Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “Distributed microgrid control”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 415 records · Page 23

An Operational Resilience Metric for Modern Power Distribution Systems

The electrical power system is the backbone of our nations critical infrastructure. It has been designed to withstand single component failures based on a set of reliability metrics which have proven acceptable during normal operating conditions. However, in recent years there has been an increasing frequency of extreme weather events. Many have resulted in widespread long-term power outages, proving reliability metrics alone do not provide adequate energy security. As a result, researchers have focused their efforts on a new set of metrics based on the concept of resilience to ensure efficient operation of power systems during extreme events. A resilient system has the ability to resist, adapt, and recover from disruptions. Therefore, resilience has demonstrated itself as a promising concept for currently faced challenges in power distribution systems. In this work, we propose a real-time resilience metric for modern power distribution systems. The metric is an aggregation of the controllable assets adaptive capacity, or their temporal flexibility in real and reactive power. This metric gives information to the magnitude and duration of a disturbance which the system can respond to without having to drop loads or have stability issues in voltage or frequency. We demonstrate the impact to resilience in a case study under normal operation and during a power contingency on a microgrid. In the future, this information can be used by operators to make more informed decisions based on system resilience in an effort to prevent power outages.

42 ENGINEERING↗

Multi-Time Scale Coordinated Control and Scheduling of Inverter-Based TCLs With Variable Wind Generation

To address microgrid tie flow errors caused by wind generation variability, here we propose and develop a multi-time scale coordinated control and scheduling strategy for inverter-based thermostatically controlled loads (TCLs). First, in hour-time scale, inverter-based TCLs with adjusting temperature set-point are modeled as virtual generators to compensate tie flow deviations in the day-ahead plan. Next, in minute-time scale, virtual batteries representing operating behaviors of inverter-based TCLs with frequency control are scheduled determined by the control of virtual generators in hour-time scale. The virtual batteries are scheduled to smooth out tie flow errors corresponding to day-ahead plan and hour-time scale schedules. The multi-time scale control methods are coordinated to employ the response potential of inverter-based TCLs and response curve-based methods are proposed to control inverter-based TCLs considering the customer privacy. The multi-time scale stochastic schedules which are based on response curves of inverter-based TCLs are coordinated to accommodate wind generation variability. Simulation results demonstrate that the microgrid tie flow errors are effectively mitigated by the proposed multi-time scale coordinated control and scheduling of inverter-based TCLs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

New Jersey Transit Grid Distributed Generation Program. Cybersecurity Design Assurance Assessment

Superstorm Sandy caused a major disruption to passenger-rail and other commuter systems throughout New York and New Jersey. To address this issue, New Jersey Transit (NJT) established the NJ TRANSITGRID project, an effort designed to power bus, ferry, and limited passenger-rail service during natural or man-made disasters. Given the importance of these transportation systems, NJT partnered with Sandia National Laboratories (Sandia) to assess the cyber-resilience of the information systems that monitor and control the electrical systems within the microgrid. The Sandia “tabletop” assessment is based on the most recent 20% design packages. From this assessment, the Sandia team identified several security areas that were undefined or did not implement industry best practices. Finally, the Sandia team presented possible follow-on assessment activities and recommended investigating multiple hardening technologies. Addressing these findings and adding state-of-the-art detection and mitigation technologies will help ensure the NJ TRANSITGRID is built with more comprehensive cyber-resilience features.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Fuzzified PaCcET for Economic-Emission Scheduling of Microgrids

In this paper, a new approach is proposed to solve a multi-objective economic-emission scheduling problem in microgrids (MGs) by simultaneously minimizing the energy and emission costs of the MG with various distributed energy resources (DERs). The proposed approach is an extension of a computationally effective multiobjective optimization technique, Pareto concavity elimination transformation (PaCcET). The proposed approach, referred to as Fuzzified-PaCcET, employs a fuzzy logic controller to dynamically revise crossover and mutation rates in the original PaCcET leading to the faster convergence of the solution. The proposed approach finds the best Pareto front, also referred to as a Non-dominated set (NDS) of solutions, instead of finding a single optimal solution. In order to find the solutions on concave areas of the Pareto front, an iterative objective space transformation is performed in the PaCcET algorithm to allow a linear combination of objective functions (in the transformed objective space). The proposed Fuzzified-PaCcET-based scheduling is implemented on a MG with various dispatchable and non-dispatchable DERs to find the set of optimal solutions according to the total fuel cost of DERs, as well as the most optimum environmental cost. In order to extract the best compromise solution (BCS) among NDS of solutions, a fuzzy-based method is implemented. The comparison of the simulation results of the Fuzzified-PaCcET with that of PaCcET shows that Fuzzified-PaCcET can generate better solution with less computational burden.

Gautam, Mukesh↗

Enabling Secure Scalable Microgrids with High Penetration Renewables

Laboratory Directed Research and Design (LDRD) originating technologies are being developed to address challenges inherent to highly stochastic energy sources and loads, to conceivably satisfy the electrical energy needs of national/international power systems. The Enabling Secure, Scalable Microgrids with High Penetration Renewables Grand Challenge LDRD (FY11-FY13) aimed to develop a novel intelligent grid architecture, Secure Scalable Microgrid (SSM), based on closed loop controls and an agent-based architecture supporting intelligent power flow control. The approach was to enable self-healing, self-adapting, self-organizing architectures and allow a trade-off between storage in the grid versus information flow to control generation sources, power distribution, and where necessary, loads. L

24 POWER TRANSMISSION AND DISTRIBUTION↗

Fuzzified PaCcET for Economic-Emission Scheduling of Microgrids

In this paper, a new approach is proposed to solve a multi-objective economic-emission scheduling problem in microgrids (MGs) by simultaneously minimizing the energy and emission costs of the MG with various distributed energy resources (DERs). The proposed approach is an extension of a computationally effective multiobjective optimization technique, Pareto concavity elimination transformation (PaCcET). The proposed approach, referred to as Fuzzified-PaCcET, employs a fuzzy logic controller to dynamically revise crossover and mutation rates in the original PaCcET leading to the faster convergence of the solution. The proposed approach finds the best Pareto front, also referred to as a Non-dominated set (NDS) of solutions, instead of finding a single optimal solution. In order to find the solutions on concave areas of the Pareto front, an iterative objective space transformation is performed in the PaCcET algorithm to allow a linear combination of objective functions (in the transformed objective space). The proposed Fuzzified-PaCcET-based scheduling is implemented on a MG with various dispatchable and non-dispatchable DERs to find the set of optimal solutions according to the total fuel cost of DERs, as well as the most optimum environmental cost. In order to extract the best compromise solution (BCS) among NDS of solutions, a fuzzy-based method is implemented. The comparison of the simulation results of the Fuzzified-PaCcET with that of PaCcET shows that Fuzzified-PaCcET can generate better solution with less computational burden.

42 ENGINEERING↗

Resilient Control of Networked Microgrids Using Vertical Federated Reinforcement Learning: Designs and Real-Time Test-Bed Validations

Improving system-level resiliency of networked microgrids against adversarial cyber-attacks is an important aspect in the current regime of increased inverter-based resources (IBRs). To achieve that, this paper contributes in designing a hierarchical control layer, in conjunction with the existing control layers, resilient to adversarial attack signals. Considering model complexities, unknown dynamical behaviors of IBRs, and privacy issues regarding data sharing in multi-party-owned microgrids, designing such a control layer is non-trivial. Here, to tackle these issues, a novel federated reinforcement learning (Fed-RL) method is proposed. To grasp the interconnected dynamics of networked microgrids, the paper develops Federated Soft Actor-Critic (FedSAC) algorithm following the vertical structure of implementing Fed-RL. Next, utilizing the OpenAI Gym interface, we built a custom set-up in GridLAB-D/HELICS co-simulation platform, named Resilient RL Co-simulation (ResRLCoSIM), to train the RL agents with IEEE 123-bus benchmark comprising 3 interconnected microgrids. Finally, the learned policies in the simulation are transferred to the real-time hardware-in-the-loop (HIL) test-bed developed using the high-fidelity Hypersim platform. Finally, experiments show that the simulator-trained RL controllers achieve desirable performance with the test-bed platform, validating the minimization of the sim-to-real gap.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Ensuring Transient Stability With Guaranteed Region of Attraction in DC Microgrids

DC microgrids have promising applications in renewable integration due to their better energy efficiency when connecting DC components. However, they might be unstable since many loads in a DC microgrid are regulated as constant power loads (CPLs) that have a destabilizing negative impedance effect. As a result, the state trajectory displacement caused by abrupt load changes or contingencies can easily lead to instability. Many existing works have been devoted to studying the region of attraction (ROA) of a DC microgrid, in which the system is guaranteed to be asymptotically stable. Nevertheless, existing work either focuses on using numerical methods for ROA approximations that generally have no performance guarantees or cannot ensure a desired ROA for a general DC microgrid. To close this gap, this paper develops an innovative control synthesis algorithm to make a general DC microgrid have a theoretically guaranteed ROA, for example, to cover the entirety of its operating range regarding state trajectories. Here, we first study the nonlinear dynamics of a DC microgrid to derive a novel transient stability condition to rigorously certify whether a given operating range is a subset of the ROA; then, we formulate a control synthesis optimization problem to guarantee the condition’s satisfaction. This condition is a linear constraint, and the optimization problem resembles an optimal power flow problem and has a good computational behavior. Simulation case studies verify the validity of the proposed work.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Critical values of cyber parameters in a dynamic microgrid system

An islanded microgrid can be used to serve critcal load as a resiliency source when a severe outage occurs. In an islanded mode, control of a microgrid relies on the communication system significantly. Hence, microgrids are cyberphysical systems and, therefore, the cyber system plays a crucial role in the performance of the cyber-power system. A microgrid control scheme is proposed for power dispatch and regulation based on the droop and proportional-integral (PI) feedback control. The proposed control strategy is validated for transient stability following dynamic events. To evaluate the impact of a networked control system on control performance, a cyber model is developed to represent data acquisition periods and communication delays. An analytical method is proposed to determine the critical values for the data reporting periods and communication delays. The analytical method based on a state space model of a networked control system is applicable for large-scale systems. A 2-dimensional stability region of a microgrid in the space of cyber parameters can be obtained by the proposed method, and the critical values of cyber parameters are determined based on the stability region. Simulation results validate that the design of a microgrid as a cyber-physical system needs to be guided by critical values for the data reporting period and communication delay to prevent system instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Transient Safety Filter Design for Grid-Forming Inverters

Unlike conventional generators, inverter-based generation are fundamentally incapable of providing rotational inertia. While grid-forming inverters alleviate some of that problem by synthesizing small inertia via feedback control, additional control mechanisms are needed to ensure safety and security during transients. In this paper, we propose novel real-time safety-constrained feedback controllers (``safety filters'') for droop-based (grid-forming) inverters to ensure transient security of the grid. The safety filter acts as a buffer between the network operational layer and the inverter-control layer, and only lets those dispatch control signals pass to the inverter droop-controller, which are guaranteed to not violate the safety specifications (frequency, voltage, current limits). Using a distributed barrier certificates method, we construct sector-like conditions on the control policies, which guarantee the satisfaction of transient safety specifications. Sum-of-square programming is used to synthesize the safety filters. Numerical simulation results are provided to illustrate the performance of the proposed filter on inverter-based microgrids.

Kundu, Soumya↗

Co-design optimization of combined heat and power-based microgrids

With the emergent need for clean and reliable energy resources, hybrid energy systems, such as the microgrid, are widely adopted in the United States. A microgrid can consist of various distributed energy resources, for instance, combined heat and power (CHP) systems. Here, the CHP module is a distributed cogeneration technology that produces electricity and recaptures heat generated as a by-product. It is an energy-efficient technology converting heat that would otherwise be wasted to valuable thermal energy. For an optimal system configuration, this study develops a novel co-design optimization framework for CHP-based cogeneration microgrids. The framework provides the stakeholder with a method to optimize investments and attain resilient operations. The proposed co-design framework has a mixed integer programming (MIP) model that outputs decisions for both plant designs and operating controls. The microgrid considered in this study contains six components: the CHP, boiler, heat recovery unit, thermal storage system, power storage system, and photovoltaic plant. After solving the MIP model, the optimal design parameters of each component can be found to minimize the total installation cost of all components in the microgrid. Furthermore, the online costs from energy production, operation, maintenance, machine startup, and disruption-induced unsatisfied loads are minimized by solving the optimal control decisions for operations. Case studies based on designing a CHP-based microgrid with empirical data are conducted. Moreover, we consider both nominal and disruptive operational scenarios to validate the performance of the proposed co-design framework in terms of a cost-effective, resilient system.

42 ENGINEERING↗

Guest Editorial: Planning and operation of resilient distribution system for integrated multi-energy

Resilience is the ability of power systems to prepare for and adapt to low-probability, high-impact incidents and withstand and recover rapidly from disruptions. With the ageing of electricity distribution infrastructure and increasing threats of weather-related incidents and natural disasters, the need to effectively enhance the resilience of the electricity distribution system has become urgent and has attracted worldwide attention. Although there are an increasing number of publications related to enhancing resilience strategies, resilience is an emerging concept in power systems. Existing practices are mostly focused on deploying distributed energy resources (DERs) and microgrids, hardening the existing infrastructures and building redundant capacities. However, from a broader perspective, resilience enhancement of power distribution system is a systematic engineering, involving long-term system planning and upgrading (e.g., deployment of smart grid technologies and intelligent switches), short-term proactive scheduling, real-time robust and resilient control of DERs, and post-event restoration and recovery strategies. Based on this point, this Special Issue in IET Energy System Integration focuses on soliciting the most recent and original technologies, scheduling and control strategies for improving the resilience of power distribution system. Eight papers are presented in this Special Issue, covering various aspects related to resilience enhancement of power distribution system, including fault-tolerant frequency measurement, robust scheduling of integrated electricity and district heating systems, robust control of DERs, efficient methods for safety verification as well as novel graph theory-based approach to restore the distribution systems after multiple simultaneous faults. A brief introduction of these 8 papers is provided below.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Virtual Oscillator Control Maintains Grid Operations with High Inverter Penetrations

VOC makes each inverter behave electrically like a spring, 'bouncing back' to its normal operating range when disturbed. Coupling these inverters electronically could result in a new way to stabilize power grids. VOC has been demonstrated in a microgrid using several small inverters. In addition, five custom-designed inverters have been built and will be tested with grid simulations at NREL using power hardware-in-the-loop technology. VOC may provide a simple method to keep microgrids stable -- a topic of growing interest as resilience to energy disruptions gains prominence. VOC may also provide a means to transition power grids from today's inertia-dominated systems to systems that do not rely on rotating machinery.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Multi-time Scale Coordination of Distributed Energy Resources in Isolated Power Systems

In isolated power systems, including microgrids, distributed assets, such as renewable energy resources (e.g. wind, solar) and energy storage, can be actively coordinated to reduce dependency on fossil fuel generation. The key challenge of such coordination arises from significant uncertainty and variability occurring at small time scales associated with increased penetration of renewables. Specifically, the problem is with ensuring economic and efficient utilization of DERs, while also meeting operational objectives such as adequate frequency performance. One possible solution is to reduce the time step at which tertiary controls are implemented and to ensure feedback and look-ahead capability are incorporated to handle variability and uncertainty. However, reducing the time step of tertiary controls necessitates investigating time-scale coupling with primary controls so as not to exacerbate system stability issues. In this paper, an optimal coordination (OC) strategy, which considers multiple time-scales, is proposed for isolated microgrid systems with a mix of DERs. This coordination strategy is based on an online moving horizon optimization approach. The effectiveness of the strategy was evaluated in terms of economics, technical performance, and computation time by varying key parameters that significantly impact performance. The illustrative example with realistic scenarios on a simulated isolated microgrid test system suggests that the proposed approach is generalizable towards designing multi-time scale optimal coordination strategies for isolated power systems.

Mayhorn, Ebony↗

Optimized V1G and V2G Electric Vehicle Fleet Management and Grid Transaction at Marine Corps Air Station Miramar in San Diego, CA

The overall technical goal of the project was to demonstrate an all-electric bi-directional non-tactical fleet at Marine Corps Air Station (MCAS) Miramar that was integrated and controlled with other distributed energy resources (DERs) (i.e., PV, stationary battery, and building loads) to provide resilience to critical electric loads in the event of grid outages, to minimize charging costs, and to provide economic energy resources to electricity markets. In this project, the specific, technical objectives were: 1. Demonstrate that bi-directional electric vehicles can provide critical complementary services to fixed storage batteries in microgrid applications while performing function as non-tactical vehicles. 2. Demonstrate participation of bi-directional (V2G) and unidirectional (V1G) PEVs for demand management and minimization of charging costs. 3. Demonstrate integration of multiple DERs for grid service participation. US Marine Corps Air Station (MCAS) Miramar in San Diego was the site of this electric vehicle-to-microgrid-utility grid test and demonstration project. Existing microgrid assets in this study included (1) a public works building; (2) a 30-kW rooftop photovoltaic (PV) system and (3) a separate 250 kW carport PV system. In this project, six bi-directional V2G vans were located at the MCAS Miramar’s showcase building-scale microgrid to develop and test technical capabilities that V2G can provide in microgrid applications (e.g., cost reduction and resiliency). These resources provided aggregated demand management and simulated participation in current retail DR programs. The vehicles used in this demonstration were selected because they provided functionality that MCAS Miramar needed, 15 passenger transport and facilities work cargo carrying capacity, and bi-directional charging capability that the research project required. All vehicles in this study were manufactured and distributed by VIA Motors, Inc. There were six vehicles total and each was VIA’s VTRUX eREV V2G model, a modified General Motors Chevrolet 2500 2WD van. Three of the vans were configured as passenger vans and the other three were configured as cargo vans. Each van had an on-board bi-direcrtional inverter/charger, Bel Power Solutions model 350INVCHGT150-120-240-8G nominally rated at +/-15 kW. The VIA van’s charging connector follows the J1772 charging protocol. The bi-directional EVSEs demonstrated in this study were manufactured by Coritech, Inc. Each VGI-80-AC charging station enabled enhanced V2G charging capability to a Clipper Creek CS-100 charging module. The enhanced capabilities included ethernet communication following the SEP2.0 protocol with a distributed energy resource function set and an operator screen displaying real-time SOC, voltage, and current. The VGI-80-AC charging stations are classified as level 2 with a maximum current output of 80 A or effectively 19 kW. The VIA van’s onboard charger limited the charging and discharging power to 15 kW in each direction. A control computer was installed in the EWOC and connected to an existing monitor. The V2G control communication network was a completely stand-alone closed system that did not have any connection to any other networks on the base. A cybersecure remote communication connection was created with a cellular modem, firewall hardware, and a virtual private network configuration.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Multidimensional Holistic Framework for the Security of Distributed Energy and Control Systems

The digitization of smart grid distributed generation and industrial control systems has prompted utilities to deploy tools with ubiquitous communications that potentially widen the attack surface. The utilities still continue to rely on the traditional cybersecurity technologies, such as firewalls, anti-malware tools, and passwords that do not ensure security across all dimensions of the information assurance model required for a strong cybersecurity business process. This paper proposes a multidimensional holistic framework that addresses this gap through advanced technologies, intelligent algorithms, and continued assessments. To show proof, the layered defense model, a solution dimension of the framework, is integrated into the National Renewable Energy Laboratory's Security and Resilience Testbed to replicate a utility's enterprise and substation networks. The model is used to evaluate the security and resilience of microgrid control systems, and, based on the insights gathered, recommend best practices for utility cybersecurity analysts for a strong business process. Here, with this baseline, the paper conceptually introduces intelligence-driven solutions comprising contextual data analysis and machine learning to respond to advanced persistent threats sponsored by campaign efforts.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Development of a Practical Secondary Control for Hardware Microgrids

Practical, vendor-agnostic interoperability guidelines for the secondary control architecture of microgrids (MGs) with multiple grid-forming (GFM) inverter-based resources (IBRs) have not yet been developed. Therefore, this paper proposes a generic and vendor-agnostic secondary control architecture that operates with all GFM IBRs and synchronous generators. This secondary control does not require the use of additional measurement devices in the MG and utilizes the inherent communication systems of the GFM units, such as Modbus TCP/IP. The practical challenges of Modbus registers, such as packet loss and quantization error, and their detrimental impacts on secondary control actions are investigated. The proposed three-stage modification for any secondary control architecture to mitigate these impacts includes: 1) averaging the data read, 2) situational event-triggering of the controller, and 3) finite iteration of the controlling action. The proposed method is validated using a 3-..phi.., 480 V, 60 Hz, 500 kVA laboratory hardware microgrid with commercial two GFM IBRs and one diesel generator. The experimental results corroborates the fact the proposed modification in the secondary control architecture is advantageous for practical usage under erroneous measurements.

communication systems↗

Microgrid Plant Control Design and Development

This report discusses the technical performance of the proposed microgrid at Potsdam, New York, and the enhanced microgrid controller platform. The test objectives were outlined by the DOE, and summary results and discussion are given for each objective. The findings show that the proposed Potsdam, NY microgrid would have a significant impact on the regional CO 2 emissions, the amount of imported energy from the utility, and the resiliency of the critical loads. Additionally, the enhanced microgrid control system developed for this project was tested to be compliant with IEEE 1547 standards, and able to generate revenues to help offset energy costs by way of participation in ancillary services.

24 POWER TRANSMISSION AND DISTRIBUTION↗