed objective space). The proposed Fuzzified-PaCcET-based scheduling is implemented on a MG with various dispatchable and non-dispatchable DERs to find the set of optimal solutions according to the total fuel cost of DERs, as well as the most optimum environmental cost. In order to extract the best compromise solution (BCS) among NDS of solutions, a fuzzy-based method is implemented. The comparison of the simulation results of the Fuzzified-PaCcET with that of PaCcET shows that Fuzzified-PaCcET can generate better solution with less computational burden.

42 ENGINEERING↗