Transformer Health Monitoring Using Dissolved Gas Analysis
As integral components of any power plant, transformers supply the generated electricity to the grid. However, a transformer’s cellulose-based paper insulation and the mineral oil in which it is immersed break down over time under standard operating conditions—or more rapidly due to potential faults within the system. As the transformer’s mineral oil breaks down, gases are released that can be measured and monitored. This technical brief exhibits a collection of diagnostic and prognostic techniques that utilities can adopt in lieu of labor-intensive periodic preventive maintenance routines. Furthermore, prognostic models have been incorporated using the latest version of the Institute of Electrical and Electronics Engineers (IEEE) standard (IEEE, 2019) for dissolved gas analysis (DGA), thus expanding it to include estimation of the time to maintenance. Overall, four different methodologies are explained, each of which aids in determining a transformer’s state of health. These methodologies include the Chendong model, the IEEE thermal life consumption model (IEEE, 2012), a diagnostic model for DGA, and a prognostic model for DGA that uses an autoregressive integrated moving average (ARIMA) model. An additional improvement for estimating missing system parameters by using monitoring data (i.e., a tool for parameter estimation utilizing Powell’s method) is presented, enabling the IEEE thermal life consumption model to benefit not only the collaborating power plant, but also the power industry at large.