Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “smart grid control”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

AI-Driven Smart Community Control for Accelerating PV Adoption and Enhancing Grid Resilience

The U.S. Department of Energy (DOE) has launched a Connected Communities program that supports projects that expand DOE's network of grid-interactive, efficient building communities nationwide. As an early pilot of Connected Communities, the National Renewable Energy Laboratory (NREL) and its partners have developed and demonstrated a community-scale, hierarchical control solution to address the potential grid issues arising from high penetration of solar photovoltaics (PV) as well as to improve grid reliability and resilience in this residential community. A field pilot study has been performed at an affordable housing development called the Basalt Vista Community, which was built for school teachers and other professionals in the local workforce and represents an autonomous energy grid with all-electric, energy-efficient homes. With no natural gas line in the community, this is the first all-electric net-zero community in rural Colorado. In the field pilot study, NREL has validated the performance of the hierarchical control solution, which consists of NREL's foresee home energy management systems (HEMS) and community aggregators, in increasing demand flexibility and self-consuming PV, reducing potential over-voltages, and supporting critical loads during emergency events. In this presentation, we will present the methodology, simulation and field pilot results, and lessons learned from the project.

all-electric community↗

Online distributed price-based control of DR resources with competitive guarantees

Demand response (DR) of building HVAC load can provide crucial demand-side flexibility for the future smart grid. Compared to direct load control, price-based control can respect the customers’ autonomy and privacy. However, it is challenging for price-based control to attain provable performance guarantees under future uncertainty. In this paper, we propose a framework for a utility to perform price-based control of flexible building load within the utility’s service area, in order to attain competitive performance guarantees in terms of controlling the system peak demand under future uncertainty. By adopting a two-step approach, our online price-based control solution can attain a provable competitive ratio for all possible realizations within a given uncertainty set. Simulation experiments demonstrate that, with a robustification procedure, our solution can perform well not only for worst-case inputs, but also for average-case inputs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Real-Time Testbed for Studying Cyberattacks and Defense in DER-integrated Smart Inverter Systems

In this paper, we propose a Hardware-in-the-Loop (HIL) simulation testbed suitable for the implementation and testing of realistic cyberattacks on grid-tied smart inverter systems integrated with Distributed Energy Resources (DER) that use the Distributed Network Protocol-3 (DNP3) protocol for communications between grid components. Specifically, our testbed combines a Real-Time Digital Simulator (RTDS) NovaCor device, outfitted with GNETx2 network interface cards, a gridtied DER topology implemented via the RTDS software package RSCAD, and a custom virtual network that emulates a man in the middle attacker. The Man-in-the-Middle (MITM) attacker captures DNP3 traffic and falsifies telemetry data in DNP3 packets to trigger unwarranted commands from a DNP3 controller that exploit smart inverter grid support functions. We choose DNP3 and implement grid support functions according to the IEEE Std. 1547-2018 mandated for the interconnection and interoperability of DER power systems with associated power components. Furthermore, we develop a protocol payload agnostic attack detection framework that leverages the round-trip time (RTT) anomalies between DNP3 requests and responses and can detect the presence of attacks without having to analyze the payload’s contents, while balancing trade-offs between false alarm counts, missed detections, and time to detection. To facilitate further research, we publicly release benign and attack network traffic exchanged between various sensors, controllers, and actuators in our grid-tied inverter testbed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power and Communications Hardware-in-the-Loop CPS Architecture and Platform for DER Monitoring and Control Applications: Preprint

The rapid growth of distributed energy resources (DERs) has prompted increasing interest in the monitoring and control of DERs through hybrid smart grid communications. The deployment of communications and computation has transformed the traditional physical power grid into a smart cyber-physical system (CPS). To fully understand the interdependency between physical grid and cyber netowrks, this study designed a power and communications hardware-in-the-loop (PCommHIL) CPS architecture, which enables the flexible verification of DER monitoring and control with hybrid communications architectures and Internet protocols. Design, development and case study of a PCommHIL testbed for the DER coordination are discussed in detail, and the proposed platform integrates DER devices, Advanced Metering Infrastructures (AMIs), and a suite of hybrid communications networks for distribution automation applications. Case study on DER situational awareness and Volt-Var control validates the efficacy of this proposed PCommHIL platform with hybrid communications designs. Results show that the HAN communication technologies play a critical role in hybrid designs and it is the bottleneck for DER applications. High performance communication technologies are highly recommended to be applied in the HAN for enhanced monitoring and real-time control of DERs.

AMIs↗

Solid-State Transformer and Hybrid Transformer With Integrated Energy Storage in Active Distribution Grids: Technical and Economic Comparison, Dispatch, and Control

Solid-state transformer (SST) and hybrid transformer (HT) are promising alternatives to the line-frequency transformer (LFT) in smart grids. The SST features medium-frequency isolation, full controllability for voltage regulation, reactive power compensation, and the capability of battery energy storage system (BESS) integration with multiport configuration. The HT has a partially-rated converter for fractional controllability and can integrate a small BESS. Fast grid-edge voltage fluctuations from increased solar photovoltaic (PV) and electric vehicle (EV) penetration are difficult to manage for mechanical load tap changers. Hence, along with the trend towards more BESS in the grid, the controllability and the storage integration capability of the SST and HT are of strong interest. However, a review of literature shows existing SST and HT research is mostly at converter level, while system-level assessments are scarce. Assessing technical and economic impacts is critical to understanding the benefits and role of the SST and HT to guide future research, which is presented for the first time in this article. Experimental results from medium-voltage (MV) SST and MV HT prototypes are shown to confirm equipment-level feasibility, where the voltage controllability waveforms of a MV HT prototype are reported for the first time. Comparative simulations are performed on a modified IEEE 34-bus system. Here, a grid-model-less decentralized grid-edge voltage control method and a day-ahead BESS dispatch method are proposed for the SST and HT. The simulations show that the SST and HT with integrated storage can host more PV, achieve peak shaving, mitigate voltage fluctuation and reverse power flow, and support energy arbitrage for operational cost reduction, as compared to the LFT. Moreover, comprehensive analyses of net present value (NPV) and internal rate of return (IRR) are performed under different installed PV capacities, HT’s partial converter ratings, and BESS capacities. Sensitivities to future cost reductions of the PV and BESS are studied. Although the NPV and IRR are currently negative, 60% capital cost reduction or 150% revenue increase will make the SST and HT economically viable in the use case studied.

14 SOLAR ENERGY↗

Experimental Evidence on Latency in a Fleet of Controllable Water Heaters

Demand response is an important emerging part of smart grids with wide coverage in theoretical and modeling research. However, experimental evidence on the real-life behavior of controllable loads is still limited. We present observations regarding latency and communication aspects of the operation on a fleet of residential water heaters in a smart neighborhood in Atlanta, GA. Our analysis shows that latency in water heaters is not constant and does not follow a Gaussian distribution. We also find that there is a systematic relationship between latency and hour of the day. Latency was found to increase during morning and evening hours compared to the afternoon. These findings could help better plan deployment of control for demand response programs. Understanding delays associated with controlling smart devices is crucial for proper design and algorithm development for optimization, frequency of dispatch, and override detection.

communication delay↗

Efficient Phasor-Based Dynamic Volt/VAr and Volt/Watt Analysis of Large Distribution Grid with High Penetration of Smart Inverters

As the penetration of power-electronics based smart inverters (SIs) is increasing in distribution grids, it adds computational challenges in solving dynamic models of large-scale distribution feeders. Voltage and reactive power (Volt/VAr), and voltage and active power (Volt/Watt) dynamics have been analyzed at slower time scales akin to the control of legacy grid devices. However, smart inverters, being power-electronics based devices, can provide dynamic active/reactive power support at a faster time scale, which necessitates Volt/VAr and Volt/Watt dynamics to be analyzed at a faster time scale. The existing dynamic models are overly detailed and computationally intractable for distribution feeders with a large number of inverters. In this context, this proposed work aims towards developing a computationally tractable, scalable, and accurate phasor-based model for dynamic Volt/VAr and Volt/Watt analyses of large distribution systems with high penetration of smart inverters. Case studies demonstrate that the proposed phasor-based model sufficiently captures the Volt/VAr and Volt/Watt dynamics, and is computationally faster by one order of magnitude compared to the average model and by two orders of magnitude compared to the detailed switching model. Case studies also demonstrate the efficacy and scalability of the proposed model in analyzing Volt/VAr and Volt/Watt dynamics of large-scale power networks with hundreds of SIs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Novel Authentication Management for the Data Security of Smart Grid

Bidirectional wireless communication is employed in various smart grid components such as smart meters and control and monitoring applications where security is vital. The Trusted Third Party (TTP) and wireless connectivity between the smart meter and the third party in the key management-based encryption techniques for the smart grid are expected to be totally trustworthy and dependable. In a wired/wireless medium, however, a man-in-the-middle may seek to disrupt, monitor and manipulate the network, or simply execute a replay attack, revealing its vulnerability. Recognizing this, this study presents a novel authentication management (model) comprised of two layer security schema. The first layer implements an efficient novel encryption method for secure data exchange between meters and control center with the help of two partially trusted simple servers (constitutes the TTP). In this setting, one server handles the data encryption between the meter and control center/central database, and the other server administers the random sequence of data transmission. The second layer monitors and verifies exchanged data packets among smart meters. It detects abnormal packets from suspicious sources. To implement this node-to-node authentication, One class support vector machine algorithm is proposed which takes advantages of the location information as well as the data transmission history (node identification, packet size, and data transmission frequency). This schema secures data communication, and imposes a comprehensive privacy throughout the system without considerably extending the complexity of the conventional key management scheme.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Adaptive Control of Distributed Energy Resources for Distribution Grid Voltage Stability

Volt-VAR and Volt-Watt functionality in photovoltaic (PV) smart inverters provide mechanisms to ensure system voltage magnitudes and power factors remain within acceptable limits. However, these control functions can become unstable, introducing oscillations in system voltages when not appropriately configured or maliciously altered during a cyberattack. In the event that Volt-VAR and Volt-Watt control functions in a portion of PV smart inverters in a distribution grid are unstable, the proposed adaptation scheme utilizes the remaining and stably-behaving PV smart inverters and other Distributed Energy Resources to mitigate the effect of the instability. The adaptation mechanism is entirely decentralized, model-free, communication-free, and requires virtually no external configuration. Here we provide a derivation of the adaptive control approach and validate the algorithm in experiments on the IEEE 37 and 8500 node test feeders.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Extremum seeking control of distributed energy resources with decaying dither and equilibrium-based switching

Embodiments relate to an operating system coupled to and controlling at least one Distributed Energy Resource (DER) in a smart grid and includes an electricity distribution network and a 2-dimensional Extremum Seeking (2D-ES) controller coupled to network. The electricity distribution network has first and second inputs and one output and maps all active power and reactive power inputs to the smart grid providing measurements of an objective function. The 2D-ES controller controls the DER and includes an active power loop and a reactive power loop. The active power loop is in communication with the first input and the output, governs active power contribution, and receives measurements of the objective function which contain static and oscillatory components. The reactive power loop is in communication with the second input and the output, governs reactive power contribution, and receives measurements of the objective function which contain static and oscillatory components.

Arnold, Daniel↗

On the Use of Smart Meter Data to Estimate the Voltage Magnitude on the Primary Side of Distribution Service Transformers

This paper develops a novel method to estimate the voltage magnitude on the primary side of distribution service transformers. The proposed method relies exclusively on smart meters, and therefore it is fully data-driven. This is an important feature because electric utilities have detailed models of only the primary network - that is, the network between the distribution substation and the primary side of service transformers that are installed closer to end-customer sites. The network that connects the secondary side of service transformers to end-customer sites, referred to as the secondary network, is simply represented by a lumped load. For each secondary network, the proposed method uses data acquired from only 2 smart meters: the closest and the farthest-in the sense of electrical distance - from the service transformer. As a reference to this feature, the proposed method is named SM2Vp. To our knowledge, this is the first time a method is shown to provide actionable information for realtime operation and control of power distribution grids using only two smart meters per secondary network. This is important because utilities have experienced barriers in managing and using large data sets for real-time operation and control. SM2Vp is primarily intended to provide pseudo-measurements for distribution system state estimation, but it can also be used directly for voltage control schemes. The performance of SM2Vp is demonstrated by numerical simulations carried out on three secondary network synthetic models and by using field data provided by a utility partner serving customers in southwestern California. A maximum relative error of approximately 3.9% or less is observed for the primary voltage magnitude estimates in all numerical experiments.

distribution service transformer↗

PUF-Based Two-Factor Authentication Protocol for Securing the Power Grid Against Insider Threat

Recent advances in smart grid technologies have enabled additional distributed control paradigms that allow more efficient and reliable operation. However, this creates new security concerns for the grid, such as attackers using spoofed grid control devices to generate false measurements. This paper introduces a two-factor authentication protocol leveraging standard public-key cryptography as one authentication factor and a hardware-based fingerprint, known as a Physical Unclonable Function, as a second authentication factor. This protocol incurs a small overhead and prevents cyber-attacks even when an adversary is able to compromise the cryptographic keys stored in the non-volatile memory of an intelligent control device.

42 ENGINEERING↗

Cyber Energy Emulation Platform (CEEP) [SWR-20-102]

NREL's Cyber-Energy Emulation Platform (CEEP) provides the capability to realize cyber-energy security and resilience through automation and orchestration of virtualized systems and software defined networks for the electric grid. CEEP enables testing and validation of grid-security and -control methodologies as the grid evolves to include smart technologies/systems, such as virtualization and containerization of grid components, software defined networking, simulation and co-simulation frameworks, and hardware in the loop. CEEP is a modular system that can be distributed and deployed across different hardware infrastructure sizes and network architectures. For example, CEEP can visualize, emulate, and/or coordinate the Smart-Grid Network Visualization, Intrusion Detection, and Network Healing system. Using CEEP, intrusion-detection and network-self-healing solutions can be deployed at grid control centers, within secure private clouds, and in cyber-energy appliances.

Rivera, Joshua↗

A Smart and Flexible Microgrid with a Low-cost Scalable Open-source Controller (Final Report)

This report contains information regarding the activities carried out in the project "A Smart and Flexible Microgrid with a Low-cost Scalable Open-source Controller. The project aims at developing a community-based flexible microgrid (FMG) with smart grid features, including multiple utility feeders and dynamic boundaries that utilize intelligent switches and ultra-high-speed communication links already in a smart grid. The project also aims at developing a corresponding controller for such an FMG with low cost and high scalability. With distributed renewable energy resources (DERs) and the intelligent microgrid controller, the FMG will achieve aggressive emission reduction, increased energy use efficiency, and reliability improvement goals. The FMG and its controller design will be scalable for different geographic areas, load sizes, distributed generation source number and types, and even multiple MGs within a distribution electric power system. In order to achieve these project objectives, three main development tasks were carried out: FMG design, FMG controller development, and FMG controller testing. The fourth task was technology to market.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Demand Response in Residential Energy Code: Technical Brief

As buildings account for over 75% of U.S. electricity use, effectively managing their loads can greatly facilitate the transition towards a clean, reliable grid. Grid-interactive efficient buildings (GEBs) combine efficiency and demand flexibility with smart technologies and communication to provide occupant comfort and productivity while serving the grid as a distributed energy resource (DER). In turn, GEBs can play a key role in ensuring access to an affordable, reliable, sustainable, and modern U.S. electric power system. Their national adoption could provide $\$$100-200 billion in U.S. electric power system cost savings over the next two decades. The associated reduction in CO 2 emissions is estimated at 6% per year by 2030 (DOE 2021). Building codes represent standard design practice in the construction industry and continually evolve to include advanced technologies and innovative practices. Historically, national model energy codes establish minimum efficiency requirements for new construction (ICC 2020). Expanding codes to support GEB capabilities is a pivotal step towards realizing demand flexibility in support of a clean grid by addressing capabilities to improve interoperability between smart building systems, the grid, and renewable energy resources. Realizing GEBs requires buildings with automated demand response (DR) capabilities that enable standardized communication with or control of, subject to explicit consumer consent, energy smart appliances or home energy management systems. This is achieved through direct or indirect (i.e., via an aggregator) communication between appliances and the electric grid. Energy codes can also support DR communication standardization and advance the deployment of building-integrated DERs such as energy storage, generation, and electric vehicles (EVs). Incorporating automated DR capabilities in energy codes provides many benefits to the consumers. Specifically, it aligns building electric load demand with intermittent renewable energy source availability, decreases peak load on the electric grid, allows buildings to respond to utility price signals, supports electrical network reliability and market growth of products and processes aligned with clean economic growth. The incorporation of DR into the model residential energy codes was considered for both the 2021 and 2024 International Energy Conservation Code (IECC) code development cycles. The approved DR measures in the 2021 cycle were removed in response to appeals (ICC 2020). Updated language was presented for consideration again for the 2024 IECC, where it was negotiated and again approved, and again removed in response to appeals (ICC 2024). This resulted in many sections, including sections on demand responsive controls, being moved to the credits options or an appendix as a voluntary application. This technical brief updates the proposed DR components such that they can be considered by states and local governments for direct incorporation into their codes, as well as for future IECC energy code development. The proposal refinements are intended to support consistency in approach and provide a degree of certainty for building owners, designers, contractors, manufacturers, and building and fire safety professionals. The scope of this technical brief includes three strategies for DR in residential buildings: 1) smart thermostats with demand-responsive control, 2) electric water heating incorporating demand-responsive controls and communication and 3) grid Integrated solar and energy storage systems.

2021 IECC↗

Optimal Control of SOEC-Based Hydrogen Production Systems for Demand Response Using Deep Reinforcement Learning in Smart Grids

Solid oxide electrolysis cell (SOEC) hydrogen production technology can range in size from small, appliance-size equipment to large-scale, central production facilities that can be tied directly to renewable or non-greenhouse-gas-emitting forms of electricity production, making it an ideal resource for demand response (DR). The SOEC hydrogen production system is a complex integrated system that encompasses fluid dynamics, electrical dynamics, and electrochemical and thermal dynamics, all of which involve non-linearity and non-convexity. Proper control of the SOEC hydrogen production system is crucial to enable its participation in the DR program. Here, to overcome the difficulty of designing an explicit control law for such nonlinear systems with nonconvex optimization features in DR applications, deep reinforcement learning (DRL) is explored to achieve the optimal control of the SOEC system for DR participation. Specifically, a twin delayed deterministic policy gradient (TD3) control framework is applied to achieve optimal response performance during DR events by considering power tracking error and hydrogen production efficiency with a suitable reward function. Two case studies with grid connections for tracking different DR commands were investigated. The first case study involved operating conditions reaching the boundaries, while the second involved operating conditions within the boundaries. The results showed that the proposed DRL-based control for SOEC can track the DR signal in a timely manner while maintaining high energy efficiency.

08 HYDROGEN↗

Peak Reduction Using Mode Adjustment of Heat Pump Water Heaters in a Residential Neighborhood

Building electrification is putting pressure on distribution grid worldwide. Peak reduction is an important concern that can help reduce the growing stress and allow to defer investments in new capacity. Water heaters represent a convenient way of reducing peak because they are less dependent on weather, and their storage volume allows for asynchronous water heating and hot water use. Previous empirical studies investigated the ability of water heaters to reduce peak through the adjustment of the temperature setpoint. However, not all equipment vendors offer this option. This study aims at understanding the feasibility of peak reduction with an alternative configuration available in the market - by adjusting the device mode rather than temperature setpoint. The peak reduction methodology is tested in an occupied 46-townhome neighborhood located in Atlanta, GA. We find that peak shifting is possible with the adjustable mode approach, with the change in the peak load by 30-60%.

demand response↗