Quantitative Metrics for Grid Resilience Evaluation and Optimization

Power system resilience has become a critical topic in recent years because of the increasing trend of extreme events and the growing integration of intermittent renewable energy sources. To enhance grid resilience against high-impact, low-frequency events, two questions should be answered: how to quantify the resilience of a given grid and how to incorporate the quantification into power system planning, operation, and restoration. Here this paper develops a new set of quantitative metrics with clear physical interpretation to comprehensively evaluate power system resilience. Using microgrids as an example, an event-based corrective scheduling (ECS) model and an online model predictive control (OMPC) model are developed to integrate the proposed quantitative resilience metrics into power system optimization models for resilience enhancement. The ECS model employs extreme event data to investigate the optimal restoration solution and to help microgrid operators prepare to respond to similar events. The OMPC model provides online decision-making support for operators to handle ongoing outages in the most resilient fashion. The effectiveness and superiority of the proposed quantitative resilience metrics and the resilience enhancement models are demonstrated through simulations and comparative studies on an IEEE test feeder and a real distribution feeder in Southern California.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A tool for assessing demand side management and operating strategies for isolated microgrids

Globally, power system operators are exploring ways to leverage the capabilities of smart meters to implement fine-grained demand side management (DSM). Here this paper presents a new simulation tool to evaluate operating strategies for smart-meter-enabled (SME) islanded microgrids being advanced for sustainable rural electrification in emerging economies. Based on MATLAB/Simulink, the tool's component-level models of small microgrids can be easily configured. Alternative rule-based operating strategies are implemented with controllable supply and storage components as well as other components driven by external factors (e.g., weather and time of day). To account for the wide range of possible operating conditions in real-world applications, statistical metrics can be evaluated using Monte Carlo (MC) methods based on user-defined, time-dependent probability distributions for demands, supplies, and environmental variables. Features of the tool are demonstrated with case studies for a representative microgrid in rural Rwanda.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analysis of Grid-Forming Inverter Controls for Grid-Connected and Islanded Microgrid Integration

Autonomous grid-forming (GFM) inverter testbeds with scalable platforms have attracted interest recently. In this study, a self-synchronized universal droop controller (SUDC) was adopted, tested, and scaled in a small network and a test feeder using a real-time simulation tool to operate microgrids without synchronous generators. We presented a novel GFM inverter control adoption to better understand the dynamic behavior of the inverters and their scalability, which can impact the distribution system (DS). This paper provides a steady-state and transient analysis of the GFM power inverter controller via simulation to better understand voltage and frequency stabilization and ensure that the critical electric loads are not affected during a prolonged power outage. The controllers of the GFM inverter are simulated in HYPERSIM to examine voltage and frequency fluctuations. This analysis includes assessing the black start capability for photovoltaic microgrids, both grid-connected and islanded, during transient fault conditions. The high photovoltaic PV penetration levels open exciting opportunities and challenges for the DS. The GFM inverter control demonstrated appropriate response times for synchronization, connection, and disconnection to the grid. The DS has become more resilient and independent of fossil fuels by increasing the penetration of inverter-based distributed energy resources (DERs).

Ward, Laura (ORCID:0000000345501581)↗

Community Microgrid Assistance Partnership (C-MAP) [Slides]

This informational webinar, held on Nov. 11, 2024, covered the structure, technical focus, and eligibility criteria for the first Request for Proposals (RFP) released by the Community Microgrid Assistance Partnership (C-MAP). Eligible communities are invited to propose a community-based microgrid development or improvement project for funding and/or technical assistance. C-MAP is a program led by the U.S. Department of Energy Office of Electricity with management and coordination by the National Renewable Energy Laboratory. C-MAP will bring together many of the organizations that are working to understand, improve, and implement advanced microgrid energy systems in underserved and Indigenous communities in remote areas, facilitating a new forum for engagement and collaboration. Wraparound services from regional organizations will support the participating communities in microgrid operations as it relates to advancing their energy goals.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Variable frequency response testbed to validate protective relays up to 20 kHz☆

Microgrids operate in islanding or utility grid mode. In islanding mode, distributed energy sources with power electronics inverters can generate fault currents over a wide range of frequencies. To gain a better understanding of the nature of these events, it is crucial to measure currents at frequencies of up to 20 kHz at transient states with protective relays. Protective relays at these frequency responses should be tested prior to being installed in microgrids. However, testing at high-frequency currents cannot be done with Relay Test Equipment (RTE) that generate signals up to 50th Harmonic for 60 Hz (3 kHz). In this study, a frequency response method and testbed for high-frequency currents of up to 20.16 kHz was developed and tested. The testbed utilized a RTE and High-Frequency Power Source/ Amplifier. Furthermore, frequency relay experiments were run at frequencies of up to 1 and 20.16 kHz at a current magnitude of 0.1 and 0.5 A, respectively. The events were collected, and the current magnitude and frequency were plotted at time and frequency domain, respectively. The study of current magnitude and frequencies of up to 20.16 kHz for two overcurrent relays was performed and validated the variable frequency testbed and methodology.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Deep Reinforcement Learning for Microgrid Cost Optimization Considering Load Flexibility

This paper proposes a novel Soft-Actor-Critic (SAC) based Deep Reinforcement Learning (DRL) method for optimizing the cost of microgrid operation by leveraging load flexibility. The proposed SAC-DRL method is designed to coordinate the control of distributed energy resources (DERs) and flexible load, addressing practical energy billing formation by power distribution utilities. Key contributions include an innovative reward function to mitigate sparse reward challenges and a mixed control strategy for discrete and continuous variables, ensuring radial network topology and minimizing power loss. We evaluate the proposed method on the model of a real microgrid located in Southern California, U.S.. The SAC-DRL model is tested to demonstrate its efficacy in reducing grid dependence, optimizing resource use, and minimizing costs. The results highlight the potential of DRL in modern energy systems, offering a sustainable and economically efficient solution for energy management in microgrids.

deep reinforcement learning↗

Converter-Interfaced CHP Plant for Improved Grid-Integration, Flexibility and Resiliency

GE Research and its partner GE Renewables have proposed the use of an interface converter solution to increase the penetration of small to medium-sized CHP (1MWe to 20MWe) into distribution grids and improve their flexibility and grid support capability. Indeed, the proposed interface converter solution thanks to presence of the grid-ready inverter, allows to streamline the compliance to grid codes requirements, reduce the interconnection delays and costs and ultimately one of the main barriers for CHP adoption by commercial and industrial facilities. An additional benefit provided by the interface converter is the use of the grid-ready inverter for reactive power which eliminates the need of sizing the generator for that capability. These two benefits highly favor the economic feasibility of converter-interfaced CHP. Five user cases, each in one of the leading U.S states for CHP potential reported by the DOE in its estimation of the U.S Technical Potential of CHP, were selected to compare the economic performances of converter-interfaced CHP as compared with directly-coupled. They include a college campus in California, a hospital in New York, a water reclamation plant in Texas, a hotel in Minnesota, and a large office building in Pennsylvania. Results showed that, the presence of the interface converter allows to increase the return on investment (ROI) by 0.5 to 2 percentage points in most of the cases (4 of 5). Indeed, the interface converter by shortening the interconnection process allows to accelerate revenues while reducing interconnection costs. Added to the reduced cost of the required generator these savings trade favorably the capital cost of the converter. The analysis also showed that the profitability of the converter-interfaced CHP is highly sensitive to the energy price, interconnection delay, and converter cost. However, it appears that if the interface converter can shorten the interconnection process by at least 6 months, adopting this solution will be more economically viable than directly-coupled configuration in almost all the +23,000 sites of the U.S Technical Potential CHP. The evaluation of the benefits of a converter-interfaced CHP also showed that it enables higher ROI when coupled with other distributed energy resources (DER) such as battery energy systems (BESS) or solar photovoltaic (PV). Indeed, in those scenario, the grid-ready inverter included in the interface converter eliminates the need of separate inverters if DC-coupling is used. On the technical performance, it has been verified that the presence of the interface converter allows to reduce by 70% to 80% the CHP short-circuit contribution to grid faults. This not only reduces the mechanical and thermal stresses exposed to the CHP electrical components but also increases the grid hosting capacity which ultimately enables higher penetrations CHP. Another key benefit of the interface converter validated with hardware-in-the-loop simulations and testing is its superior capability for reactive power support. Indeed, using a power hardware testbed with two +700kW inverters configured in back-to-back, a microgrid controller and actual facilities loads it was demonstrated that the presence of the interface converter can help maintain a power factor near ~1 or regulate the voltage to ~1.0pu at the point of common coupling. This benefit can be highly valuable if in the future, due to higher penetration of renewable distributed energy resources (DER), utilities start billing demand charge based on kVA instead of kW as currently. It was also validated that converter-interfaced CHP can dispatch heat and power commands and seamlessly switch between the two modes while consistently controlling the power factor or voltage at PCC. Indeed, the power hardware testing showed that grid-connected converter-interfaced CHP can follow either the power or heat demand while maintaining a unity power factor at converter output. This research proved that the adoption of an interface converter as the solution for interconnection of CHP system into the distribution grid can greatly improve the economic feasibility of small to medium-sized CHP as well as the plant power quality, flexibility and resiliency. Additionally, it allows increased penetrations of CHP into the distribution grid, extends their grid support capability, and facilitates the integration of BESS and PV DER by streamlining their collocation within the same facilities. This ultimately provides an opportunity for commercial and small industrial facilities in the U.S to accelerate their energy transition thanks to the high energy efficiency of CHP systems and its reliable, flexible, and resilient microgrid operation when interconnected with an interface converter.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimal Renewable Resource Allocation and Load Scheduling of Resilient Communities

This paper presents a methodology for enhancing community resilience through optimal renewable resource allocation and load scheduling in order to minimize unserved load and thermal discomfort. The proposed control architecture distributes the computational effort and is easier to be scaled up than traditional centralized control. The decentralized control architecture consists of two layers: The community operator layer (COL) allocates the limited amount of renewable energy resource according to the power flexibility of each building. The building agent layer (BAL) addresses the optimal load scheduling problem for each building with the allowable load determined by the COL. Both layers are formulated as a model predictive control (MPC) based optimization. Simulation scenarios are designed to compare different combinations of building weighting methods and objective functions to provide guidance for real-world deployment by community and microgrid operators. The results indicate that the impact of power flexibility is more prominent than the weighting factor to the resource allocation process. Allocation based purely on occupancy status could lead to an increase of PV curtailment. Further, it is necessary for the building agent to have multi-objective optimization to minimize unserved load ratio and maximize comfort simultaneously.

model predictive control↗

Distributed Coordination of Demand-side Flexible Resources in Microgrid with All-Time Feasibility

The prevalence of distributed renewable generators motivates microgrid operators to exploit demand-side flexible resources (DFRs). Due to their dispersed nature, distributed DFR coordination has been a vibrant research area, while there are several issues awaiting to be addressed. On one hand, DFR power is internally coupled through power flow, while DFR usually cannot access grid information. On the other hand, in time-restricted scenarios, solution feasibility cannot be guaranteed by conventional dual-based algorithms. To fill these gaps, we propose a distributed DFR coordination framework with all-time feasibility. The proposed framework accounts for the distinct access of microgrid entities to grid information. A distributed and all-time feasible algorithm is proposed for optimal DFR coordination, which allows DFRs to make local decisions without violating constraints throughout iterations. The effectiveness of the proposed algorithm is demonstrated through case studies. The impact of peer-to-peer communication links on algorithm convergence is also investigated, which emphasizes the balance between communication investment and algorithm performance.

Li, Hongyi [Iowa State Univ., Ames, IA (United Sta↗

PV Generation and Load Forecasting for Adjuntas PR Community Microgrids

Existing frameworks to forecast time-series photovoltaic (PV) output power and consumer load for microgrid operations and controls assume a near-continuous availability of real-time input features from the field assets such as PV inverters, energy meters, and weather station. These incoming data points are used to periodically retrain models and update forecast snapshots over a moving horizon window, be it one hour-ahead, one-day ahead, or one-week ahead. However, such frameworks are not resilient to disruptions in data availability caused by losses in communications between the field sensors and data loggers. Hence, there is a need for programs that assume no availability of real-time microgrid asset data and still make reliable forecasts that can be used for decision-making. Such programs would be apt to function in extreme weather events such as hurricanes and would use lightweight recursive time-series models to independently forecast solar irradiance and ambient temperature, then compute PV power from those forecasts, as well as independently forecast consumer load. The codebase performs forecasting for the scenario of when the microgrid does not have a reliable access to forecasts or real-time observations of solar irradiance (I) and ambient temperature (AT) and load (Load) to be able to adequately forecast, in real-time, the PV power production or a business' load. In this case, using historical values of PV power and load, a univariate forecasting of generation and consumption are respectively made. The use-case in particular has two sub-scenarios: one, a normal 7-day ahead forecast where the unavailability of real-time data is assumed due to infrastructure issues such as loss of communication or sensor maintenance or service downtimes. Whereas a hurricane-caused unavailability of real-time data requires a second model trained specifically on historical hurricane days to be able to capture the extreme day behavior of generation in particular, and load if applicable. A gradient boosted regression tree comprises an ensemble of additive models that map between the input of historical values (be it irradiance, temperature, or load) and their corresponding output forecasts of a given horizon such that the individual learner predictions are summed up over the total number of such learners in the ensemble to produce an aggregate forecast. A weighting mechanism is applied to the training data in each iteration, where actual and forecast values are compared to penalize incorrect forecasts by increasing the weight and reducing it to reward correct forecasts. The code's benefits are that it: (a) accounts for a contingency where communication loss renders newly measured real-time data unavailable for model tuning and snapshot updates; (b) presents blind forecasting that recursively determines the next time-step value in a horizon using the forecast of the same attribute from a prior step; and (c) employs lightweight models that, once trained, can reliably generalize for different horizons, which make them suitable for enhancing the resilience of field microgrids prone to extreme events that encounter disruptions to data availability.

Sundararajan, Aditya [Oak Ridge National Laborator↗

Allocation Mechanisms in Rationed Markets

Economic theory has come to play an important role in power system operations through the design of wholesale markets that are central to their operation. Furthermore, transactive energy places economic theory as a cornerstone in its operational concept as it seeks to integrate the technical needs of the power system with the preferences of its participants. Traditionally the mechanism employed is the continuous double-auction but de-pending on the circumstances the power system find itself in, this mechanism may or may not be the most appropriate, i.e. a one-size fits all market institution cannot be recommended without regard for the features of the underlying trading environment. This paper seeks to explain the economic rationale that guides the choice of a market institution and takes recourse to a theoretical demonstration in the context of a rationed power system scenario where demand exceeds generation (due to any number of events such as outages, microgrid operation, etc) and electrical energy must be rationed to better understand which types of mechanisms are most appropriate.

transactive energy, power system economics, econom↗

Networked Microgrids for Improved Resilient Operation: A Case Study in Adjuntas Puerto Rico

This paper presents a case study of a network microgrid orchestrator designed to allow coordinated operation of microgrids. Through Control Hardware in the Loop (CHIL), the proposed microgrid orchestrator was validated using, as case study two community-owned microgrids in Adjuntas, Puerto Rico. These two microgrids in Adjuntas were designed to provide affordable and reliable access to electricity to 14 businesses located in the town square. In its current design, these two microgrids operate independently from each other. This paper studies how networking them would increase their resiliency metrics while operating as an island. A distributed optimization is implemented in the microgrid orchestrator due to its superior scalability compared to centralized approach as well as to maintain data privacy. Two operational modes are considered in this study to showcase the advantages of networking microgrids: a) normal island, and b) degraded island. CHIL simulations are performed to validate the proposed microgrid orchestrator. CHIL results show meaningful resiliency improvements obtained by networking microgrids during contingencies such as loss of PV generation.

Ferrari Maglia, Max↗

Hydrogen Carriers for Renewable Microgrid System Applications

Utility-scale energy storage can help improve grid reliability, reduce costs, and promote faster adoption of intermittent sources such as solar and wind. This paper analyzes the technical aspects and economics of standalone microgrids operating on intermittent power combined with hydrogen energy storage. It explores the feasibility of using dibenzyltoluene (DBT) as a liquid organic hydrogen carrier to absorb excess energy during periods of high supply and polymer electrolyte fuel cells to generate electrical energy during periods of low supply. A comparative analysis is conducted on three power demand scenarios (industrial, residential, and office), in conjunction with three alternative energy sources: solar, wind and wind–solar mix. A mixed system of solar and wind energy can maintain an annual average efficiency above 70%, except for residential power demand, which lowered the efficiency to 67%. A balanced combination of wind and solar power was the most cost-effective option. The current levelized cost of electricity (LCOE) for industrial power demand was estimated to 15 ¢/kWh, and it is projected to decrease to 9 ¢/kWh in the future. For residential power demand, the LCOE was 45% higher due to the demand profile. In comparison, battery storage is significantly more expensive than hydrogen storage, even with future cost projections, increasing the LCOE between 60 and 120 ¢/kWh.

PEM electrolysis↗

Novel Power-Hardware-in-the-Loop Interface Method for Grid-Forming Inverter Systems

Power-hardware-in-the-loop (PHIL) simulations of grid-forming (GFM) inverter systems facilitate the testing of drastic scenarios, such as on-grid to off-grid transitions and islanded microgrid operations without a stiff grid. To the authors’ best knowledge, most studies in the literature focus on PHIL simulations for grid-following inverter systems. Only a few studies focus on GFM inverters, and those are challenging and problematic, especially for high-power applications. This article proposes a novel PHIL simulation platform that enables interfacing high-power GFM inverter systems. The paper proposes the concept of a virtual GFM inverter as a part of the proposed PHIL interface. This addition of a virtual GFM inverter in the PHIL interface expands the conventional ideal transformer model (ITM) method and enables it to overcome the issues of instability of existing ITM methods. In the validation stage, a PHIL experiment is conducted on a three-phase, 480-V, 125-kVA GFM inverter system with the proposed interfacing method. The results corroborate that the proposed PHIL simulation method performs well and is stable for GFM inverter systems.

droop control↗

Scalable, Physical Effects Measureable Microgridfor Cyber Resilience Analysis

SPEMMCRA provides a low-cost simulated method to provide for testing of control theory and cybersecurity approaches to microgrid implementations. Specifically, this physics-based approach provides realistic responses to compare control strategies in simulation, but also to demonstrate actions that can or cannot be taken in taking cybersecurity actions . As communications interfaces or other actions are taken that affect the flow of data, SPEMMCRA can show whether the microgrid operation is adversely affected by what is intended to mitigate a cybersecurity event.

Rieger, CraigG↗

Sensors with Intelligent Measurement Platform and Low-cost Equipment (SIMPLE) for Monitoring and Control of Medium Voltage Distribution Systems with High Penetration of Intermittent Distributed Energy Resources

The primary focus of the SIMPLE project was to develop, commission, test and introduce intelligent voltage and current sensor platform with enhanced characteristics (accuracy, bandwidth and harmonic range) and high measurement granularity for medium voltage distribution system monitoring, protection and control. The enhancements incorporated existing (commercially available) sensors and made them suitable for applications such as voltage regulation, frequency support, fault detection and location, distribution system state estimation, power quality measurements and electrical distribution network topology processing. The development of the intelligent sensor platform was driven by the need for high-fidelity monitoring and control of medium voltage distribution feeder to enable higher penetration of renewable resources and microgrid operation.

14 SOLAR ENERGY↗

Security Enhancements for Distributed Energy Resource Systems Interconnected with Distribution Networks: Final Technical Report

The revised IEEE 1547 Standard defines new complex communication-adjustable voltage and frequency regulation and ride-through characteristics, while maintaining the general antiislanding requirement for unintentional islanding situations. Unintentional islanding is prohibited while intentional islanding is specifically allowed, thus effectively enabling microgrid operation mode. Further, IEEE 1547-2018 Standard introduces new requirements in terms of interoperability so that the DER plant/circuit segments may be seamlessly integrated with the utility networks but at the same time become vulnerable to a cyber-attack. Traditional cybersecurity measures including encryption, authentication and role-based access control may not be fully implementable to all communication protocols specified in the IEEE 1547 Standard. Therefore, in this project we have identified, researched, implemented and tested several cyberphysical approaches that rely mostly on the behavior of the DER circuit and may help with validating the incoming command and control action potentially coming through an insecure communications channel. Additionally, we have built semantic models and communications profiles for DER facilities and have implemented lightweight IEC 61850 based publisher-subscriber GOOSE messaging mechanism, with security extensions in terms of authentication and encryption. The project proposed information models for integration into UCA OpenFMB 2.0 profiles focusing on grid code compliance.

24 POWER TRANSMISSION AND DISTRIBUTION↗