Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “primary frequency control”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Distribution Feeder-Scale Fast Frequency Response via Optimal Coordination of Net-load Resources Part II: Large-Scale Demonstration

This work is the second of a two-part series in which we develop and experimentally demonstrate a hierarchical control solution for optimally coordinating thousands of deferrable loads and distributed energy resources (DERs) to provide fast frequency response (FFR) from an entire distribution feeder. In Part I, we developed and proved practical algorithms for fast, cost-based optimal dispatch and for determining the optimal amount of headroom to operate solar inverters with to support FFR dispatch while minimizing opportunity cost. Simulation results in Part I demonstrated the advantages of the hierarchical dispatch approach in being able to maintain fast solution times needed for FFR even when the problem size increases. In Part II, we implement the algorithms developed in Part I in a novel, large-scale power hardware-in-the-loop experiment including embedded controllers and more than 100 powered appliance loads and DER connected to a simulated real-world distribution system with more than 10,000 controlled devices. Experimental results from multiple scenarios confirm that the optimal FFR dispatch approach scales well and can optimally coordinate more than 10,000 net-load resources across a distribution network while achieving hardware response times within 500 ms, which is not possible using state-of-the-art optimal coordination approaches.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distribution Feeder-Scale Fast Frequency Response via Optimal Coordination of Net-load Resources Part I: Solution Design

This work is the first of a two-part series that develops and experimentally demonstrates a first-of-its-kind hierarchical control solution for optimally dispatching thousands of deferrable loads and distributed energy resources (DERs) across a distribution feeder to provide fast frequency response (FFR) within 500 ms to the bulk power system. This approach rapidly coordinates resources online after a frequency event occurs, allowing fast-changing, behind-the-meter (BTM) resources to be incorporated and aggregate FFR power set points to be achieved more quickly and accurately than existing approaches. We also present a solution for determining the optimal amount of headroom to operate solar inverters with to minimize opportunity cost while ensuring the FFR response viability of a building with the inverter and deferrable loads. In Part I, we develop practical algorithms for fast, cost-based optimal dispatch at multiple aggregation scales (single building, multiple buildings, and full distribution feeder), establish their optimality, and demonstrate via simulation that they are faster than state-of-the-art, coordinated frequency response approaches. In Part II, the entire platform is implemented and experimentally verified using a unique power hardware-in-the-loop demonstration, including more than 100 powered loads and DERs connected to a real-world distribution network model and over 10,000 net-load resources dispatched.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Improving Primary Frequency Response in Networked Microgrid Operations using Multilayer Perceptron-Driven Reinforcement Learning

Individual microgrids can improve the reliability of power grids during extreme events, and networked microgrids can further improve efficiency through resource sharing and increase the resilience of critical end-use loads. However, networked microgrid operations are subject to large switching transients, which can cause dynamic instability and lead to system collapse. These transients are especially prevalent in microgrids with high penetrations of inverter-connected renewable energy resources, which do not provide the system inertia needed to mitigate the transients. Existing generator controls can be modified to invoke a drop in terminal voltage in response to a frequency deviation, thereby reducing load and improving frequency response. This paper investigates the use of a reinforcement-learning--based controller trained over several switching transient scenarios to modify generator controls during large frequency deviations. Compared to previously used proportional integral controllers, the proposed controller can improve primary frequency response while adapting to changes in system topologies and events.

Radhakrishnan, Nikitha↗

Testing and Analysis of Grid Forming Inverter Control for Achieving Resilient and Economic Operation of an Islanded Microgrid

This investigation examines the feasibility of operating a battery energy storage system (BESS) in parallel with synchronous generation by using grid forming (GFM) control in order to achieve frequency control objectives while mitigating increases to operating costs in the context of an islanded microgrid. The BESS GFM control system, which is based on conventional droop techniques, is modeled along with the overall microgrid using the Real Time Digital Simulator (RTDS) to allow for integration of genset controller hardware. A series of simulations are performed to test the voltage and frequency regulation capability of the BESS control system when the primary frequency regulating genset is tripped offline. The results of the simulations suggest that the GFM control scheme will successfully maintain frequency and voltage stability, which will enable operation without a back-up genset while not compromising the microgrid resiliency to contingencies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Adaptive Load Shedding as Part of Primary Frequency Response To Support Networked Microgrid Operations

Global changes in the deployment of distributed energy resources, control and communications technologies, business models, and regulatory policy are increasing the operational options for future distribution systems. One such option is the coordinated operation of distributed resources to form microgrids and networks of microgrids to support traditional bulk power systems during normal operations and critical end-use loads during outages. While individual standalone microgrids have been extensively studied and deployed, the coordinated operation of networked microgrids is operationally more challenging due to the dynamic boundaries and changing mix of generation resources. Here, this paper presents a method of using a distributed control architecture to support primary frequency response in networked microgrids operations. The support of primary frequency response is accomplished using the Open Field Message Bus reference architecture and Grid Friendly Appliance controllers.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

A Comparison of Multivariable Control Design Techniques for a Turbofan Engine Control

This paper compares two previously published design procedures for two different multivariable control design techniques for application to a linear engine model of a jet engine. The two multivariable control design techniques compared were the Linear Quadratic Gaussian with Loop Transfer Recovery (LQG/LTR) and the H-Infinity synthesis. The two control design techniques were used with specific previously published design procedures to synthesize controls which would provide equivalent closed loop frequency response for the primary control loops while assuring adequate loop decoupling. The resulting controllers were then reduced in order to minimize the programming and data storage requirements for a typical implementation. The reduced order linear controllers designed by each method were combined with the linear model of an advanced turbofan engine and the system performance was evaluated for the continuous linear system. Included in the performance analysis are the resulting frequency and transient responses as well as actuator usage and rate capability for each design method. The controls were also analyzed for robustness with respect to structured uncertainties in the unmodeled system dynamics. The two controls were then compared for performance capability and hardware implementation issues.

Garg, Sanjay↗

State-Constrained Grid-Forming Inverter Control for Robust Operation of AC Microgrids

The control of grid-forming inverters has become an important problem to achieve high efficiency, reliability, and resilience of the future power grid. The distributed control that utilizes a sparse communication network has been proposed for AC microgrids, in which each DG only has access to the information of a small number of its neighboring DGs, reducing the computational complexity and improving the resiliency to faults and unknown parameters. However, these approaches have not provided a clear analysis of the coupling between active/reactive power injections and the voltage magnitude/frequency or a distributed updating law with a solid theoretical foundation. Additionally, in the existing approaches, tracking the references from the secondary control may violate operational constraints.

Xu, Ying↗

Software Control Program For Transportable Microgrid State-of-charge Balancing And Frequency Stability Controls

A deterministic state-of-charge (SOC) balancing approach software control code is introduced as an integral secondary management to primary control layer of an islanded small microgrid or nanogrid system made up of multiple grid-forming inverter/battery/solar combination systems, where each set of batteries with each inverter are on independent DC buses (i.e. non-paralleled on the DC sides). A DERMS-level control approach, algorithm and automation controller program was developed to improve coordination and enable microgrid asset compliance and SOC balancing, enabling provision of a system-level power stability support architecture, load support, and asset scalability. The architecture is configured to treat each unit or micro/nano-grid as a node in a microgrid network, allowing for autonomous DERMS control regarding load and SOC balancing and power stability. As the network grows with the addition of units, greater coordination efforts may be required. The ideal small network microgrid ranges from 2-10 inverter/battery units before additional control parameters must be considered in the existing architecture. The control approach focuses on a deterministic state-of-charge analysis as the primary level control process followed by a secondary control loop using a forced frequency-watt droop strategy to conform off-the-shelf components into behaving under a leader-follower configuration. Adopting this control scheme has been shown to allow for a balanced, unit-coordinated microgrid network, enabling stable power flow. The deterministic state-of-charge approach is introduced as an integral primary control layer of an islanded small network microgrid. A standard strategy for SOC balancing is implementing a battery management system (BMS) to control SOC on the DC side. An alternative approach is to determine how to coordinate sending and receiving power on the AC side with multiple units. The latter approach assesses all the integrated units in the microgrid network. Once the individual units are identified, further system data is required to calculate each unit's total kWh, provided information about its capability to supply or consume kWh and availability. The secondary control layer in the multi-layered small network microgrid methodology uses the primary layer’s decision to initiate frequency setpoint changes, initializing the SOC balancing. The secondary control layer considers numerous system-dependent variables to enable a charging and discharging profile based on adjustable frequency setpoints. The combined architecture will result in stable, coordinated power flow enhancing an AC microgrid's functionalities.

Myers, KurtS [Idaho National Laboratory (INL), Ida↗

Reinforcement Learning-Based Secondary Control Strategy for Voltage and Frequency Regulation in Islanded Inverter-Based Microgrids

This paper presents a reinforcement learning (RL) approach for secondary voltage and frequency control in islanded inverter-based microgrids. The proposed control strategy aims to restore voltage and frequency deviations caused by the primary droop control while ensuring proper power sharing between distributed generators. The RL agent is designed to provide correction signals to the primary control, considering communication delays and system constraints. The effectiveness of the proposed control strategy is validated through simulation results in MATLAB/Simulink environment, demonstrating superior performance in maintaining voltage and frequency within the nominal values.

Rodriguez Martinez, Omar Felipe [University of Pue↗

MAFRIT (Multi-Area Frequency Response Integration Tool)

The Multi-Area Frequency Response Integration Tool (MAFRIT) is the only software tool of its kind that integrates primary frequency response (turbine governor control) with secondary frequency response (automatic generation control). It simulates the power system dynamic response in full time spectrum with variable time steps from millisecond to minutes to hours and days. Capable of simulating both normal and event conditions, this tool can represent real power system operations and thus evaluate the primary and secondary reserves adequacy. This unique interaction of a turbine governor model and a novel automatic generation control model places special emphasis on electric power systems with high penetrations of renewable generation.

Himanshu, Jain↗

Interactive Power to Frequency Dynamics Between Grid-Forming Inverters and Synchronous Generators in Power Electronics-Dominated Power Systems

With increased attention on grid-forming inverters as a power system stabilizing device during high shares of inverter-based resource operations, there is a present need for a transparent and methodical investigation of the inverted and direct power to frequency control capabilities and impacts of these devices on emerging power systems. Here, analysis of the frequency dynamics of the droop-controlled grid-forming inverter and the synchronous generator illuminates the inverted active power-frequency relationship and the frequency response order reduction, forming the basis for novel, nonlinear frequency control approaches. Device-level electromagnetic transient domain simulations corroborate the order-reduction findings, establish that a properly designed dc-side system has a negligible impact on power transfer and will not impede frequency regulation, and confirm the primary frequency response improvement with nonlinear control. Simulations of the 9- and 39-bus test systems validate the order reduction and associated decoupling of the nadir and rate of change of frequency in larger networks. Oscillatory mode analysis confirms the grid-forming benefit of increased damping; decreased damping is observed at shares above 80%, but not at 100%. Finally, simulations on a validated Maui power system model with a 96% of inverter-based resources model yield a trend toward a first-order response.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Advanced Sensor Deployment for Distribution System State Estimation and Fault Identification

Distribution systems are currently facing steep operational challenges as a result of the rapidly increasing integration of renewables and other distributed energy resources (DERs) at both the primary and secondary circuit levels. Distribution utilities and system operators have traditionally had some visibility of their primary circuits using low-frequency supervisory control and data acquisition systems, and they have had very poor if not zero visibility of the secondary circuits where the presence of DERs is constantly increasing. Therefore, this paper presents simulation studies to demonstrate the benefits of an advanced, high-fidelity sensor technology, called as the Meta-Alert System (MAS), developed by Electrical Grid Monitoring, Ltd. (EGM), on the distribution grid. First, a reliable model of the EGM sensors is developed, and then two use cases, distribution system state estimation (DSSE) and fault identification are simulated to evaluate the performance of the MAS technology. Simulation results on the Electric Power Research Institute J1 feeder demonstrate that the MAS can effectively participate in system-level DSSE programs and can detect and locate faults faster than traditional distribution protection schemes.

distribution system↗

Model Based Predictive Control for Frequency Support in Multi-port Autonomous Reconfigurable Solar Plants

Primary frequency support functionality can be an added advantage for any new grid integrated power electronics resource. With increased penetration of power electronics resources, inertial and primary frequency response capabilities are decreasing. In this research paper, an advanced model-based predictive control (MBPC) algorithm for providing frequency support to a new topology of integrated photovoltaic(PV), batterybased energy storage systems (ESS), and high-voltage direct current (HV dc) systems called multi-port autonomus reconfigurable solar (MARS) plants is based on the synchronverter-based control. The simulation of MARS-HV dc system with proposed control strategy is simulated and validated for MARS connected to low short circuit ratio (SCR) grids in PSCAD/EMTDC simulation environment. The control algorithm proposed showcases better performance in terms of frequency nadir improvement and frequency steady state improvemnt with respect to no frequency control.

Marthi, Phani Ratna Vanamali↗

Tuned Chamber Core Panel Acoustic Test Results

This report documents acoustic testing of tuned chamber core panels, which can be used to supplement the low-frequency performance of conventional acoustic treatment. The tuned chamber core concept incorporates low-frequency noise control directly within the primary structure and is applicable to sandwich constructions with a directional core, including corrugated-, truss-, and fluted-core designs. These types of sandwich structures have long, hollow channels (or chambers) in the core. By adding small holes through one of the facesheets, the hollow chambers can be utilized as an array of low-frequency acoustic resonators. These resonators can then be used to attenuate low-frequency noise (below 400 Hz) inside a vehicle compartment without increasing the weight or size of the structure. The results of this test program demonstrate that the tuned chamber core concept is effective when used in isolation or combined with acoustic foam treatments. Specifically, an array of acoustic resonators integrated within the core of the panels was shown to improve both the low-frequency absorption and transmission loss of the structure in targeted one-third octave bands.

Schiller, Noah H.↗

Design and Evaluation of a Model-Free Frequency Control Strategy in Islanded Microgrids with Power-Hardware-in-the-Loop Testing

The deterioration of inertial and primary frequency response of islanded microgrids has been a crucial issue for the proper operation of such microgrids. Several approaches, including inertia emulation strategies, have been proposed to improve the primary frequency response. However, the demonstrations of most inertia emulation research works are based on simulation-only testing which hinder their applicability in the field. In this paper, a novel model-free control (MFC) strategy for frequency response support in a diesel-wind microgrid system is presented, and it is tested for evaluation using a power-hardware-in-the-Ioop (PHIL) platform. The PHIL testing is one step closer to field testing since it allows real-time verification and accounts for the nonlinear grid dynamics, noise, and time delays that are usually ignored in simulation-only environments. The proposed MFC strategy is fully distributed, has low computational requirements, and can be easily implemented in resource constrained devices such as smart inverters. A PHIL microgrid platform consisting of two type-3 wind turbine generators and one diesel generator is used to test the proposed MFC strategy.

Ferrari Maglia, Max↗

Frequency Recovery in Power Grids Using High-Performance Computing

Maintaining electric power system stability is paramount, especially in extreme contingencies involving unexpected outages of multiple generators or transmission lines that are typical during severe weather events. Such outages often lead to large supply-demand mismatches followed by subsequent system frequency deviations from their nominal value. The extent of frequency deviations is an important metric of system resilience, and its timely mitigation is a central goal of power system operation and control. This paper develops a novel nonlinear model predictive control (NMPC) method to minimize frequency deviations when the grid is affected by an unforeseen loss of multiple components. Our method is based on a novel multi-period alternating current optimal power flow (ACOPF) formulation that accurately models both nonlinear electric power flow physics and the primary and secondary frequency response of generator control mechanisms. We develop a distributed parallel Julia package for solving the large-scale nonlinear optimization problems that result from our NMPC method and thereby address realistic test instances on existing high-performance computing architectures. Our method demonstrates superior performance in terms of frequency recovery over existing industry practices, where generator levels are set based on the solution of single-period classical ACOPF models.

nonlinear model predictive control↗

Interaction of feel system and flight control system dynamics on lateral flying qualities

An experimental investigation of the influence of lateral feel system characteristics on fighter aircraft roll flying qualities was conducted using the variable stability USAF NT-33. Forty-two evaluation flights were flown by three engineering test pilots. The investigation utilized the power approach, visual landing task and up-and-away tasks including formation, gun tracking, and computer-generated compensatory attitude tracking tasks displayed on the Head-Up Display. Experimental variations included the feel system frequency, force-deflection gradient, control system command type (force or position input command), aircraft roll mode time constant, control system prefilter frequency, and control system time delay. The primary data were task performance records and evaluation pilot comments and ratings using the Cooper-Harper scale. The data highlight the unique and powerful effect of the feel system of flying qualities. The data show that the feel system is not 'equivalent' in flying qualities influence to analogous control system elements. A lower limit of allowable feel system frequency appears warranted to ensure good lateral flying qualities. Flying qualities criteria should most properly treat the feel system dynamic influence separately from the control system, since the input and output of this dynamic element is apparent to the pilot and thus, does not produce a 'hidden' effect.

Bailey, R. E.↗

Universal Passive Synchronization Method for Grid-Forming Inverters Without Mode Transition

Power systems are transforming with increasing levels of inverter-based resources (IBRs). This transformation requires critical roles of grid-forming (GFM) inverters replacing synchronous generators for bulk power system stabilization and ancillary services, also allowing flexible power system operation, such as microgrid that is operated by multiple GFM IBRs to achieve system resilience against contingencies. To realize the resilient power systems allowing flexible in-and-out operation of GFM IBRs potentially programmed with different primary controls, a synchronization method universally applicable, i.e., independent of control types, would be beneficial to ease the integration process, but it has not been actively studied. To fill the gap, this paper proposes a universal synchronization method that achieves a passive synchronization to enable a smooth transition in a grid with off-nominal system parameters, i.e., voltage and frequency. The logic proposed requires no modification on the primary control, thus applicable to any type of GFMs with a voltage reference input. To validate the concept, a simulation of an IEEE 13-bus benchmark system modified with 3 GFM inverters is presented. It simulates an inverter-driven black start scenario in which GFM inverters autonomously turn on and connect to the grid under heavy loading, using the synchronization logic. The case study demonstrates that GFM inverters can tune their voltage reference to smoothly synchronize without severe transients, and contribute to a seamless black start of the grid under unbalanced load conditions. Two GFM methods - Droop and dispatchable virtual oscillator control - are used for the demo to validate feasibility and interoperability of the passive synchronization.

black start↗