Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “Ventilation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 505 records · Page 28

Inspection and assessment of the H-Canyon ventilation system at the Savannah River Site - 15385

Innovative methods and unique equipment were required to perform the inspection of a large inaccessible sand filter tunnel in an aging facility. Among the singular methods utilized was a specialized robot that addressed the difficulties encountered while performing mandatory structural integrity inspections of the Department of Energy (DOE) Savannah River Site (SRS) H-Canyon Sand Filter Tunnel. There were many unanticipated hazards related to degraded conditions. Novel approaches and support equipment were used, including new measurement techniques, high-strength Kevlar{sup TM} cable, a boom-mounted camera, and a larger, more robust robot. With each evolution, additional analysis mandated requirements and considerations for future inspections. Because this was a visual inspection, many photos were taken to document the mission and lessons learned from the earlier incomplete robotic attempts to inspect these areas. Anyone working with aging facilities that have inaccessible structures, systems and components will find the technical process, with resulting solutions, useful. (authors)

12 MANAGEMENT OF RADIOACTIVE AND NON-RADIOACTIVE W↗

Advancements in the H-Canyon Exhaust Ventilation System Inspections at the Savannah River Site - 16030

A facility safety envelope requires management of activities to ensure no unacceptable radiological or chemical hazards to the public, site worker and environment occur. While appropriate design and construction methods ensure an initial physical plant configuration, what actions must an operating Facility take to ensure the physical plant continues to meet a safety configuration throughout Facility life? While a physical walk down of the plant is a tried and true method to confirm conditions, what other methods must be used when a walk down is not possible? What inspection methods are used when balancing budget pressures against obtaining inspection data? The periodic inspections of the H-Canyon Exhaust Tunnel are performed remotely. The 2015 remote Tunnel inspection has been the most successful inspection to date. This presentation highlights the continued lessons learned with the most recent 2015 remote Tunnel inspection. These lessons learned are applicable to Facilities considering or performing remote inspections. The Recovery Crawler Project was tasked with determining if the 2014 Inspection Crawler could be retrieved, perform the retrieval if feasible and complete the inspection of the remaining sections of the exhaust tunnel that were not previously performed. The objectives for the project were met, the Inspection Crawler was deemed unusable and left in place and the Recovery Crawler performed the complete 143 meters (470 feet) of tunnel inspection and an additional 55 meters (180 feet) of exhaust tunnel inspection not previously completed. The remote inspection of a 60+ year operating Canyon Exhaust tunnel is a complex endeavor requiring close coordination of multiple organizations, adherence to Conduct of Operations, Radiological Safety, Worker Safety, etc. principles as well as alignment with Facility Safety Basis requirements. This paper discusses the challenges, actions required getting ready for the 2015 recovery and continued inspection and the hazards encountered performing the actual recovery/inspection. (authors)

12 MANAGEMENT OF RADIOACTIVE AND NON-RADIOACTIVE W↗

Investigation of potential aerosol transmission and infectivity of SARS-CoV-2 through central ventilation systems

Here we evaluate the concentrations and probabilities of infection for both building interior and exterior exposure sources using a well-mixed model in a connected multizone building. As a central hub of many community and economic activities, buildings provide social connectivity, but the COVID-19 pandemic has reduced social connectivity due to concerns of viral spread within buildings. Although single zone models of infectious spread are well studied, the impact of aerosolized spread of SARS-CoV-2 via air handling systems in multizone buildings remains unexplored. Here we evaluate the influence of filtration, air exchange rates, and the fraction of outdoor air on the probability of infection using the well-known well-mixed modeling approach for a multizone. We find filtration lowers the concentration and probability of infection in both source and connected rooms provided at least some air is recirculated, but that probability is not zero. Filtration has no influence without recirculation or unless the outdoor air contains virus. We find that increasing the air exchange rate removes virus from the source room faster but also increases the rate of exposure to connected rooms. Therefore, slower air exchange rates reduce infectivity in connected rooms at shorter durations, but higher air exchange rates reduce infectivity at longer durations. We further find that when outdoor air is virus free, increasing the fraction of outdoor air is helpful, but, when outdoor air is infective, pathogen exposure inside can persist for hours after a short-term release.

60 APPLIED LIFE SCIENCES↗