At least 451 records · Page 25

Distribution System State Estimation in the Presence of High Solar Penetration

In recent years, the low-to-medium voltage distribution networks are experiencing rising levels of distributed energy resources, including renewable generation, along with improved sensing, communication and automation infrastructure. As such, state estimation methods for distribution systems are becoming increasingly relevant as a means to enable better control strategies that can both leverage the benefits and mitigate the risks associated with high penetration of variable and uncertain distributed generation resources. Primary challenges of this problem include modeling complexities (nonlinear non-convex power-flow equations), limited availability of sensor measurements, and high penetration of uncertain renewable generation. This paper formulates the distribution system state estimation as a nonlinear weighted least squares problem, based on sensor measurements as well as forecasts data (both load and generation). We investigate the sensitivity of state estimator accuracy to (load/generation) forecast uncertainties, sensor accuracy, and sensor coverage levels.

Distribution system state estimation, nonlinear op↗

A Vision for Co-optimized T&D System Interaction with Renewables and Demand Response

The evolution of the power system to the reliable, effi- cient and sustainable system of the future will involve development of both demand- and supply-side technology and operations. The use of demand response to counterbalance the intermittency of re- newable generation brings the consumer into the spotlight. Though individual consumers are interconnected at the low-voltage distri- bution system, these resources are typically modeled as variables at the transmission network level. In this paper, a vision for co- optimized interaction of distribution systems, or microgrids, with the high-voltage transmission system is described. In this frame- work, microgrids encompass consumers, distributed renewables and storage. The energy management system of the microgrid can also sell (buy) excess (necessary) energy from the transmission system. Preliminary work explores price mechanisms to manage the microgrid and its interactions with the transmission system. Wholesale market operations are addressed through the devel- opment of scalable stochastic optimization methods that provide the ability to co-optimize interactions between the transmission and distribution systems. Modeling challenges of the co-optimization are addressed via solution methods for large-scale stochastic op- timization, including decomposition and stochastic dual dynamic programming.

14 SOLAR ENERGY↗

System and component development for long-duration energy storage using particle thermal energy storage

Energy storage, at various scales, will be required to maintain reliable power supply from variable renewable resources, and improve grid resilience. Long-duration energy storage (10-100 h) can substitute baseload coal power generation and increase levels of renewable power supply. Thermal energy storage (TES) has siting flexibility and the ability to store a large capacity of energy, and thus it has the potential to meet the needs of long-duration energy storage. Here, a novel TES system was developed by using solid particles as storage media and charging/discharging electricity from renewable power connected via the electric grid. The particle TES uses low-cost silica sand at 30-40$/Ton that is stable at high temperatures of >1,000 degrees C. Thus, the particle TES system has an overall low storage cost and high thermal-power efficiency. Key components of the system were conceptually designed and modeled for their performance. Conversion of electricity to thermal energy using electric heating can achieve a >98% charging efficiency, and the conversion of thermal energy back to electricity uses an air-Brayton combined power cycle with >52% thermal-to-electricity efficiency at >1,170 degrees C to achieve a >50% roundtrip efficiency after subtracting estimated plant parasitic losses. Laboratory-scale prototypes were fabricated and tested to verify their design approaches and operations relevant to product-scale components.

25 ENERGY STORAGE↗

Optimal Complementarity Analysis of Potential Floating Solar Co-Located With Existing Hydropower Assets Across the Contiguous United States

The U.S. is expected to double its rate of renewable capacity from 2024 to 2030. However, the stochastic nature of renewable energy poses challenges to the operation and reliability of our power grid. The combined generation from renewable energy sources, with dispatchable sources (such as hydropower) operating as a hybrid energy plant, could mitigate this variability. In this paper, the complementarity analysis of selected U.S. reservoirs with existing hydropower assets (EHAs) and potential floating photovoltaics (FPVs) is conducted for the continuous U.S. (CONUS). The optimal FPV capacity for each site is determined by minimizing the variability of the combined output, while adhering to the FPV potential. Our results indicate that over 50% of the analyzed reservoirs achieve a stability coefficient exceeding 0.5, leading to a less-variable output after optimization. Finally, we analyze the complementary hydro-FPV hybrid reservoirs by considering both the Pearson correlation coefficient and the stability coefficient on daily, monthly, and yearly scales. Summaries are included of locations of theoretical FPVs co-located with hydropower plants that exhibit high complementarity based on the selected metrics.

13 - HYDRO ENERGY↗

Control and Coordination of Frequency Responsive Residential Water Heaters

Demand-side frequency control can complement traditional generator controls to maintain the stability of large electric systems in the face of rising uncertainty and variability associated with renewable energy resources. This paper presents a hierarchical frequency-based load control strategy that uses a supervisor to flexibly adjust control gains that a population of end-use loads respond to in a decentralized manner to help meet the NERC BAL-003-1 frequency response standard at both the area level and interconnection level. The load model is calibrated and used to model populations of frequency-responsive water heaters in a PowerWorld simulation of the U.S. Western Interconnection (WECC). The proposed design is implemented and demonstrated on physical water heaters in a laboratory setting. A significant fraction of the required frequency response in the WECC could be supplied by electric water heaters alone at penetration levels of less than 15%, while contributing to NERC requirements at the interconnection and area levels.

Williams, Tess L.↗

Data Driven Approach to Analyzing The Impact of Power Plant Cycling on Air Preheater Degradation and Remaining Useful Life

Due to the increased penetration of renewable energy generation sources, and fluctuations of the oil and gas prices, modern coal burning power plants deal with increased variability in the demand for power generation. These varying demands result in their intermittent under-capacity operation (cycling). Periodical ramping down and back up to follow the daily power demands causes damages to the plant components reducing its operational life. In this paper we analyze the impact of cycling on a rotary Ljungstrom air preheater (APH) unit installed at a coal fire power plant in the US. An inefficient air preheater can significantly impact boiler performance. Due to the repeated boiler’s hot-cold start, the APH experiences fluctuating operating conditions that result in accelerated degradation mechanisms, such as dew-point corrosion, fouling/deposition plugging, and air heater leakage. The analysis in this paper utilizes field data related to APH basket replacement, and the number of cycles experienced by the boiler to model the life expectancy of the baskets. The data-driven model enables preventive maintenance strategies for the APH by predicting how long the APH baskets will last in a probabilistic sense. Furthermore, the analysis showed that an increase in cycling for a fixed operation time can reduce the APH basket remaining useful life by about 30%.

20 FOSSIL-FUELED POWER PLANTS↗

Loads as a Resource: Frequency Responsive Demand

Demand-side frequency control can complement traditional generator controls to maintain the stability of large electric systems in the face of rising uncertainty and variability associated with renewable energy resources. This report presents a hierarchical frequency-based load control strategy that uses a supervisor to flexibly adjust control gains that a population of end-use loads respond to in a decentralized manner to help meet the NERC BAL-003-1 frequency response standard at both the area level and interconnection level. The load model is calibrated and used to model populations of frequency-responsive water heaters in a PowerWorld simulation of the U.S. Western Interconnection (WECC). The proposed design is implemented and demonstrated on physical water heaters in a laboratory setting. A significant fraction of the required frequency response in the WECC could be supplied by electric water heaters alone at penetration levels of less than 15%, while contributing to NERC requirements at the interconnection and area levels.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Low-Cost Sulfur Thermal Storage for Increased Flexibility and Improved Economics of Fossil-Fueled Electricity Generating Units (Final Report)

The US electric grid relies on conventional fossil fuel power plants for reliable and secure power, but these plants suffer from physical and financial strain due to the influx of inexpensive and variable solar and wind electricity. Conventional power plants need to generate electricity flexibly and on-demand to accommodate these renewable resources on the grid. Integrating a low-cost thermal energy storage (TES) gives fossil assets the ability to regulate their output efficiently and optimize the plant operation to maximize revenue in the wholesale electricity market. Element 16’s TES concept uses sulfur, a byproduct of the oil & gas industry, as the storage media that is 10 times cheaper than molten salt used in commercial two-tank TES technology. In this project, the team completed a detailed feasibility and technoeconomic study establishing the impact, cost and performance of molten sulfur TES system integrated with fossil assets.

20 FOSSIL-FUELED POWER PLANTS↗

Selection of Global Climate Model Data for Downscaling With Generative Machine Learning and Use in the Power Planning for Alignment of Climate and Energy Systems Project

The range of results from climate models and scenarios is important to the understanding of uncertainty in power planning analysis. A U.S. Department of Energy-funded analytic project called Power Planning for Alignment of Climate and Energy Systems is developing data and analytic methods to reflect the effects of climate change on key variables for power system planning, as part of the Grid Modernization Lab Consortium. This project will select and prepare global climate model results for use in power system planning models. A related report (Evaluation of Global Climate Models for Use in Energy Analysis) assesses the performance of various global climate models from the Coupled Model Intercomparison Project Phase 6 data archive for their historical skill with respect to energy system performance and for their future projections under multiple climate change scenarios. Building from that report, we describe the selection of a climate scenario (Shared Socioeconomic Pathway [SSP] 2-4.5) and five climate models: TaiESM1, EC-Earth3-CC, GFDL-CM4, EC-Earth3-Veg, and MPI-ESM1-2-HR. We describe the model selection criteria, which were based on the quality of the match between model results under historical conditions and on the representation of the range of future values for several variables. These results will be downscaled via an open-source generative machine learning method called Super-Resolution for Renewable Energy Resource Data with Climate Change Impacts.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

DATA DRIVEN APPROACH TO ANALYZING THE IMPACT OF POWER PLANT CYCLING ON AIR PREHEATER DEGRADATION AND REMAINING USEFUL LIFE

Due to the increased penetration of renewable energy generation sources, and fluctuations of the oil and gas prices, modern coal burning power plants deal with increased variability in the demand for power generation. These varying demands result in their intermittent under-capacity operation (cycling). Periodical ramping down and back up to follow the daily power demands causes damages to the plant components reducing its operational life. In this paper we analyze the impact of cycling on a rotary Ljungstrom air preheater (APH) unit installed at a coal fire power plant in the US. An inefficient air preheater can significantly impact boiler performance. Due to the repeated boiler’s hot-cold start, the APH experiences fluctuating operating conditions that result in accelerated degradation mechanisms, such as dew-point corrosion, fouling/deposition plugging, and air heater leakage.The analysis in this paper utilizes field data related to APH basket replacement, and the number of cycles experienced by the boiler to model the life expectancy of the baskets. The data-driven model enables preventive maintenance strategies for the APH by predicting how long the APH baskets will last in a probabilistic sense. The analysis showed that an increase in cycling for a fixed operation time can reduce the APH basket remaining useful life by about 30%.

Sharma, Himanshu↗

Battery Degradation Modeling in Hybrid Power Plants: An Island System Unit Commitment Study: Preprint

As hybrid power plants (HPPs), such as photovoltaic (PV) and battery combinations, become increasingly important in power systems with high renewable energy penetration to address PV variability and ensure grid stability. This paper focuses on the urgent need to model the coordination between PV and battery systems in HPPs while accounting for battery degradation. We present a generation scheduling model that explicitly incorporates PV-battery hybridization in the unit commitment problem. Moreover, the cost function of the HPP scheduling problem endogenously considers battery degradation with adjustable weights to strike a balance between minimizing production costs and prolonging battery life, particularly when providing energy arbitrage and ancillary services. Using a realistic island system simulation, we demonstrate that accounting for battery degradation in the scheduling problem can significantly extend battery life with only minor additional production costs.

battery degradation↗

Wholesale Electricity Market Design with Increasing Levels of Renewable Generation: Incentivizing Flexibility in System Operations

This paper discusses the importance and challenges of incentivizing flexibility during short-term operations of the bulk power system due to the increasing variability and uncertainty from growing penetrations of variable generation (VG). Operational flexibility can refer to many aspects of a resource's capability to support the power system, such as the speed, range, and duration of power output, as well as the ability to autonomously respond to frequency or voltage changes. Inefficient utilization of existing flexibility, or unwillingness of resources to provide flexibility, can compromise system reliability by not meeting the changing net load, and it can also lead to higher costs when an inefficient use of flexibility resources occurs. There are many existing characteristics of market design that incentivize flexibility in some manner. How they incentivize the provision of flexibility as well as the level of flexibility is still debated. We explore some of these existing market designs, as well as new market mechanisms, such as pay-for-performance regulating reserve and flexible ramping products, that aim to explicitly incentivize the provision of more flexibility to the system, particularly as a result of increasing VG penetration levels.

24 POWER TRANSMISSION AND DISTRIBUTION↗

PV Ramping in a Distributed Generation Environment: A Study Using Solar Measurements; Preprint

Variability in Photovoltaic (PV) generation resulting from variability in the solar radiation over the PV arrays is a topic of continuing concern for those involved with integrating renewables onto existing electrical grids. The island of Lanai, Hawaii is an extreme example of the challenges that integrators will face due to the fact that it is a small standalone grid. One way to study thisproblem is to take high-resolution solar measurements in multiple locations and model simultaneous PV production for various sizes at those locations. The National Renewable Energy Laboratory (NREL) collected high-resolution solar data at four locations on the island where proposed PV plants will be deployed in the near future. This data set provides unique insight into how the solar radiationmay vary between points that are proximal in distance, but diverse in weather, due to the formation of orographic clouds in the center of the island. Using information about each proposed PV plant size, power output was created at high resolution. The team analyzed this output to understand power production ramps at individual locations and the effects of aggregating the production from all fourlocations. Hawaii is a unique environment, with extremely variable events occurring on a daily basis. This study provided an excellent opportunity for understanding potential worst-case scenarios for PV ramping. This paper provides an introduction to the datasets that NREL collected over a year and a comprehensive analysis of PV variability in a distributed generation scenario.

14 SOLAR ENERGY↗

Modelling and control coordination scheme of a wind‐to‐hydrogen set for future renewable‐based power systems

New challenges regarding system stability and efficiency arise when power systems operate with a high penetration level of inverter‐based renewable sources (IBRSs) and few synchronous generators. Since IBRSs have been on the rise, to secure the stable operation of future power systems, IBRSs will be required to support systems without having to rely on remaining synchronous generators. Also, to efficiently manage the uncertainty of renewable production, power‐to‐gas technology can provide the required flexibility. This study proposes modelling and a control coordination scheme (CCS) of a wind‐to‐hydrogen (W2H) set to optimise electricity production from a variable‐speed wind turbine generator (WTG) while helping balance between supply and demand in a system. To achieve this, a grid‐forming (GFM) inverter‐based WTG is modelled and a set of electrolyser and fuel cell is integrated at the DC circuit of a GFM‐WTG to be coordinated. Furthermore, the CCS offers an opportunity to reduce the investment cost for deploying a W2H set by utilising the control capabilities of a WTG and reducing the need for an additional device. The performance of the proposed W2H set with the CCS was verified considering the variations in system load and wind speed by using Power System Computer Aided Design (PSCAD)/ElectroMagnetic Transients including Direct Current (EMTDC).

Kim, Jinho↗

The Role of Regional Connections in Planning for Future Power System Operations Under Climate Extremes

Identifying the sensitivity of future power systems to climate extremes must consider the concurrent effects of changing climate and evolving power systems. We investigated the sensitivity of a Western U.S. power system to isolated and combined heat and drought when it has low (5%) and moderate (31%) variable renewable energy shares, representing historic and future systems. We used an electricity operational model combined with a model of historically extreme drought (for hydropower and freshwater-reliant thermoelectric generators) over the Western U.S. and a synthetic, regionally extreme heat event in Southern California (for thermoelectric generators and electricity load). We found that the drought has the highest impact on summertime production cost (+10% to +12%), while temperature-based deratings have minimal effect (at most +1%). The Southern California heat wave scenario impacting load increases summertime regional net imports to Southern California by 10-14%, while the drought decreases them by 6-12%. Combined heat and drought conditions have a moderate effect on imports to Southern California (-2%) in the historic system and a stronger effect (+8%) in the future system. Southern California dependence on other regions decreases in the summertime with the moderate increase in variable renewable energy (-34% imports), but hourly peak regional imports are maintained under those infrastructure changes. By combining synthetic and historically driven conditions to test two infrastructures, we consolidate the importance of considering compounded heat wave and drought in planning studies and suggest that region-to-region energy transfers during peak periods are key to optimal operations under climate extremes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Introduction to the Special Section on Control and Management of Electric Power Systems With High Shares of Inverter-Based Resources

The growing interest in the integration of variable renewable energy (VRE) and distributed energy resources (DER) on both policy and economic grounds is driving the transformation of electric power systems. The significant deployment of VRE and DER can effectively displace the conventional synchronous generator-based power plants that for decades have been the foundation for power system generation and stability in electric power systems. Inverter-based resources (IBRs) introduce a high-level of uncertainty, variability, and complexity into the operation of electric power networks, and the transformation to IBRs raises a wide range of technical questions and operational challenges. The optimal coordination and control of these resources requires greater interoperability and necessitates significant upgrades of grid automation, including real-time monitoring.

distributed power generation↗

Optimal Control of Distributed Energy Resources using Model Predictive Control

In an isolated power system (rural microgrid), Distributed Energy Resources (DERs) such as renewable energy resources (wind, solar), energy storage and demand response can be used to complement fossil fueled generators. The uncertainty and variability due to high penetration of wind makes reliable system operations and controls challenging. In this paper, an optimal control strategy is proposed to coordinate energy storage and diesel generators to maximize wind penetration while maintaining system economics and normal operation. The problem is formulated as a multi-objective optimization problem with the goals of minimizing fuel costs and changes in power output of diesel generators, minimizing costs associated with low battery life of energy storage and maintaining system frequency at the nominal operating value. Two control modes are considered for controlling the energy storage to compensate either net load variability or wind variability. Model predictive control (MPC) is used to solve the aforementioned problem and the performance is compared to an open-loop look-ahead dispatch problem. Simulation studies using high and low wind profiles, as well as, different MPC prediction horizons demonstrate the efficacy of the closed-loop MPC in compensating for uncertainties in wind and demand.

Mayhorn, Ebony T.↗

Unified Modeling Architecture for Load Management in Extreme Heat: The New York City Case

Integration of renewable resources to meet growing energy demand is becoming a global priority under decarbonization mandates. This study contributes to ongoing efforts on this key subject by assessing the feasibility of using coastal-urban renewable energy resources, namely, offshore wind and rooftop photovoltaic systems, to meet electricity demand of New York City during the intense recent heat wave period of June 2025. A unified modeling framework, based on the urbanized weather research and forecasting model, is used to simulate climate, renewable resources, and energy demand variables. Findings show significant energy load mismatch of approximately 1150 GWh over the month, between the demand and the combined renewable generation outcome. Three storage integration scenarios are analyzed to mitigate the deficits, reducing said deficits by a minimum of approximately 9% over the duration of the month. This study provides a transferable modeling framework tool for evaluating renewable integration in dense urban environments that can be used by grid operators to support grid resilience during extreme heat events.