Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “Cascading failures”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 55 records · Page 3

A Methodology to Evaluate the Grid Reliability Impact of Oscillations Induced by Large Loads

The rapid growth of hyperscale AI data centers is bringing renewed attention to the reliability risk that sustained forced oscillations pose to bulk power systems, with cyclic computational workloads emerging as a new forcing source. Unlike the broadband, stochastic disturbances from traditional industrial loads such as arc furnaces, AI training and inference facilities can inject large active power swings concentrated at specific frequencies over extended durations - characteristics that existing grid planning practices do not account for. While the North American Electric Reliability Corporation (NERC) has recognized this gap and called for system-level studies of large load interconnections, no standardized methodology exists to screen, simulate, and quantify these risks at the planning stage. This report presents the Risk Assessment Tool for Large Load-induced Events (RATLLE), a Python-based, publicly available script suite developed at the Pacific Northwest National Laboratory to evaluate bulk power system reliability risks from data center-induced oscillations. RATLLE implements a three-module workflow: a screening module that identifies vulnerable interconnection locations and excitable system modes; a simulation module that models cyclic data center load behavior using a commercial positive sequence simulation platform; and an analysis module that computes risk metrics and generates interactive visualization dashboards. The risk metrics, formulated around simulation observables, map oscillation impacts to a three-stage severity scale spanning latent equipment fatigue through imminent cascading failure. The methodology is demonstrated on two Western Electricity Coordinating Council (WECC) system models: a publicly available 240-bus reduced representation and a detailed 2031 Heavy Winter planning case. Case studies illustrate that even modest 50 MW forced oscillations at resonant frequencies can produce wide-area power swings, N-1 security constraint violations, and cascading generator trips through protection actions - outcomes that would not occur under normal operating conditions without oscillations present. The results underscore the need for standardized oscillation impact assessment in large load interconnection studies and provide a reproducible, extensible framework for utilities to adopt or customize within their existing planning workflows.

Biswas, Shuchismita↗

Identification of Critical Infrastructure via PageRank

Assessing critical infrastructure vulnerabilities is paramount to arranging efficient plans for their protection. Critical infrastructures are cyber-physical systems that can be represented as a network consisting of nodes and edges and highly interdependent in nature. Given the interdependent nature of critical infrastuctures, failure in one node may cause failure in many others resulting in a cascade of failures. In this paper, we propose a node criticality metric that uses Google’s PageRank algorithm to identify nodes that are likely to fail (are vulnerable), nodes whose failure may cascade to many other sites in the network (are important), and nodes that are both vulnerable and important (are critical). We then present a series of experiments to understand how protecting certain critical nodes can help mitigate massive cascading failures. Simulating failures in a real-world network with and without critical node protections demonstrates the importance of identifying critical nodes in an infrastructure network.

Kay, Bill↗

Solar Photovoltaic (PV) Damage Assessment After Typhoon Mawar: Findings and Recommendations for Resilient PV on Guam

A team from the National Renewable Energy Laboratory (NREL) visited Guam in August 2023 to assess failure modes of solar photovoltaic (PV) systems after Typhoon Mawar and to provide recommendations to increase the resilience of PV systems on Guam. The team visited 30 systems: commercial and utility scale, and rooftop and ground-mounted. The team observed systems with no apparent damage, as well as systems that were completely lost. Systems fared very well overall. The average failure rate of rooftop systems was 18%, with a median failure rate of 2%, meaning the few systems that suffered total loss pulled up the average. Only eight 8 of the 25 rooftop systems suffered more than 5% damage. All ground-mounted systems suffered less than 0.5% damage, aside from a carport that lost 16% of its modules. PV systems at Andersen Air Force Base suffered 5% damage on average, with a median system failure of 0.6%. In almost all cases, failures were the result of: (1) Inadequate clamping of the module frame to the mount, (2) Module mounting clamps rotating out of underlying support rail (i.e., T-bolt that rotates free at less than 60 degrees of rotation), (3) An object hitting the panel resulting in a fracture, and in some cases leading to a cascading failure of several more panels, and (4) Excessive tilt angle (in Guam, greater than 5 degrees can be a risk due to wind speed, and power production trade-offs are insignificant).

14 SOLAR ENERGY↗

Resilience of Urban Transport Network-of-Networks under Intense Flood Hazards Exacerbated by Targeted Attacks

Natural hazards including floods can trigger catastrophic failures in interdependent urban transport network-of-networks (NoNs). Population growth has enhanced transportation demand while urbanization and climate change have intensified urban floods. However, despite the clear need to develop actionable insights for improving the resilience of critical urban lifelines, the theory and methods remain underdeveloped. Furthermore, as infrastructure systems become more intelligent, security experts point to the growing threat of targeted cyber-physical attacks during natural hazards. Here we develop a hypothesis-driven resilience framework for urban transport NoNs, which we demonstrate on the London Rail Network (LRN). We find that topological attributes designed for maximizing efficiency rather than robustness render the network more vulnerable to compound natural-targeted disruptions including cascading failures. Our results suggest that an organizing principle for post-disruption recovery may be developed with network science principles. Our findings and frameworks can generalize to urban lifelines and more generally to real-world spatial networks.

54 ENVIRONMENTAL SCIENCES↗

Networked Microgrid Topology Reconfiguration to Promote Fairness in Proactive Load Shedding

Increasing occurrences of natural disasters and grid emergency events consistently challenge the safe and reliable operations of power systems. During such emergency situations, system operators may proactively shed load to mitigate risks. However, uncoordinated implementation of load shedding may disrupt electricity supply and even lead to cascading failures. Meanwhile, it is crucial to address potential biases affecting different customers when executing load shedding. This paper addresses the dynamic topology reconfiguration problem for networked microgrids with distributed energy resources under emergency conditions. Specifically, we propose a novel rolling-horizon optimization model that integrates fairness-aware constraints into the networked microgrid topology reconfiguration. Unlike existing approaches that focus solely on efficiency or apply fairness considerations in static settings, our method explicitly incorporates temporal fairness constraints to restrict repeated or excessive load curtailment for load blocks. Moreover, the fairness-aware constraints are specifically developed for the context of dynamic networked microgrid topology reconfiguration, and are designed to be convex or amenable to linear reformulations, which offers a more tractable alternative to traditional models with non-convex formulations. Numerical studies on a modified IEEE 13-bus system and a larger-sized SMART-DS networked microgrid system demonstrate the performance of the proposed algorithm towards more fairness-aware networked microgrid topology reconfiguration decision-making.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Compressible battery foams to prevent cascading thermal runaway in Li-ion pouch batteries

Lithium-ion battery packs require thermal management to achieve optimum life and safety. This is becoming crucial for battery packs composed of high-energy-density cells. Pouch cells themselves achieve highest packaging efficiency but require additional structural support and thermal management when grouped into modules, especially under abusive conditions such as thermal runaway. Novel foam battery pads have demonstrated to cushion volume changes of pouch cells and are reengineered in this study to mitigate cell-to-cell thermal runaway propagation. The compressible pads are made of polyurethane foams incorporating flame-retardant additives or coatings, including intumescent and fire wall materials. Here their performances were evaluated by conducting nail penetration tests on modules composed of pouch cells at 100% state of charge (SOC), with the foams placed in between the cells. Experimental results show cascading thermal runaway was considerably delayed by polyurethane foams incorporating flame-retardant additives or coatings. Complete prevention of cascading failure was achieved with dense polyurethane foams with multilayered coatings of both fire wall and intumescent materials.

25 ENERGY STORAGE↗

High-Fidelity Multiphysics Modeling of a Heat Pipe Microreactor Using BlueCrab

Researchers who are actively developing nuclear microreactors are planning to employ innovative designs and features using traditional commercial modeling tools that may be inadequate for their design and licensing activities. The codes developed under the U.S. Department of Energy Office of Nuclear Energy Advanced Modeling and Simulation (NEAMS) program provide flexibility in terms of geometry modeling and multiphysics coupling and are particularly well suited for modeling novel microreactor concepts. To test the maturity of these codes, this paper introduces a conceptual heat pipe microreactor (HP-MR) designed to gather various technologies of interest to microreactor developers such as control drums, heat pipes, and hydride moderators. Here, the objective of this effort is to demonstrate NEAMS tools capability to perform high-fidelity multiphysics simulations, using coupled neutronics (via the Griffin code), heat conduction (via the BISON code), heat pipe modeling (via the Sockeye code), and hydrogen redistribution in hydride metal moderator (via the SWIFT code). Codes are coupled in-memory through the Multiphysics Object-Oriented Simulation Environment (MOOSE) framework, which permits flexible multiphysics data transfer schemes. The analysis confirmed two key aspects of the HP-MR concept: (1) its ability to follow the power load requested from the heat pipe and (2) its ability to avoid heat pipe cascading failure unless designed with high power close to operating failure limits of its heat pipes. The developed computational model was distributed publicly on the Virtual Test Bed for training purposes to accelerate adoption by industry and to provide a high-fidelity multiphysics solution for benchmarking against other tools. Additional multiphysics analyses including other transients and coupled physics were identified as necessary future work, together with a focus on validating multiphysics behavior against experiments.

Microreactor↗

Finite-time correlations boost large voltage angle fluctuations in electric power grids

Abstract Decarbonization in the energy sector has been accompanied by an increased penetration of new renewable energy sources in electric power systems. Such sources differ from traditional productions in that, first, they induce larger, undispatchable fluctuations in power generation and second, they lack inertia. Recent measurements have indeed reported long, non-Gaussian tails in the distribution of local voltage frequency data. Large frequency deviations may induce grid instabilities, leading in worst-case scenarios to cascading failures and large-scale blackouts. In this article, we investigate how correlated noise disturbances, characterized by the cumulants of their distribution, propagate through meshed, high-voltage power grids. For a single source of fluctuations, we show that long noise correlation times boost non-Gaussian voltage angle fluctuations so that they propagate similarly to Gaussian fluctuations over the entire network. However, they vanish faster, over short distances if the noise fluctuates rapidly. We furthermore demonstrate that a Berry–Esseen theorem leads to the vanishing of non-Gaussianities as the number of uncorrelated noise sources increases. Our predictions are corroborated by numerical simulations on realistic models of power grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Load Shed Recovery With Transmission Switching and Intentional Islanding Methods After (N-2) Line Contingencies

Changing power system configuration may result in load shed recovery (LSR) because topology change can provide power flow control in meshed network. Some topologies may favor generation redispatch as compared to others and can eliminate line congestion which leads to LSR. One of the known methods for topology change is called transmission switching (TS) and research conducted in the past showed that TS is an effective means of mitigating load shedding. Another method of topology control is intentional islanding (IIS). In this manuscript, we explore IIS as a potential solution for LSR. IIS based on generator coherency has been presented in literature for mitigating cascading failures. However, IIS has not been explored solely as a LSR mechanism. In this paper, we compare the LSR based on IIS with well known LSR algorithm based on TS. The comparison is performed for IEEE 39-bus system and IEEE 118- bus system. The results show that IIS has a potential to perform better than TS in terms of computational efficiency and LSR.

42 ENGINEERING↗

Impact of Load Tap Changer Control Operation Under Microgrid Conditions

Every microgrid is unique in its diversity of assets, operation, and network structure. This uniqueness presents challenges for each microgrid implementation that need to be understood and addressed to prevent power quality concerns, stability issues, and blackouts. In this research work, we present one challenge faced during microgrid operation that could potentially cause a blackout in some microgrid configurations. Through the incorrect operation of the load tap changer controller during an islanding event for a microgrid with generation present on both primary and secondary busses, the primary voltage will increase or decrease beyond allowable bounds, causing a cascading failure. This work presents the issue first with simulation results to demonstrate the phenomenon and then presents results of load tap changer controller operation using a controller-hardware-in-the-loop experiment. Finally, details of the complete sequence of operation and the blackout scenarios are presented and summarized.

blackout↗

A Sequential Model Predictive and Deep Reinforcement Learning-Based Controller for Distribution System Outage Mitigation under Hurricane Events

This paper proposes a proactive outage mitigation framework for power distribution networks to withstand hurricane-induced disruptions. It leverages Model Predictive Control (MPC) to identify safe lines for proactive switching during hurricanes, minimizing the risk of cascading failures and voltage violations. The switching strategies optimized by MPC are sequentially integrated with a Deep Reinforcement Learning agent using the Advantage Actor-Critic algorithm, enabling dynamic line switching to maximize connected buses and minimize voltage violations in real time. Using a probabilistic hurricane model, the framework predicts line failures and adapts to varying conditions to enhance grid resilience. Simulations on the IEEE 123-bus system demonstrate its effectiveness in maintaining high connectivity and minimizing disruptions. Real-time testing with an RTDS confirms the practicality and reliability of the proposed approach.

Selim, Alaa [University of Connecticut]↗

Methods for Analysis and Quantification of Power System Resilience

This paper summarizes the report prepared by an IEEE PES Task Force. Resilience is a fairly new technical concept for power systems, and it is important to precisely delineate this concept for actual applications. As a critical infrastructure, power systems have to be prepared to survive rare but extreme incidents (natural catastrophes, extreme weather events, physical/cyber-attacks, equipment failure cascades, etc.) to guarantee power supply to the electricity-dependent economy and society. Thus, resilience needs to be integrated into planning and operational assessment to design and operate adequately resilient power systems. Quantification of resilience as a key performance indicator is important, together with costs and reliability. Quantification can analyze existing power systems and identify resilience improvements in future power systems. Given that a 100% resilient system is not economic (or even technically achievable), the degree of resilience should be transparent and comprehensible. Several gaps are identified to indicate further needs for research and development.

42 ENGINEERING↗

Perspective—On the Need for Reliability and Safety Studies of Grid-Scale Aqueous Batteries

Li-ion batteries currently dominate electrochemical energy storage for grid-scale applications, but there are promising aqueous battery technologies on the path to commercial adoption. Though aqueous batteries are considered lower risk, they can still undergo problematic degradation processes. This perspective details the degradation that aqueous batteries can experience during normal and abusive operation, and how these processes can even lead to cascading failure. We outline methods for studying these phenomena at the material and single-cell level. Considering reliability and safety studies early in technology development will facilitate translation of emerging aqueous batteries from the lab to the field.

25 ENERGY STORAGE↗

A Review of Resilience and Long-Term Planning in Power and Water Systems in the United States

There is recognition among power and water utilities that the frequency and magnitude of high consequence and low probability events could increase as a result of climate change. The interconnected nature of energy-water systems raises the possibility of cascading failures, increasing complexity and risks. Resilience and long-term planning are important ways of weathering the effects of climate change. First, to understand more about resilience, we reviewed existing literature on resilience definitions, metrics, and modeling, focusing on integrated water-power systems. Second, to understand how resilience and planning are being applied in practice, we interviewed utilities and organized, curated, and synthesized the interview data to arrive at several key findings, which are presented here. We found that there is not a consistent definition for resilience, yet it is something that utilities regularly plan for, often with different names and varying methods/measures. However, there is a tangible shift in the industry towards defining and determining measurable resilience metrics. While the exact metrics are a work in progress, utilities are taking steps forward by (1) putting people and culture at the center of resilience, (2) recognizing their own interdependencies, and (3) pursuing better cross-sector collaboration.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

A Persistence Meter for Nimble Alarming Using Ambient Synchrophasor Data

Persistent oscillations in the power grid are often indicative of fragility, and may be harbingers of systemic or cascading failures. Modernization of the grid, including increased penetration of intermittent renewables and integration of new power electronics, is making the oscillatory swing dynamics of the network both more complex and variable. In this project researchers from the University of Wisconsin-Madison (Bernard Lesieutre, lead), Washington State University (Sandip Roy, lead), and the Electric Power Group (Neeraj Nayak, lead) have developed technologies that monitor persistent oscillations in the grid and provide operators with alarms and analytics when concerning oscillations are detected. Some of the algorithms have already been implemented in EPG’s PGDA software and integrated into their RTDMS system for use in control rooms.

24 POWER TRANSMISSION AND DISTRIBUTION↗

SCEPTRE: A Cyber-Physical Emulation Capability

Cyber-physical systems form a critical but vulnerable backbone to US critical infrastructure. Recent high-profile cyber-attacks have shown the need for increased assessment and hardening of these systems. However, such assessments and investigations into advanced technologies to harden these systems is difficult due to their operational nature. Instead, modeling of these systems is heavily leveraged. Investigation into these complex systems and their potential cascading failures requires comprehensive modeling of both the cyber and physical components of the system. This paper introduces SCEPTRE, an emulation capability to address this need.

45 MILITARY TECHNOLOGY, WEAPONRY, AND NATIONAL DEF↗

Resilience of Interdependent Water and Power Systems: A Literature Review and Conceptual Modeling Framework

As increasing pressures of population growth and climate change arise, water and power systems (WPS) are becoming increasingly interdependent. This interdependency has resulted in an increased potential for cascading failures, whereby the service interruption of one system can propagate to interdependent ones. This paper makes four contributions. First, we present an extensive literature review in the field of integrated water and power resilience, leveraging both institutional and technical literature research landscapes. We compare various modeling approaches used to model interdependent WPS and discuss the different metrics and definitions that are typically employed to quantify and define resilience. Relevant challenges and gaps related to modeling tools and metrics are also discussed, and appropriate recommendations are made. Second, the paper presents a visualization prototype for interdependent WPS to showcase water and power system interdependencies and reveal co-managed resilience strategies that can be used to improve resilience under different types of common threats. Third, we provide a conceptual decision support framework that simultaneously optimizes a portfolio of co-managed resilience strategies in the face of multiple, uncertain threats and addresses WPS interdependencies. Finally, we present future trends regarding digitalization, integrated planning, collaborative governance, and equity needs for building more resilient WPS.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Productivity in an evolutionary space station

Space station productivity is treated from a systems point of view, considering the functions and attributes of space station development, formation, and operation that affect productivity. An optimum planning method is needed to assure that the station will have mission flexibility, technology advancement, maintainability, and evolutionary capability. Advanced technology will be designed into the housekeeping and utility functions of the station. Greater risk taking may be allowed into designs if the potential benefits of the advanced system support the risk, and if the system can be buffered from causing a failure cascade throughout the station. A common data base is needed to store and track all designs, developments, and changes in the station subsystems. Systems that can be automated and free the human inhabitants for more productive work are favored, as are modular components that are highly fault-free. Human control must also be possible, especially during check-out and verification, and also for teaching the automated systems new or modified tasks.

Anderson, J. L.↗