Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “distribution system voltage control”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 361 records · Page 20

Learning with Adaptive Conservativeness for Distributionally Robust Optimization: Incentive Design for Voltage Regulation: Preprint

Information asymmetry between the Distribution System Operator (DSO) and Distributed Energy Resource Aggregators (DERAs) obstructs designing effective incentives for voltage regulation. To capture this effect, we employ a Stackelberg game-theoretic framework, where the DSO seeks to overcome the information asymmetry and refine its incentive strategies by learning from DERA behavior over multiple iterations. We introduce a model-based online learning algorithm for the DSO, aimed at inferring the relationship between incentives and DERA responses. Given the uncertain nature of these responses, we also propose a distributionally robust incentive design model to control the probability of voltage regulation failure and then reformulate it into a convex problem. This model allows the DSO to periodically revise distribution assumptions on uncertain parameters in the decision model of the DERA. Finally, we present a gradient-based method that permits the DSO to adaptively modify its conservativeness level, measured by the size of a Wasserstein metric-based ambiguity set, according to historical voltage regulation performance. The effectiveness of our proposed method is demonstrated through numerical experiments.

distribution system operator↗

Efficient learning of power grid voltage control strategies via model-based deep reinforcement learning

Here this article proposes a model-based deep reinforcement learning (DRL) method to design emergency control strategies for short-term voltage stability problems in power systems. Recent advances show promising results for model-free DRL-based methods in power systems control problems. But in power systems applications, these model-free methods have certain issues related to training time (clock time) and sample efficiency; both are critical for making state-of-the-art DRL algorithms practically applicable. DRL-agent learns an optimal policy via a trial-and-error method while interacting with the real-world environment. It is also desirable to minimize the direct interaction of the DRL agent with the real-world power grid due to its safety-critical nature. Additionally, the state-of-the-art DRL-based policies are mostly trained using a physics-based grid simulator where dynamic simulation is computationally intensive, lowering the training efficiency. We propose a novel model-based DRL framework where a deep neural network (DNN)-based dynamic surrogate model (SM), instead of a real-world power grid or physics-based simulation, is utilized within the policy learning framework, making the process faster and more sample efficient. However, having stable training in model-based DRL is challenging because of the complex system dynamics of large-scale power systems. We addressed these issues by incorporating imitation learning to have a warm start in policy learning, reward-shaping, and multi-step loss in surrogate model training. Finally, we achieved 97.5% reduction in samples and 87.7% reduction in training time for an application to the IEEE 300-bus test system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Deep Learning-enhanced Block-Diagram Modeling of Solar Power Systems

Data-driven models of power system inverter-based resources are desired to run simulations faster than with detailed electromagnetic transient models, to hide proprietary design details, to support control system design applications, and to aggregate the effects of distributed energy resources. This paper applies a customized Hammerstein Wiener framework to train block diagram models from thousands of electromagnetic transient simulations or experimental test records. The block diagram models integrate with larger grid simulations as voltagecontrolled current sources or current-controlled voltage sources for several simulators. Guidelines for block architecture and training are presented. Three-phase balanced, three-phase unbalanced, and single-phase examples all achieve an acceptable root mean square error of no more than 0.05 per-unit.

Mcdermott, Thomas E. [Private consulting company]↗

Using an Advanced Distribution Management System Test Bed to Evaluate the Impact of Model Quality on Volt/VAR Optimization: Preprint

In this paper, we present a test bed for evaluating existing and future advanced distribution management system (ADMS) applications in a realistic laboratory setting, including other utility management systems and field equipment. We present an example of using it to evaluate the impact of the ADMS network model quality on a Volt/VAR optimization (VVO) application. The test bed integrates a commercial ADMS with a real-time simulation model of a utility distribution feeder. Representative power and controller hardware are integrated through hardware-in-the-loop (HIL) techniques. The performance of the ADMS VVO application is also evaluated for different levels of measurement density. Initial results indicate that a higher model quality achieves the highest possible energy savings while avoiding voltage violations, whereas a lower model quality results in increased energy savings but at the expense of more voltage violations.

ADMS↗

Reconfigurable Real-Time Power Grid Emulator for Systems With High Penetration of Renewables

Novel power system control and new utility devices need to be tested before their actual deployment to the power grid. To assist with such a testing need, real-time digital emulators such as RTDS and Opal-RT can be used to connect to the physical world and form a hardware in the loop (HIL) emulation. However, due to the limitations of today's computational resources, the accuracy and fidelity suffer from different levels of model reductions in purely digital simulations. CURENT has developed a reconfigurable electric grid hardware testbed (HTB) to overcome the limitations of digital emulators. The HTB has been used to develop measurement, control, modeling, and actuation techniques for a national grid with a high penetration of renewables. The power electronic-based system includes emulators for synchronous generators; photovoltaics with grid-interfacing inverter; wind turbines; induction motor loads, ZIP loads, power electronic loads; batteries; ac and dc transmission lines; short circuit faults and grid relay protection; and a multiterminal HVDC overlay including power electronics interfaces. The system contains real elements of power flow, measurement, communication, protection, and control that mimic what would be seen in an actual electric grid. This paper presents an overview of the HTB and several scenarios that have been run to determine control and actions needed for the future power grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Photovoltaic Inverter Momentary Cessation: Recovery Process is Key

Momentary cessation refers to an inverter control mode. When the inverter terminal voltage falls below (or exceeds) a certain level, the inverter ceases to output any current, but attempts to maintain (or quickly regain) phase-locked loop synchronization to allow for quick reinjection of current when the voltage recovers to a certain point. This paper presents a photovoltaic (PV) momentary cessation model developed in PSS/E. Simulations are presented for a high voltage transmission line fault contingency in the Hawaiian island of Oahu power system on a validated PSS/E model, modified to include a custom distributed PV inverter model, and different near-future distributed PV penetration levels. Simulations for the island power system include different penetration levels of PV, and different recovery times (ramp rates and delays) after momentary cessation. The results indicate that during low voltage events, such as faults, momentary cessation can produce severe under frequency events, causing significant load shed and shortly thereafter, in some cases, over frequency events that cause generation to trip offline. The problem is exacerbated with higher penetration levels of PV. If momentary cessation is used (as is typically the case for distribution-connected resources), the recovery process after momentary cessation should be carefully considered to minimize impacts to bulk power system stability.

14 SOLAR ENERGY↗

Distributed Cooperative Control of Hybrid AC/DC Microgrid

This paper presents a distributed cooperative control-based power management algorithm for a hybrid AC/DC microgrid. The proposed algorithm for a hybrid microgrid system controls the power flow through the interface converter between the AC and DC microgrids. This algorithm allows power sharing between the distributed generators in the microgrid according to their power ratings. Moreover, it enables the fixed scheduled power delivery through the interface converters in both directions at different operating conditions while maintaining voltage regulation and improving the frequency profile. The effectiveness of the controller is confirmed by simulation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

MULTI-FIDELITY MODELING AND UNCERTAINTY QUANTIFICATION OF INVERTER BASED RESOURCES IN INTEGRATED T&D SYSTEMS

Uncertainty quantification plays a pivotal role in improving the accuracy and reliability of inverter operation within modern power systems that are increasingly dominated by inverter-based resources (IBRs). IBRs, especially those operating under grid forming (GFM) control, rely heavily on a complex set of control parameters and system measurements to maintain voltage, frequency, and power balance. Traditional deterministic modeling approaches often fail to capture these parameter deviations, potentially resulting in suboptimal control actions, reduced system stability, or even instability under high penetration of IBRs. In this paper, we demonstrate the application of model calibration and uncertainty quantification (UQ) principles to an integrated transmission and distribution (T&D) model involving a GFM converter and provide a framework for prioritizing control improvements, guiding robust design, and informing adaptive strategies that can accommodate real-time variability in system conditions. The proposed approach could be valuable in enhancing the robustness of current and future power systems under increased IBR penetrations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Shunt-Connected FACTS and Synchronous Condensers

In recent years, the electric-transmission system has undergone a significant transformation marked by a greater integration of renewable-energy sources like wind and solar, the phasing out of thermal generation plants, and a concerted effort towards electrifying energy consumption. To keep pace with the integration of renewable-energy sources and the escalating demands of industries and households, it is imperative to expand and modernize the existing power infrastructure. These upgrades are essential to maintain grid stability, enhance power delivery, and boost overall efficiency of the system. However, challenges have emerged with the growing complexity of power grids, particularly in the realms of voltage control, transient stability, and power-quality management.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Real-Time Testbed for Smart Grid Recloser Controller

The growing need for a low voltage recloser has become apparent due to the rise in requirements for a smart grid. This includes more detailed management of power flow forward (towards load) and backward (towards generation), source synchronization in real time, more indepth fault responses, and the use of green energy. The SEL-651R-2 relay is a device that can manage these needs, especially in fault response and synchronization, and is commonly used in systems called microgrids. Microgrids are distribution level systems that are able to operate separated from the main grid, are typically installed much closer to the load(s), and are fed by distributed energy resources (DERs), such as wind, solar or diesel generators. The SEL-651R-2 is normally used in the field with presets operative settings, but the Western Michigan University (WMU) Center for Interdisciplinary Research on Secure, Efficient and Sustainable Energy Technology (WMU InterEnergy Center) wished to test this device in its range of capabilities for microgrid application. A Hardware-In-the-Loop (HIL) testbed was implemented and used through the Real Time Digital Simulator (RTDS) using the RSCAD software to test the SEL-651R-2's use cases and functions. The testbed includes a microgrid with interconnection to a larger main grid, and the relay is meant to control the recloser at the point of common coupling (PCC) between the main grid and microgrid. The testbed shows how basic protections, reclosing, and synchronization checks function when handling faults that affect both the microgrid and the main grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

The Impact of Behind-the-Meter Heterogeneous Distributed Energy Resources on Distribution Grids: Preprint

The increasing integration of distributed energy resources (DERs) on the electric grid brings new challenges and opportunities for utility grid operations. With the rapid deployment of DERs, there is emerging interest in integrating these controllable devices with utility operations at all levels for monitoring and management. Different types of DERs such as Photovoltaics (PV), energy storage, electric vehicles (EVs), etc. have varying effects on the grid based on how and where they are deployed. Again, the DER deployment and its impact are network-dependent, while the traditional electric grids were not designed to host DERs. To understand the challenges with increasing behind-the-meter (BTM) DERs and to identify the needs in deploying advanced controls, a comprehensive grid impact study is indispensable. This paper investigates the impacts of integrating a mix of DERs in the utility distribution network in Colorado, U.S. Firstly, BTM DERs at the residential scale including distributed PV; battery energy storage systems (BESS); heating, ventilation, and air-conditioning (HVAC) load; electric water heater (EWH) load; and EVs are modeled. The impacts of integrating these resources on the distribution network are evaluated by conducting time-series simulations for different scenarios considering different days to capture the worst-case conditions. Monte Carlo simulations are conducted to generate the realistic EV charging profile. The voltage issues, substation transformer loadings, and critical nodes in the network are identified with the incorporation of uncoordinated EV charging loads and other DER in the network. This analysis helps visualize the DER impact on the grid, identify the challenges, and provides an insight into the new distribution management and control needs to enable reliable and resilient distribution grid operations. Additionally, further analysis is performed to estimate the daily residential electricity cost with the inclusion of DERs under time-of-use tariffs. The result shows the daily residential electricity cost reduced by 20:7% on average with DERs compared to the case without DERs.

27 ARPA - Advanced Research Projects Agency-Energy↗

All Hazards Approach to Grid Modernization

Resilience hazards for electric power systems are on the rise, exacerbated by both a rise in extreme weather events and manmade physical and cyber attacks. At the same time, grid modernization challenges plague the United States, covering everything from increased electrification and ambitious renewable energy targets to aging infrastructure and regulation that lags behind today’s challenges. This talk will cover an all-hazards risk based approach that addresses both rising resilience and grid modernization challenges. Examples of this approach taken for national laboratory research projects will be discussed, including a deep dive into a project that addressed black start, resynchronization, distributed control, and cybersecurity challenges for an operational microgrid up to sub-transmission voltages. As takeaways from this project are translated from demonstration scale to real-world exercises, key lessons are noted on the translation from research into practice and how this can inform risk-based research moving forward

17 WIND ENERGY↗

POWER ELECTRONICS GRID TIED SYSTEM FINAL REPORT

Across the country, electric utilities are grappling with the persistent hurdles of integrating Distributed Energy Resources (DERs). Managing these assets safely and effectively is a complex endeavor, complicated by varying ownership structures, management philosophies, and the diversity of the technologies themselves. Consequently, the industry has seen a proliferation of bespoke system designs, control strategies, and communication frameworks—forcing utilities to spend significant time and resources developing one-off integration solutions. This project addressed these integration hurdles through a scalable demonstration of intelligent devices designed to coordinate and control diverse resources in low-voltage applications. This concept minimized the need for complex integration by transforming the separate DERs into a dispatchable virtual power plant (VPP) with integrated resiliency functions (called a Node). By collaborating with a utility partner, the project focused on developing rapidly implementable use cases that bridged the gap between theoretical control and real-world deployment

99 GENERAL AND MISCELLANEOUS↗

Network-Aware and Welfare-Maximizing Dynamic Pricing for Energy Sharing: Preprint

The proliferation of behind-the-meter (BTM) distributed energy resources (DER) within the electrical distribution network presents significant supply and demand flexibilities, but also introduces operational challenges such as voltage spikes and reverse power flows. In response, this paper proposes a network-aware dynamic pricing framework tailored for energy-sharing coalitions that aggregate small, but ubiquitous, BTM DER downstream of a distribution system operator's (DSO) revenue meter that adopts a generic net energy metering (NEM) tariff. By formulating a Stackelberg game between the energy-sharing market leader and its prosumers, we show that the dynamic pricing policy induces the prosumers toward a network-safe operation and decentrally maximizes the energysharing social welfare. The dynamic pricing mechanism involves a combination of a locational ex-ante dynamic price and an ex-post allocation, both of which are functions of the energy sharing's BTM DER. The ex-post allocation is proportionate to the price differential between the DSO NEM price and the energy sharing locational price. Simulation results using real DER data and the IEEE 13-bus test systems illustrate the dynamic nature of network-aware pricing at each bus, and its impact on voltage.

energy communities↗

Tri-Sectional Approximation of the Shortest Path to Long-Term Voltage Stability Boundary with Distributed Energy Resources

Ensuring long-term voltage stability is critical for reliable operations of power grids. High share of distributed energy resources (DERs) can create complicated system operation modes that may invalidate the traditional long-term voltage stability analysis based on typical operation modes. To address this challenge, this paper investigates how to compute the shortest path to the voltage stability boundary in the DER aggregated load space with large dispersion. Instead of working in the Euclidean space, we establish the analysis and computations on the algebraic power flow manifold to better capture the curvature change of the shortest path along the direction of losing stability. A modified optimal control framework is presented for obtaining the ground-truth of the smooth shortest path on the manifold. To efficiently and accurately solve for the shortest path, we further leverage the geometric features of the power flow manifold and propose a tri-sectional approximation model that is scalable for large-scale systems. Several numerical examples, up to the 1354-bus system, with different DER penetration levels and high dimensional renewable power injection variations are evaluated. The simulation results demonstrate that the tri-sectional approximation achieves high accuracy and efficiency to approximate the shortest path to the voltage stability boundary.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Novel Decentralized PWM Interleaving Technique for Ripple Minimization in Series-Stacked DC-DC Converters: Preprint

Cascaded dc-dc converters are commonly used in applications where distributed energy sources or loads are connected to elevated voltage levels for power transfer. In such systems, it is advantageous to minimize the ripple on the bus current and voltage by proper phase shifting of the pulse-width modulation (PWM) pulses among the converters via a method known as interleaving. Existing approaches use either a centralized controller or separate communication lines among the stacked converters to control their relative PWM switch transitions. The key drawbacks are that these methods entail significant wiring, the central controller acts as a single point of failure, and implementation on very large numbers of units is impractical. In this paper, we introduce a decentralized interleaving control (DIC) strategy that acts on local current measurements at every converter and achieves communication-free PWM interleaving among the series-stacked converters. The proposed controller is simple in structure and is shown to converge asymptotically to the interleaved state irrespective of clock drifts among the digital signal processors. Experimental results are provided for a system of five series-connected converters showing a 10 times reduction in the current ripple compared to normal operation.