Spectral Clustering-Based Partitioning of Large-Scale Power Electronics-Based Power Systems for Small-Signal Stability Analysis

The nodal admittance matrix (NAM)-based approach is well-suited for small-signal stability analysis of large-scale power electronics-based power systems (PEPSs), as it preserves the system structure through its admittance matrix. Previous studies have explored partitioning such systems into subareas and interconnections to reduce computational burden; however, they lacked a formal algorithmic procedure for determining feasible partitions. While several grid partitioning methods, such as those based on graph theory or machine learning, exist in the literature, they cannot be directly applied to NAM-based analysis due to differing objectives and constraints. Here, this paper addresses this gap by presenting a systematic, step-by-step procedure for applying a spectral partitioning algorithm that yields a division of the system into subareas suitable for NAM-based analysis. The computational complexity of the proposed method is also derived to demonstrate its efficiency and justify the practicality of the resulting subarea decomposition. The performance of the partitioning method is evaluated by applying the spectral clustering-derived subareas and interconnections to the NAM-based partitioning approach on a 140-bus system. Computational times for the full-system and partitioned NAM analyses are compared using MATLAB. Additionally, PSCAD simulations of the complete system and partitioned subareas are carried out to verify the effectiveness of the proposed method.

Nupur [Univ. of Tennessee, Knoxville, TN (United S↗

Generalized Power Flow Model of an Extra High-Power Multi-Terminal HVdc Transmission Grid with Parallel-Connected and Voltage-Stacked Converters

To increase power transfer capacity of high-voltage direct current (HVdc) transmission, a new extra high-power HVdc architecture with multiple standard modular multilevel converters (MMCs) per substation has recently been introduced. This paper proposes a power flow model for a multi-terminal HVdc (MTdc) grid with this innovative substation architecture. The proposed MTdc model can be integrated seamlessly with existing ac-dc power flow algorithms with minimal modifications. The model is applicable to various MTdc grid types and topologies, different numbers of dc buses, dc lines, and MMCs per substation, along with diverse control parameters. In addition, it accurately captures both balanced and unbalanced operations of the MTdc grid. The proposed model is verified using a 5-terminal bipole MTdc grid that spans 4 areas in the Eastern Interconnection system of the USA. The numerical solutions obtained from unified and sequential ac-dc power flow algorithms under different operating conditions closely match the time-domain simulation results in PSCAD, validating the accuracy and versatility of the proposed MTdc power flow model.

Nguyen, Quan H.↗

Sequence Impedance Modeling of Grid-Forming Inverters

Grid-forming control of inverter-based resources has been identified as a critical technology for operating power systems with high levels of inverter-based resources. This paper presents the sequence impedance modeling of a grid-forming inverter to evaluate its small-signal stability properties. Droop control structure is implemented to control the inverter in grid-forming mode, and the impact of individual controller on the inverter impedance characteristics is discussed. The developed sequence impedance model is compared with that of the grid-following inverter. It is found from the developed sequence impedance models that grid-forming inverters are less prone to harmonic resonance problems during operation with weaker grids. The developed models are validated using PSCAD simulations.

grid- following inverter↗

Consensus-Based Approach for Active Power Control and Reserve Estimation in Distributed PV Systems

With the increased adoption of distributed energy resources (DER), they are expected to contribute to power system reliability services and enhance power system stability. This paper presents a distributed consensus control approach for the real-time active power reserve estimation and power management in distributed PV (photovoltaic) systems. The proposed method estimates the cumulative active power reserve from numerous PV generators using only the sparse communication network for a DER aggregator to provide active power regulation services. The real-time active power reserve estimation using the proposed approach can be used by DER aggregators to manage curtailment in distributed PV systems to maintain stipulated reserves and further to provide power system frequency regulation. Using the proposed approach, the DER aggregator only requires measurements at the feeder substation and it does not require information from individual DER units, thereby improving system resiliency. The proposed distributed consensus control method is validated on IEEE 123 testbed using PSCAD simulations.

active power reserve↗

Quantified Fast Frequency Response of Inverter-Based Resources for Bulk-Power System Study

Quantifying fast frequency response (FFR) of inverter-based resources (IBRs) is crucial for robust frequency regulation, managing resources, and improving system reliability in the power grids with high penetration levels of IBRs. This paper proposes a concept of frequency response scheme that its response is quantifiable and applicable to the generic IBR models. To achieve this, a stepwise-energy function is derived as a control module by considering operational constraints of IBRs. Then the module is implemented along with generic IBR models in electromagnetic transient (EMT) and electromechanical-based software. To quantify the FFR, the implemented module calculates available incremental active power for a specific time duration. This energy profile is being updated depending on IBR’s operating conditions and is provided into a power grid upon detecting a frequency event. Thus, due to this characteristic, this scheme can quantify the FFR and enable applicable IBRs to provide their available headroom within frequency arrest period. Thereby, this scheme can help estimate IBRs’ frequency response and is more effective in improving the initial frequency response than frequency-dependent control schemes: rate-of-change-of-frequency based and droop-based control schemes. The performance of the proposed scheme was tested under different IBR penetration levels using PSLF and PSCAD simulators.

Kim, Jinho↗

Optimal Droop Setting for Congestion Reduction in a 100% Grid-Forming Inverter-based Power System

he high penetration of inverter-based resources (IBRs) introduces new challenges to power systems due to the complex inverter control. However, IBRs can be configured to maximize their benefits to improve system resilience and reliability. This paper proposes a steady-state optimization model that aims to mitigate transmission congestion in a 100% grid- forming (GFM) IBR-based power system. This goal is achieved by determining the optimal droop settings for the GFM IBRs under different congestion conditions due to renewable energy and load variations. The numerical solution is rigorously verified by a high-fidelity model of the IEEE 39-bus test system with detailed GFM IBR control in the time-domain electromagnetic transient (EMT) simulation tool PSCAD. The numerical solution and simulation results show a significant congestion reduction while meeting all other operating requirements. It is also observed that the numerical solving time is substantially less compared to the EMT simulation time.

Nguyen, Quan H.↗

A new HVdc Substation Architecture with Higher Power Transfer Capability

The power transferred through high voltage direct current transmission (HVdc) systems is increasing with increased resilience and reliability needs as well as large scale deployment of renewable energy systems. In this paper, a new HVdc substation (SS) architecture with higher power transfer capability is proposed. The HVdc converters or valve groups (VG) are connected in series and parallel fashion such that the total power rating of the SS is increased. The control challenges associated with such SS architecture are identified and appropriate control modifications are proposed. The same is verified through PSCAD based simulations.

Jaldanki, Sreenivasa↗

Benchmark High-Fidelity EMT Models for Power Grid with PV Plants

In recent times electromagnetic transient (EMT) modeling tools have been identified as one of the most important requirements in replicating, analyzing, and investigating the dynamics of the power grid with photovoltaic (PV) plants. However, there are no benchmark models for power grid with PVs to investigate emerging challenges with higher penetration of PVs (like trips and momentary cessations during faults from a region far away). To this end, in this paper, synthetic benchmark high-fidelity EMT dynamic models of power grid with large-scale PV plants are presented. The models are developed in PSCAD and PSCAD/Fortran. Simulation results for different use cases (events) and scenarios are presented.

Marthi, Phani Ratna Vanamali↗

Transient Stability Analysis of Direct Droop-Controlled Grid-Forming Inverter with Current Clipping as Current Limiting Control

This paper investigates the transient stability of the direct droop-controlled grid-forming (GFM) inverter which employs the current clipping-based approach for overcurrent limitation. An equivalent circuit model of the direct-droop GFM inverter with current clipping is developed for this purpose. It is shown that during overcurrent conditions, the GFM inverter with current clipping acts as a voltage source with a virtual resistance behind the inverter filters. To compute the parameters of this virtual resistance an analytical expression is given in the paper. Then utilizing the developed circuit, a criteria to exit current limiting during post-fault conditions is given. The developed analytical approaches are then validated through electromagnetic transient (EMT) simulation results in PSCAD software and finally concluding remarks are drawn.

Mohiuddin, Sheik Mohammad↗

Phasor-Domain Modeling of Inverter Based Resources Considering Unbalanced Grid Faults

A significant increase in inverter-based distributed energy resources (DERs) is expected in distribution systems of the near future. The latest phasor modeling approach of DERs with emerging control technologies can capture relevant dynamics in large-scale three-phase distribution systems with unbalanced construction. However, there is a lack of appropriate phasor models to deal with unbalanced fault scenarios. As such, this paper describes per-phase phasor modeling approach appropriate for unbalanced grid disturbance studies in distribution systems with high penetration of DERs. The overall modeling performance of representative DERs is simulated in phasor domain GridLAB-D environment and validated against controller hardware-in-the loop (CHIL) testing or electromagnetic transient (EMT) based switching model simulation in PSCAD with test cases including different unbalanced grid faults. The high accuracy retained from the simulation verifies the effectiveness of the proposed phasor modeling approach considering interactions between positive and negative sequence signals.

Chen, Zhe↗

A Testing Framework for Grid-Forming Resources

This paper presents a testing framework for grid-forming (GFM) resources. First, it analytically derives in the frequency domain the active and reactive power response of an ideal voltage source with a reactor. These transfer functions are then used to quantify the voltage source behavior expected from a GFM inverter within subtransient timescales (5-15 cycles) following a grid disturbance. The paper also shows that the testing of a GFM inverter might require a reactor of an appropriate size between the inverter and the grid simulator used for the inverter testing. Finally, the paper presents a systematic approach for developing specifications for GFM resources using active and reactive power response frequency scans. The testing framework and results presented in this paper are demonstrated using EMT-PSCAD simulations of a 1-MW GFM inverter.

frequency scans↗

Dynamic Capabilities of an Energy Storage-Embedded DFIG System

Power electronic-based wind turbine generators (WTGs) are capable of providing inertial response to the grid by releasing kinetic energy from the turbine blade; thus, as conventional power plants are retired, the reduction of online inertia can be compensated by designing frequency controls for the WTGs. Deployment of energy storage technology for renewable generations has been increased to have the renewables centralized with a system operator as an independent power supply by making up for their nature of generation. In addition, the cost of energy storage has dropped over time and global research activities on energy storage have been funded by private industries and governments. This paper investigates the opportunity of deploying an energy storage on a doubly fed induction generator (DFIG)-based WTG to respond to the system frequency, and then explores dynamic capabilities of the energy storage-embedded DFIG to boost its contribution while the frequency response is being provided by the power system's online inertia; thus, enabling an effective delivery of ancillary services to the system. To do this, the dynamic models of DFIG and energy storage are combined and simulated under the different operating conditions of a DFIG, such as subsynchronous, synchronous, and supersynchronous operations, using the PSCAD.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Performance Testing and Assessment of Protection Scheme Using Real-Time Hardware-in-the-Loop and IEC 61850 Standard

The main challenge of the microgrid is to design a suitable protection scheme due to the complexity of the architecture of the microgrid. The importance of the proposed protection technique is threefold. First, it presents a co-simulation platform to integrate between a simulated model on power system computer aided design (PSCAD)/real time digital simulator computer aided design (RSCAD) software’s and physical devices schweitzer engineering laboratories (SEL) 421-7 relays to protect the microgrid that includes different resources connected based on inverter interface. Second, it presents a comprehensive hardware/software setup to test the protective relays in a closed loop system and shows how to configure the protective relay’s International Electrotechnical Commission 61850 communications. Third, IEEE 1588 standard is used to provide sub nanoseconds latency between the simulated model that emulated on real time digital simulator (RTDS) and the external devices. Also, the measurement signals are synchronized between RTDS and the external devices using giga-transceiver synchronization card (GTSYNC) interface card and SEL-2488 satellite-synchronized network clock. The results showed that the co-simulation infrastructure introduces a highly dependable design, analysis, and testing environment for cyber and physical data flow in the system. Besides that, the voltages at ac/dc sides and frequency at fault condition were maintained due to the energy storage device contributions at different modes of operation.

42 ENGINEERING↗

A Two-Stage Current Limiting Control Strategy for Direct-Droop-Controlled Grid-Forming Inverters

This paper presents a two-stage current limiting control strategy with fault ride-through capability for the direct-droop-controlled grid-forming (GFM) inverters. The proposed approach comprises Stage 1 and Stage 2 current limiting controls. During faults, Stage 1 current limiting control instantly clamps the inverter output current magnitude to its maximum transient limit by blocking the switching pulses to the insulated-gate bipolar transistors (IGBTs) with the help of a hysteresis loop control, and Stage 2 current limiting control limits the inverter output current magnitude to its steady-state limit by regulating the amplitude and frequency of the modulating waveform utilizing the active and reactive current limiting control loops. By implementing the current limiting actions in two stages, this approach can effectively limit the over-current within a few cycles after the fault occurrence and ensure synchronism to the grid after long-term fault events. The efficacy of the proposed control approach is validated through electromagnetic transient (EMT) simulation results conducted on a single GFM inverter-based test system and the IEEE 39-bus test system with multiple GFM inverters in the PSCAD platform.

Mohiuddin, Sheik Mohammad↗

Machine Learning-Assisted Stability Boundary Determination of Multiport Autonomous Reconfigurable Solar Power Plants

The multiport autonomous reconfigurable solar (MARS) power plant is a promising solution to integrate renewable resources and energy storage systems into the alternating current (ac) power grid and an high-voltage direct current (HVdc) link. In the MARS system, various input power sources are connected to the individual submodules (SMs) through direct current (dc)–dc converters. However, the presence of external power sources can result in unbalanced capacitor voltages of SMs, thereby violating stability constraints under multiple/diverse operating conditions. This article aims to address the gap by accurately determining the stability boundary of the MARS system. As such, a novel machine learning (ML)-assisted energy balancing control (EBC) criterion is proposed. Further, in conjunction with a refined EBC, this approach ensures balanced capacitor voltages across various types of SMs, significantly enhancing the overall system efficiency. The proposed EBC criterion effectively controls EBC activation and deactivation, achieving remarkable accuracy. Both power systems computer aided design (PSCAD)/electromagnetic transients including direct current (EMTDC) simulations and control hardware-in-the-loop (cHIL) tests are conducted to validate the feasibility and efficiency of the proposed method. By combining the EBC and ML-assisted EBC criterion, efficient energy management is achieved for systems featuring multiple input power sources, such as MARS. This approach enables the system to fully exploit its potential across an expanded operational range while upholding high-efficiency standards.

14 SOLAR ENERGY↗

Dynamic Modeling of Sequential Service Restoration in Islanded Single Master Microgrids

This paper presents a methodology for generating restoration sequences in distribution systems and microgrids with emphasis on deriving optimal switching times for remote control switches (RCS). Microgrid architecture considered are assumed to be operating in islanded single master mode. Control methods for handling the unbalance inherent in distribution systems using single-phase controlled PQ inverters were developed and incorporated in the proposed method. The problem of considering simultaneously both energy optimization and dynamic stability of the system, which is lacking in existing methods, was addressed by studying the transient behavior of microgrids based on extended EMTP simulations and then approximate and incorporate these behaviors into the optimization formulation for restoration. The approach is based on multi-objective optimization of final restored load and total restoration time. The methodology was studied on a modified IEEE 123 node test feeder. An EMTP simulation in PSCAD of the formed microgrids was used to validate the accuracy of the dynamic and steady-state characteristics of the resulting systems. By considering the transient behavior of DGs during restoration, a better restoration sequence that does not trigger protection relays could be realized.

42 ENGINEERING↗

Distributed Small-Signal Stability Conditions for Inverter-Based Unbalanced Microgrids

The proliferation of inverter-based generation and advanced sensing, controls, and communication infrastructure have facilitated accelerated deployment of microgrids. A coordinated network of microgrids can maintain reliable power delivery to critical facilities during extreme events. Low-inertia offered by the power-electronics–interfaced energy resources, however, can present significant challenges to ensuring stable operation of the microgrids. In this work, distributed small-signal stability conditions for inverter-based microgrids are developed that involve the droop-controller parameters and the network parameters (e.g. line impedances, loads). The distributed closed-form parametric stability conditions derived in this paper can be verified in a computationally efficient manner, facilitating reliable design and operations of networks of microgrids. Dynamic phasor models have been used to capture the effects of electromagnetic transients. Furthermore, numerical results are presented, along with PSCAD simulations, to validate the analytical stability conditions. Effects of design choices, such as the conductor types, and inverter sizes, on the small-signal stability of inverter-based microgrids are investigated to derive useful engineering insights.

24 POWER TRANSMISSION AND DISTRIBUTION↗

From Event Data to Wind Power Plant DQ Admittance and Stability Risk Assessment

This paper presents a dynamic event data-based stability risk assessment method for power grids with high penetrations of inverter-based resources (IBRs). This method relies on obtaining the IBRs' DQ admittance through dynamic event data and computing the system's eigenvalues based on the admittance models. Two critical technologies are employed in this research, including time-domain and frequency-domain data fitting and dq-frame voltage and current signal derivation. The first technology is key to obtaining the s-domain expressions from the transient response data, and the s-domain DQ admittance model from the frequency-domain measurements. The second technology is key to obtaining the dq-frame voltage and current signals from either the three-phase instantaneous measurements or the phasor measurement unit (PMU) data. The method is illustrated using data generated from a Type-4 wind power plant modeled in PSCAD. This paper demonstrates the technical feasibility of the proposed approach.

17 WIND ENERGY↗