Nuclear Powered Microgrids: DOE-NE Microreactor Program Winter Meeting
This presentation will cover grid integration and controls activities and capabilities at INL focusing on nuclear energy integration with details on microgrid capabilities.
SEARCH · Engineering Papers
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
This presentation will cover grid integration and controls activities and capabilities at INL focusing on nuclear energy integration with details on microgrid capabilities.
This paper proposes a framework to determine the optimal active and reactive power dispatch of distributed photovoltaic (PV) generation, switched capacitors, and voltage regulators in multi-phase unbalanced distribution systems. The objectives of the optimal dispatch are minimization of the energy loss, PV real power curtailment, and switching operations of capacitors and voltage regulators, in addition to elimination of voltage violation and reverse power flow. The optimization problem is formulated in rectangular coordinates as a nonlinear, nonconvex problem with discrete variables. A hierarchical twostage framework is proposed to effectively handle those discrete variables and reduce the computational time compared to the unified approach in which all variables are solved simultaneously. The efficacy of the proposed approach and the accuracy of the obtained numerical solution is validated using the unbalanced multi-phase IEEE 34-bus with 15-minute load and PV data.
This paper develops a novel method to estimate the voltage magnitude on the primary side of distribution service transformers. The proposed method relies exclusively on smart meters, and therefore it is fully data-driven. This is an important feature because electric utilities have detailed models of only the primary network - that is, the network between the distribution substation and the primary side of service transformers that are installed closer to end-customer sites. The network that connects the secondary side of service transformers to end-customer sites, referred to as the secondary network, is simply represented by a lumped load. For each secondary network, the proposed method uses data acquired from only 2 smart meters: the closest and the farthest-in the sense of electrical distance - from the service transformer. As a reference to this feature, the proposed method is named SM2Vp. To our knowledge, this is the first time a method is shown to provide actionable information for realtime operation and control of power distribution grids using only two smart meters per secondary network. This is important because utilities have experienced barriers in managing and using large data sets for real-time operation and control. SM2Vp is primarily intended to provide pseudo-measurements for distribution system state estimation, but it can also be used directly for voltage control schemes. The performance of SM2Vp is demonstrated by numerical simulations carried out on three secondary network synthetic models and by using field data provided by a utility partner serving customers in southwestern California. A maximum relative error of approximately 3.9% or less is observed for the primary voltage magnitude estimates in all numerical experiments.
Taking a step towards a greener planet has created an increased need for a higher integration of renewable energy resources into the electric grid. Nonetheless, the intermittency and uncertainty associated with renewable generation have slowed down this integration. Demand response (DR) has been recently adopted to address this challenge by utilizing demand side flexibility and enabling the participation of many grid-interactive efficient buildings (GEBs). However, existing DR methods require significant modeling and/or training efforts and are computationally expensive. To address the aforementioned issues, we propose a model-free control (MFC)-based strategy that is robust to the time delays in the temperature measurements of the thermostatically controlled loads (TCLs). It assigns to each GEB a local controller to maintain the TCLs’ temperatures within desired comfort levels, while the load aggregator (LA) allocates the assigned reference power provided by the distribution system operator (DSO) to support a specific grid service, such as demand peak reduction, load shifting, balancing supply and demand, and consuming the solar photovoltaic power locally. We investigate the effects of such loss of information on the local control action as well as on meeting the power allocation constraint. We conclude that, for an appropriate choice of design parameters, the proposed MFC controller is satisfactorily robust to measurement time delays.
This paper presents a hierarchical control system to mitigate the variability of solar photovoltaic (PV) power plant and provide ancillary services to the electric grid without the need for additional non-solar resources. With coordinated management of each inverter in the system, the control system commands the power plant to proactively curtail a small fraction of its instantaneous maximum power potential, which gives the plant enough headroom to ramp up production from the overall power plant, for a service such as regulation reserve. This control system is practical for continuously changing cloud cover conditions in partially cloudy days. A case study from a site in Hawaii with one-second resolution solar irradiance data is used to verify the efficacy of the proposed control system. The proposed control algorithm is subsequently compared with the alternative control technology from the literature, the grouping control algorithm; the results show that the proposed hierarchical control system is over 10 times more effective in reducing generator mileage to support power fluctuations from solar PV power plants.
The growing interest in onsite solar photovoltaic and energy storage systems is partially motivated by customer concerns regarding grid reliability. However, accurately assessing the effectiveness of PVESS in mitigating these interruptions requires a comprehensive understanding of location-specific outage patterns and the ability to simulate realistic scenarios. To address the gap, we introduce the Power Reliability Event Simulation TOol (PRESTO), the first publicly available tool that simulates location-specific power interruptions at the county level. PRESTO allows for a more realistic assessment of system reliability by considering the unpredictability and location-specific patterns of power interruptions. We applied PRESTO in a case study of a single-family home across three U.S. counties, examining the performance of a solar photovoltaic system with 10kWh of battery storage during short-duration power interruptions. Our findings show that this system reliably met 93% of energy demand for essential non-heating and cooling loads, fully serving these loads in 84% of events, despite the constraints of daily time-of-use bill management which limits the battery's state-of-charge reserve. However, when heating and cooling loads were included, system performance decreased significantly, with only 70% of demand met and full service in 43% of events. These results highlight the challenges of using solar photovoltaic and energy storage systems for short-duration outages, emphasizing the need to consider factors like battery size and grid charging strategies to improve reliability. Our study demonstrates the practical applications of PRESTO, providing valuable insights into potential mitigation strategies including grid charging and optimizing battery size.
Low temperature thermal energy is an abundant and untapped energy source for large scale electrical power and energy production around the world. Many different stationary sources such as industrial and thermal power plants produce significant amounts of low temperature heat that goes unused. The primary reason for the energy loss is because the temperature of the heat is often too low for traditional systems to economically generate power from this waste heat. Many different technologies are being researched to produce grid–scale power from low temperature heat to increase grid efficiency, advance decarbonization efforts, and progress electrical power production to a more distributed system. A thermally regenerative battery (TRB) is one promising technology in this space, as it has large power and energy densities relative to competitive technologies and therefore has the potential to disrupt the current power generation mix. TRBs combine two unit operations (a redox flow battery and a distillation column) which are easily scalable and mature, meaning that if a viable TRB chemistry can be identified, its development to pilot and commercial scale can be streamlined. The all–aqueous, copper thermally regenerative ammonia battery (Cuaq–TRAB) was the first TRB that did not use an electrodeposition/dissolution reaction by stabilizing Cu(I) and Cu(II) in the electrolyte, allowing all electroactive species to be stable in an aqueous phase. Through these electrolyte modifications, coulombic efficiency, open circuit potential, and copper solubility all increased, resulting in large gains to power density, energy density, and energy efficiency.
Increased deployment of wind and solar raises new questions for power system planners regarding the future mix of generation technologies, optimal siting of generation capacity, trade-offs between generation and transmission investments, and system flexibility needs. The National Renewable Energy Laboratory (NREL) is working with Tamil Nadu Generation and Distribution Company (TANGEDCO) to answer the following questions: How much—and what type—of generation and transmission investments are needed to serve future demand at least cost? How can variable resources such as wind and solar be considered in the planning process? What are the key drivers (e.g., policies, technology costs, fuel constraints) for investments?
With the increasing level of inverter-based resources (IBRs) in modern power systems, this paper presents a small-signal stability analysis for power systems comprising synchronous generators (SGs) and IBRs. Four types of inverter controls are considered: two grid-following (GFL) controls, with or without grid support functions; droop-based grid-forming (GFM) controls; and virtual oscillator control-based GFM. We also analyze the impact of STATCOM and synchronous condensers on system stability to assess their role in the energy mix transition. With the small-signal dynamic behavior of the major technologies modeled, this paper provides stringent stability assessments using the IEEE 39-bus benchmark system modified to simulate future power systems. The exhaustive test cases allow for (a) assessing the impacts of different types and controls of generation and supplementary grid assets, as well as system inertia and line impedance on grid stability, and (b) elucidating pathways for the stabilization of IBR-dominated power systems. The analysis also indicates that future power systems can be stabilized with only a fraction of the total generation as voltage sources without SGs or significant system inertia if they are well distributed. This study provides insights into future power system operations with a high level of IBRs that can also be used for planning and operation studies.
As a result of climate change, extreme weather events are occurring more frequently and with increasing impact. This trend poses a significant challenge for distribution utilities and system operators to ensure that there is uninterrupted power supply to critical loads in their networks; thus, the level of proactive preparation of the distribution system to be able to handle severe impacts of extreme weather events represents the system's resilience. One method that distribution system planners can use to prepare for future extreme events is to plan multiple microgrids which can use local generation as much as possible to supply critical loads. But partitioning an existing distribution system such that multiple feasible islands are planned and which are capable of supporting critical loads is still challenging for distribution systems - first, because of the size of the network graph partitioning problem and, second, because of the difficulty in properly formulating the desired attributes of such islands or microgrids. Therefore, this paper presents a genetic algorithm based approach that facilitates incorporating multiple objectives for grid partitioning by formulating two types of problems - node allocation and edge elimination - and it considers multiple topological and resilience-enhancing objectives. The performance of the proposed genetic algorithm-based approach is numerically evaluated on multiple test systems as well as on a real distribution feeder in Colorado, United States.
With the increasing integration of inverter-based resources into the power grid, there has been a notable reduction in system inertia, potentially compromising frequency stability. To assess the suitability of existing area inertia estimation techniques for real-world power systems, this paper presents a rigorous comparative analysis of system identification, measurement reconstruction, and electromechanical oscillation-based area inertia estimation methodologies, specifically applied to the large-scale and multi-area WECC 240-bus power system. Comprehensive results show that the system identification-based approach exhibits superior robustness and accuracy relative to its counterparts.
A modern power system is characterized by a stochastic variation of the loads and an increasing penetration of renewable energy generation, which results in large uncertainties in its states. These uncertainties bring formidable challenges to the power system planning and operation process. To address these challenges, we propose a cost-effective, iterative response-surface-based approach for the chance-constrained AC optimal power-flow problem that aims to ensure the secure operation of the power systems considering dependent uncertainties. Starting from a stochastic-sampling-based framework, we first utilize the copula theory to simulate the dependence among multivariate uncertain inputs. Then, to reduce the prohibitive computational time required in the traditional Monte-Carlo method, we propose, instead of using the original complicated power-system model, to rely on a polynomial-chaos-based response surface. This response surface allows us to efficiently evaluate the time-consuming power-system model at arbitrary distributed sampled values with a negligible computational cost. This further enables us to efficiently conduct an online stochastic testing for the system states that not only screens out the statistical active constraints, but also assists in a better design of the tightened bounds without using any Gaussian or symmetric assumption. Finally, an iterative procedure is executed to fine-tune the optimal solution that better satisfies a predefined probability. The simulations conducted in multiple test systems demonstrate the excellent performance of the proposed method.
Coastal communities face unique challenges in maintaining continuous service from critical infrastructure. This research advances capabilities for evaluating the impact of using wave energy to desalinate water on the resilience of coastal communities. The study focuses on the feasibility of using wave energy conversion to provide drinking water to communities in need and applying resilience metrics to quantify its impact on the community. To assess the feasibility of wave-powered desalination, this research couples the open-source software Wave Energy Converter SIMulator (WEC-Sim) and Water Network Tool for Resilience (WNTR). This research explores variations in both the wave resource (location, seasonality, and duration) and the ability to maintain drinking water service during a disruption scenario by applying the simulation framework to three case studies, which are based on communities in Puerto Rico. The simulation framework provides a contextualized assessment of the ability of wave-powered desalination to improve the resilience of coastal communities, which can serve as a methodology for future studies seeking the integration of wave-powered desalination with water distribution systems.
This work presents a systematic methodology for the location selection of fast-charging stations for heavy-duty electric vehicles (EVs) based on both geospatial and electric grid analysis. The geospatial analysis is based on real-world geographic information system (GIS) data of road networks and existing supportive infrastructures. The grid analysis is implemented based on node-level analysis of potential impacts on voltages and power losses in the distribution system. A case study using a realistic, three-phase, unbalanced distribution feeder from California and extracted real-world GIS data is used to demonstrate the intuitiveness and effectiveness of the proposed methodology for the location selection of fast-charging stations for heavy-duty EVs considering both electric and existing transportation infrastructures.
This paper presents an energy scheduling-based formulation for computing operating envelopes including a distribution branch screening algorithm, termed DBS-ES. The contribution of the paper is two-fold: firstly, it presents an innovative methodology for calculating operating envelopes using energy scheduling (baseline), and secondly, it enhances this methodology by incorporating a custom distribution branch screening algorithm (DBS-ES). The custom algorithm leverages power system knowledge to reduce both model build time and total processing time while maintaining the same scheduling results as the baseline. The effectiveness of the proposed approach is demonstrated through experiments on the IEEE13, IEEE123, and EPRI Secondary test feeders. Results highlight a 24.5% decrease in model build time and an 8.17% decrease in total processing time when using DBS-ES compared to the baseline, specifically for the IEEE123 test feeder. Additionally, the paper briefly discusses the influence of utility-controlled storage on computing operating envelopes, noting a general incre
This paper presents performance evaluation of hierarchical optimization and control for distributed energy resource management system (DERMS) in large distribution networks via an advanced hardware-in-the-loop (HIL) platform. The HIL platform provides realistic testing in a laboratory environment, including the accurate modeling of a full-scale distribution system of 11,000 nodes, the DERMS software controller, and 90 power hardware photovoltaics (PVs) and battery inverters. The applied DERMS algorithm is designed based on a realtime optimal power flow algorithm and implemented with acceleration design that performs fast dispatch of simulated PVs and real physical hardware DER devices every 4 seconds.
This paper studies, the grid-interconnection requirements of directly connected medium-voltage (MV) Silicon Carbide-based (SiC-based) converters and details the necessary control implementations. These power electronic converters follow the interconnection standard IEEE 1547-2018, but can also have additional controls supported by the microgrid standards in IEEE 2030.7, which is demonstrated in this work. Additionally, this paper defines the grid applications realized by these directly connected medium-voltage power electronic converters at the distribution scale and demonstrates results. The controls for the studied grid applications are then developed and implemented on the controller. The paper also includes details of the control algorithm development and validations of the control algorithm through hardware-in-the-loop results.
This report summarizes the design and application of an outdoor power line sensor testbed (OPLST) with a real-time simulator and power meter to compare a potential transformer (PT) and current transformer (CT) versus an advanced line-post sensor. The OPLST was created to validate advanced medium-voltage (20/34.5 kV) outdoor power line sensors used in electrical distribution systems. Electrical utilities have installed metering and relay-protection transformers like PTs and CTs for several decades. The PTs/CTs are iron core measurement transformers based on the electromagnetic induction principle and provide reliable data in normal grid operation. However, new outdoor power line sensors (OPLS) using other technologies like voltage divider, Rogowski coil and optical principles have become available and may have favorable performance and costs compared to PTs/CTs. Therefore, the importance of testing these technologies with the PT/CT, to compare the measured phase voltage/current at different power grid scenarios is crucial to understand the performance of these new OPLS. For this study a G&W Electric Model CVS-36-O power line sensor was chosen as the OPLS to test with voltage/current signals. An OPAL-RT Technologies Model OP4510 real-time simulator and Schweitzer Engineering Laboratories Model SEL-735 power meter were installed with the 20/34.5 kV OPLST to compare the measured transient events collected from an advanced OPLS and the PT/CT. This system is installed at the Distributed Energy Communications and Control (DECC) lab, Oak Ridge National Laboratory (ORNL). The simulator generated different power grid scenarios (electrical faults, capacitor bank operation, service restoration, etc.), and its analog-output signals were connected to the voltage/current amplifiers that feed the 20/34.5 kV aerial cable loop through the PT/CT devices. Additional PT/CT devices were also wired with the medium voltage aerial cable loop to measure the phase current/voltage signals and server as references. After each test, common format for transient data exchange (COMTRADE) files were collected from the SEL-735 power meter and used to compare the performance of the OPLS with the PT/CT. The behavior of analog signals, harmonic components, total harmonic distortion and crest factors were assessed and found favorable for the G&W sensor as compared to the reference PT/CT.