This paper investigates the impact of load rejection over-voltage (LRO) from commercially available grid-tied photovoltaic (PV) solar inverters. LRO can occur when a local feeder or breaker opens and the power output from a distributed energy resource exceeds the load power. Simplified models of current controlled inverters can over-predict over-voltage magnitudes, thus it is useful to quantify testing. The load rejection event was replicated using a hardware testbed at the National Renewable Energy Laboratory (NREL), and a set of commercially available PV inverters was tested to quantify the impact of LRO for a range of generation-to-load ratios. The magnitude and duration of the over-voltage events are reported in this paper along with a discussion of characteristic inverter output behavior. The results for the inverters under test showed that maximum over-voltage magnitudes were less than 200 percent of nominal voltage, and much lower in many test cases. These research results are important because utilities that interconnect inverter-based DER need to understand their characteristics under abnormal grid conditions.
This paper reports the interim status in identifying and reviewing photovoltaic (PV) codes and standards (C&S) and related electrical activities for grid-connected, high-penetration PV systems with a focus on U.S. electric utility distribution grid interconnection.
The Energy 101: Utilities presentation, developed for the Energy Technology Innovation Partnership Project (ETIPP), provides an overview of utilities. It covers fundamental concepts, technologies, considerations, case studies, and additional resources.
Increasing need for distribution circuit reliability and resilience prompt a clearer understanding of community microgrid interconnection and operational requirements. While customer-owned, behind-the-meter microgrid implementation is not always simple, increasing demand for reliability has commercialized many installation approaches. This rapid commercialization has broadened industry understanding of single-customer microgrid integration. Moreover, off-grid behaviors of such microgrids are not required to meet utility standard interconnection requirements. However, multi-customer community microgrids (utility- or third-party operated), are less well explored and introduce more complex design and operational challenges. The control of DER along with distribution automation devices, unmanned operation, protection coordination, and other aspects makes community microgrids challenging to implement and operate in both on-grid and off-grid modes. This whitepaper is a technical primer for understanding community microgrids. It provides a foundation for understanding the components, configurations, design, and operational considerations for community microgrids.
This report summarizes work to better understand the structure of future photovoltaics business models and the research, development, and demonstration required to support their deployment.
Utilities nationwide are beginning to experience multiple solar interconnection requests per day. This request volume will soon overwhelm utility engineers, especially at smaller utilities which serve the majority of the landmass of the United States. In this project, we developed open-source software tool that automates the interconnection approval process and removes 80% of the time required to approve an interconnection and hence allow more solar to be quickly and safely integrated with the grid. This software is accompanied by a guidebook detailing interconnection best practices and utility lessons learned. Competing solar interconnection software is extremely expensive at ten times the cost of typical distribution engineering tools, it’s closed source which makes it hard to integrate into utility workflows, and it doesn’t address the hardest power flow modeling challenges of interconnection screening. Our solution was built built with our utility partners who are already experiencing multiple interconnection requests per day and integrates best practices from our past work with DOE and the cooperative community on solar integration. The resulting free and open-source solution has been disseminated through our media channels and conferences that engage over 1,900 utilities nationwide.
The rapid development of portable electronic devices increasingly requires much more energy to support advanced functions. However, currently available batteries do not meet the high energy requirement of these devices. Metal/air batteries, especially Li/air batteries, have a much higher specific energy than most other available batteries, but their power rate is limited by the accumulation of reaction products in the air electrode. Several approaches to improve the power rate of Li/air batteries have been analyzed in this work, including adjustment of air electrode porosity and catalyst reactivity distributions to minimize diffusion limitations and maximize air electrode material utilization. An interconnected dual pore system (one catalyzed and one noncatalyzed) is proposed to improve oxygen transport into the inner regions of the air electrode, but this approach alone cannot supply high power for long term applications. A time-release multiple catalyst approach is analyzed to provide temporal release of reactivity in the air electrode. When coupled with the dual pore configuration and catalysts with high reactivities, the time-release catalyst concept can extend the duration of higher powers to longer times, and result in maximum utilization of air electrode materials.
This paper presents, to our knowledge, the first system-level engineering study to bio-mimic the cybernetics and flow dynamics of energy resources in natural ecosystems for the control of heterogeneous energy infrastructures in the built environment. To this end, we introduce a novel Biomimetic Pulsing State (BPS) control that functionally mimics mature ecosystems. A preliminary Modelica-based case study features a single-family residential building with electrical and HVAC subsystems. The BPS control objective is to minimize the energy exchange between the building and the grid for the purposes of future self-supporting buildings and grid stability. The building contains PV, a wind turbine, a battery storage system, and a fan coil/heat pump HVAC system served by an ambient district energy network. Evaluating the control performance (BPS vs. constant setpoint) over several renewable energy scenarios (net importer, net zero, net exporter), simulation results show how the building's HVAC system can dynamically adjust its electrical load and temperatures to the electrical system's net energy status in real-time with BPS control. As a net importer, the heat pump consumed 29% less energy and its peak power reduced by 15% with BPS control compared to the constant setpoint case, with the zone air temperature 1 degree C lower on average. As a net exporter, the heat pump effectively consumed the same energy, but the peak power increased by 34% with BPS control, while the zone air temperature was 1 degree C higher when renewable energy was abundant, preheating the home. BPS and constant setpoint control produced comparable results under a net zero scenario. While further evaluation is essential, BPS control may help communities meet their sustainability and resiliency targets as they transition towards fully distributed and renewable energy grids.
Chemical looping with oxygen uncoupling (CLOU) is a promising carbon capture technology that utilizes two interconnected fluidized-bed reactors to separate oxygen from air using a metal oxide, and then to use that oxygen to combust fuel in a nitrogen-free environment. CLOU is particularly well suited for solid fuels such as coal since released O 2 will readily combust with solid char. This study presents simulations of the University of Utah's dual fluidized bed chemical looping process development unit (PDU) operating as a CLOU system at 100 kW th , using CPFD Software's Barracuda-VR™ CFD modeling program. A full 3D model of the PDU was used including both reactors, as well as loop seals and cyclone separators. Hydrodynamic settings and the drag model are based on previous cold-flow validation experiments. Mechanisms describing CLOU reaction kinetics for cuprous oxide oxidation in the air reactor and cupric oxide reduction in the fuel reactor were adapted from previously completed experimental work. Coal char kinetics were based on the carbon-hydrogen-nitrogen-oxygen-sulfur, CHNOS, method. Submodels for devolatilization, gasification, and homogenous gas-phase reactions used relationships from the literature. Results predict volatile burnout almost immediately, though coal combustion continues into the upper portions of the fuel reactor and cyclone. Lastly, nitrogen gas leakage into the fuel reactor is shown to be mostly carryover from the air reactor
Existing circuit camouflaging techniques to prevent reverse engineering increase circuit-complexity with significant area, energy, and delay penalty. In this paper, we propose an efficient hardware encryption technique with minimal complexity and overheads based on ferroelectric field-effect transistor (FeFET) active interconnects. By utilizing the threshold voltage programmability of the FeFETs, run-time reconfigurable inverter-buffer logic, utilizing two FeFETs and an inverter, is enabled. Judicious placement of the proposed logic makes it act as a hardware encryption key and enable encoding and decoding of the functional output without affecting the critical path timing delay. Additionally, a peripheral programming scheme for reconfigurable logic by reusing the existing scan chain logic is proposed, obviating the need for specialized programming logic and circuitry for keybit distribution. Our analysis shows an average encryption probability of 97.43% with an increase of 2.24%/ 3.67% delay for the most critical path/ sum of 100 critical paths delay for ISCAS85 benchmarks.
In this paper, a low-parasitic inductance SiC power module with double-sided cooling is designed and compared with a baseline double-sided cooled module. With the unique 3D layout utilizing vertical interconnection, the power loop inductance is effectively reduced without sacrificing the thermal performance. Both simulations and experiments are carried out to validate the design. Q3D simulation results show a power loop inductance of 1.63 nH, verified by the experiment, indicating more than 60% reduction of power loop inductance compared with the baseline module. With 0Ω external gate resistance turn-off at 600V, the voltage overshoot is less than 9% of the bus voltage at a load of 44.6A.
Photovoltaic (PV) generation is becoming increasingly common on power distribution systems. The output fluctuations of this variable resource necessitate the creation of an accurate model to ensure that any adverse impacts to the distribution system are properly addressed. To reduce model creation time, a method of extracting data from AutoCAD drawings using scripted methods was developed. This paper will present a distribution model creation and validation process, document case studies of evaluating the impact of PV interconnections on utility distribution feeders, and discuss future applications. PV integration was found to be easier on 23 kV circuits compared to 4.16 kV circuits.
The software was developed for the purpose of Microgrid Controller Procurement where multiple Microgrid Controller vendors were competing to prove the best performance. Each microgrid controller was connected to Real-Time Simulator (Opal-RT) where the Real-Time model of microgrid was simulated. Microgrid controllers were able to control most of the assets in the model. To be able to fairly compare controller's performance each controller was evaluated using exactly the same model, with the same initial conditions and exactly the same test sequence. The microgrid evaluation test sequence lasted 100 minutes and consist of various grid disturbances to which a microgrid controller must respond. The microgrid and power system will experience multiple types of disturbances while performing dispatch functions. Many functions are tested in grid-connected and islanded modes such as unexpended failures of generators, energy storage trip events, and large load fluctuations. The test sequence focuses on fault scenarios that cause the highest short-circuit fault current contribution; force a swing bus or generator capable of being a swing bus offline; cause the most reconfigurations; and cause conflicting objectives for the microgrid controller. During the test sequence execution multiple datapoints are being recorded and stored. During data postprocessing key performance parameters are extracted allowing quantitative comparison of performance on multiple aspects including: resiliency, fuel utilization, grid interconnection, ancillary services and power quality and eventually after summing all key performance parameters by comparing the overall result. To be able to perform such testing multiple tools had to be developed included in this repository including: - Real time model of microgrid (Urban-Banshee, Remote-smaller model) - Test sequence configuration tools - Test execution real-time scripts - Post processing scripts - Human Machine Interface software
The National Renewable Energy Laboratory/Southern California Edison High-Penetration PV Integration Project is (1) researching the distribution system level impacts of high-penetration photovoltaic (PV) integration, (2) determining mitigation methods to reduce or eliminate those impacts, and (3) seeking to demonstrate these mitigation methods on actual high-penetration PV distribution circuits. This report describes a field demonstration completed during the fall of 2013 on the Fontana, California, study circuit, which includes a total of 4.5 MW of interconnected utility-scale rooftop PV systems. The demonstration included operating a 2-MW PV system at an off-unity power factor that had been determined during previously completed distribution system modeling and PV impact assessment analyses. Data on the distribution circuit and PV system operations were collected during the 2-week demonstration period. This demonstration reinforces the findings of previous laboratory testing that showed that utility-scale PV inverters are capable of operating at off-unity power factor to mitigate PV impacts; however, because of difficulties setting and retaining PV inverter power factor set points during the field demonstration, it was not possible to demonstrate the effectiveness of off-unity power factor operation to mitigate the voltage impacts of high-penetration PV integration. Lessons learned from this field demonstration are presented to inform future field demonstration efforts.
The overall objective of the current project was to investigate the high pressure gasification characteristics of a feed containing both coal and biomass. The two feed types differ in their ash contents and ash composition, particularly the alkali content. Gasification of a combined feed of coal and biomass has the potential for considerable synergies that might lead to a dramatic improvement in process economics and flexibility. The proposed study aimed to develop a detailed understanding of the chemistry, kinetics, and transport effects during high pressure gasification of coal-biomass blend feed. Specifically, we studied to develop: (a) an understanding of the catalytic effect of alkali and other inorganic species present in the biomass and coal, (b) an understanding of processing conditions under which synergistic effects of the blending of coal and biomass might be observed. This included the role of particle size, residence time, and proximity of the two feed types, (c) kinetics of high pressure gasification of individual feeds as well as the blends, and (d) development of mathematical models that incorporate kinetics and transport models to enable prediction of gasification rate at a given set of operating conditions, and (e) protocols to extend the results to other feed resources. The goal was to provide a fundamental understanding of the gasification process and guide in optimizing the configurations and design of the next generation of gasifiers. The approach undertaken was centered on two basic premises: (1) the gasification for small particles without internal mass transfer limitations can be treated as the sum of two processes in series (pyrolysis and char gasification) , and (2) the reactivity of the char generated during pyrolysis not only depends on the pressure and temperature but is also affected by the heating rates. Thus low heating rates (10-50 °C/min) typical of PTGA fail to produce char that would typically be formed at high heating rates (~10 4 °C/sec), encountered in entrained flow gasifiers. The char morphology, also a function of the heating rate, would influence the transport rates during the char gasification phase. Thus, heating rate plays a critical role through which both, pyrolysis and char gasification, are interconnected. We utilized two complementary gasification experiments: PEFR (pressurized entrained flow gasifier) and PTGA (pressurized thermo-gravimetric analyzer). The PEFR allowed us to study gasification at pressures, temperatures, and heating rates relevant for coal-biomass gasifiers. The PTGA work was useful in understanding the basic chemistry of the evolution of various gaseous species during pyrolysis. These results helped improved our understanding of the chemistry and chemical changes during pyrolysis. The role alkali metals and other inorganics in char gasification using steam and/or CO 2 was investigated. Finally, the mathematical models for char gasification without the transport effects were developed at commercial operating conditions.
DOE has developed this guide to help local governments design and implement local solar plans. This guide includes examples and models tested in cities. Many of the examples are results of DOE's Solar America Cities Program.
We are interested in benchmarking both quantum annealing and classical algorithms for minimizing quadratic unconstrained binary optimization (QUBO) problems. Such problems are NP-hard in general, implying that the exact minima of randomly generated instances are hard to find and thus typically unknown. While brute forcing smaller instances is possible, such instances are typically not interesting due to being too easy for both quantum and classical algorithms. In this contribution, we propose a novel method, called posiform planting , for generating random QUBO instances of arbitrary size with known optimal solutions, and use those instances to benchmark the sampling quality of four D-Wave quantum annealers utilizing different interconnection structures (Chimera, Pegasus, and Zephyr hardware graphs) and the simulated annealing algorithm. Posiform planting differs from many existing methods in two key ways. It ensures the uniqueness of the planted optimal solution, thus avoiding groundstate degeneracy, and it enables the generation of QUBOs that are tailored to a given hardware connectivity structure, provided that the connectivity is not too sparse. Posiform planted QUBOs are a type of 2-SAT boolean satisfiability combinatorial optimization problems. Our experiments demonstrate the capability of the D-Wave quantum annealers to sample the optimal planted solution of combinatorial optimization problems with up to 5, 627 qubits.