Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “power system oscillation”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

A Practical On-line Framework for a Modified Energy Detector by Whitening Ambient PMU Data

A key application of Phasor Measurement Units (PMUs) is power system oscillation detection. An energy detector is a straightforward detection method, but setting thresholds requires extensive and time consuming baselining of data. This paper proposes a novel on-line method of whitening PMU measurements supporting a framework for detecting forced oscillations without requiring extensive baselining. An example of 24 hours of actual PMU data illustrates how a forced oscillation is very visible in the energy signal of the whitened data, while being hard to detect in the colored ambient noise. With this framework, the statistical theory for setting thresholds without baselining is much more straightforward and is the focus of future work.

Xu, Zikai↗

Forced Oscillation Source Location in Power Systems Using MVMD-assisted DEF in TF Plane

Fast and accurate forced oscillation source location (FOSL) is critical for mitigating forced oscillations in power systems. Here, to overcome the shortcomings of traditional dissipating energy flow (DEF) in decomposing the forced oscillation components from the measurement responses, a multivariate variational mode decomposition (MVMD)-assisted FOSL is proposed in this paper to locate the forced oscillation sources from measurements in time-frequency (TF) plane. The multi-channel measurement matrix of each generator is formed, then the multi-channel modes are decomposed from the formed multi-channel measurement matrix using the MVMD. Further, the intrinsic mode functions (IMFs) associated with the forced oscillation mode are distinguished from the decomposed modes according to the relative energy weights. With the distinguished IMFs, the MVMD-assisted DEF calculation method is developed to locate the forced oscillation source. Finally, the performance of the proposed method is evaluated using the simulation data of the WECC 179-bus test system and IEEE-NASPI Oscillation Source Location Contest as well as the actual PMU data of ISO New England. The results validated the effectiveness and accuracy of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Forced Oscillation Source Location of Bulk Power Systems Using Synchrosqueezing Wavelet Transform

Forced oscillation source location (FOSL) plays a significant role in mitigating forced oscillations (FOs), which threaten the power system stability. Here, this paper proposes a data-driven approach for FOSL in power systems using synchrosqueezing wavelet transform (SWT). The proposed approach conducts SWT on the measured system responses to obtain the SWT matrix. Then, the SWT-based dissipating energy flow (DEF) model in time-frequency domain and dissipating energy spectrum (DES) model in frequency domain are derived from the traditional DEF model. Further, the characteristics of SWT-based DEF and DES are revealed by referring to the traditional DEF, and the FOSL criteria of the SWT-based DEF and DES can be hereby obtained. Using the obtained FOSL criteria, the FO source can be located from the measured responses. The performance of the proposed FOSL method is evaluated by simulation data of the WECC 179-bus test system and field-measurement PMU data of the ISO New England. The results confirm the accuracy and efficiency of the proposed method in the FOSL.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Practical Event Location Estimation Algorithm for Power Transmission System Based on Triangulation and Oscillation Intensity

Event location in power systems is quite essential information for system operators to enhance control-room situational awareness capability. Therefore, it is of great importance to develop an event location estimation algorithm for transmission systems with high accuracy. With the development of wide-area measurement system (WAMS) such as FNET/GridEye, and the synchrophasor measurement devices (SMDs) such as frequency disturbance recorders (FDRs), the synchronous measurement data including frequency, voltage amplitude and phase angle can be collected and used for event location estimation. First, the phase angle and rate of change of frequency (RoCoF) trajectories are respectively used for determining two sets of wave arrival time associated with each FDR. Then, a convolutional neural network (CNN) is utilized to determine the wave arrival order to select the more suitable set of wave arrival times for a given case and to perform corresponding modifications. Next, the oscillation intensity associated with each FDR is determined based on phase angle trajectories in the center of inertia (COI) coordinate system. Finally, the multiple criteria for event location estimation are represented. In conclusion, case studies and comparisons between the proposed and previous algorithms using actual and confirmed cases in U.S. power systems are performed to demonstrate the effectiveness and improvement of the proposed algorithm in practical applications.

frequency disturbance recorder (FDR)↗

Anomaly Identification of Synchronized Voltage Waveform for Situational Awareness of Low Inertia Systems

Inverter-based resources (IBRs) such as photovoltaics (PVs), wind turbines, and battery energy storage systems (BESSs) are widely deployed in low-carbon power systems. However, these resources typically do not provide the inertia needed for grid stability, resulting in a low-inertia power system. IBRs and lack of inertia have been known to cause anomalies such as waveform distortions and wideband oscillations in power systems due to the limited inertia level, leading to increased generation trips and load shedding. Here, to achieve effective anomaly identification, this paper proposes a synchro-waveform-based algorithm utilizing real-time synchronized voltage waveform measurements from waveform measurement units (WMUs). In the proposed method, different physical characteristics, as well as statistical features, are extracted from synchronized voltage waveform measurements to filter anomalies. Then, the anomaly identification approach based on the random forest is developed and deployed into the FNET/GridEye system considering trade-offs among accuracy, computational burden, and deployment cost. Moreover, four WMUs are specially designed and deployed on Kauai Island to receive instantaneous synchronized voltage waveform measurements. To verify the performance of the proposed algorithm, different experiments are carried out with collected field test data. The result demonstrates that the performance of the proposed synchro-waveform-based anomaly categorization algorithm can accurately identify anomalies 95.35% of the time, which has comparable performance among benchmarking algorithms.

Situational awareness↗

A Twin Circuit Theory-Based Framework for Oscillation Event Analysis in Inverter-Dominated Power Systems With Case Study for Kaua‘i System

Here, this paper proposes a real-world oscillation event analysis framework for power systems that include inverter-based resources together with synchronous generators. Specifically, the proposed framework combines both measurement-and model-based techniques to readily identify potential oscillation sources, replay the oscillation event with numerical simulation, unveil the underlying oscillation mechanism, and suggest mitigation methods for a wide range of oscillation events. To strengthen the theoretical foundation of our analysis framework, this paper proposes a twin circuit theory that provides theoretical support for one key utilized but not well-proven measurement-based oscillation source identification method-Dissipating Energy Flow. Our twin circuit theory also shows that adopting well-tuned grid-forming inverters can be a potential mitigation method for oscillation events. Finally, the effectiveness of our proposed oscillation event analysis framework is demonstrated by addressing a real-world 18-20 Hz oscillation event in Kaua‘i's power system on November 21, 2021.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Feedback and Oscillations: Constructing Feedback Systems for Root Cause Analysis of Oscillations in Power Grids

Dynamic phenomena linked to inverter-based resources (IBRs) have gained global attention. Several IBR-induced dynamics have caused bulk power system-connected wind or solar power plants to trip, and some have even led to widespread outages. In addition, many oscillations have been observed involving IBR power plants. In 2023, the IEEE Power & Energy Society (PES) IBR Subsynchronous Oscillations (SSO) task force published a journal article, “Real-World Subsynchronous Oscillation Events in Power Grids With High Penetrations of Inverter-Based Resources,” in which 19 IBR oscillation events were examined for their causation. Earlier in 2020, another PES task force article, “Definition and Classification of Power System Stability-Revisited & Extended,” authored by prominent academics, introduced converter-driven stability as a new category of stability. The international power grid industry community also took action by publishing the CIGRE Green Book, Power System Dynamic Modelling and Analysis in Evolving Networks (led by Babak Badrzadeh and Zia Emin) in 2024. In August 2024, the Energy Systems Integration Group (ESIG) released a practical guide led by Nick Miller, “Diagnosis and Mitigation of Observed Oscillations in IBR-Dominant Power System: A Practical Guide.” The goal of the guide is to assist practicing engineers in making initial judgments and conducting detailed analyses about oscillations. Finally, when addressing the classification of stability and oscillations, the guide emphasizes a causality-based taxonomy for grouping, such as voltage control-induced oscillations, synchronization-induced oscillations, and frequency or active power control-induced oscillations.

Fan, Lingling [Univ. of South Florida, Tampa, FL (↗

Oscillatory Spreading and Inertia in Power Grids

The increase in variable renewable generators (VRGs) in power systems has altered the dynamics from a historical experience. VRGs introduce new sources of power oscillations, and the stabilizing response provided by synchronous generators (SGs, e.g., natural gas, coal, etc.), which help avoid some power fluctuations, will lessen as VRGs replace SGs. These changes have led to the need for new methods and metrics to quickly assess the likely oscillatory behavior for a particular network without performing computationally expensive simulations. This work studies the impact of a critical dynamical parameter - the inertia value - on the rest of a power system's oscillatory response to representative VRG perturbations. We use a known localization metric in a novel way to quantify the number of nodes responding to a perturbation and the magnitude of those responses. This metric allows us to relate the spread and severity of a system's power oscillations with inertia. We find that as inertia increases, the system response to node perturbations transitions from localized (only a few close nodes respond) to delocalized (many nodes across the network respond). We introduce a heuristic computed from the network Laplacian to relate this oscillatory transition to the network structure. We show that our heuristic accurately describes the spread of oscillations for a realistic power-system test case. Using a heuristic to determine the likely oscillatory behavior of a system given a set of parameters has wide applicability in power systems, and it could decrease the computational workload of planning and operation.

dynamical systems↗

Model-less Source Location for Forced Oscillation based on Synchrophasor and Moving Fast Fourier Transformation

Forced oscillations in power systems occur when the grid is driven by an external and periodic force. To quickly detect and locate the source of the forced oscillation is critical in terms of ensuring the reliability of an interconnected power grid. This paper explores the electromechanical wave propagation theory and the Fast Fourier Transformation to analyze the forced oscillations. It proposes a model-less, adaptive, fast, and accurate source location algorithm. The proposed algorithm is extensively evaluated through simulation data from a 70k-bus U.S. Eastern Interconnection test system and field-collected synchrophasor data from the distribution-level wide-area monitoring system, FNET/GridEye. The evaluation results demonstrate the correctness and effectiveness of the proposed model-less forced oscillation source location algorithm.

Wang, Weikang↗

Framework for Analysis and Quantification of Wide-Area Control Resilience for Power Systems

Wide-area control helps damp the inter-area oscillations in modern power systems. However, compared to traditional local control, it is more vulnerable to cyber attacks due to its dependence on remote real-time-communicated measurements. In this paper, a formal mathematical framework for analyzing resilience of various wide-area controllers under adversarial scenarios is proposed. A novel resilience index based on the $\H_2$ norm of the post-attack closed-loop system is defined. Computation of such an index is, in general, challenging due to the combinatorial nature of the attack profiles and the bilinear nature of the problem. To address these difficulties, a gradient-based path-following-like solution is developed in this paper to solve a relaxed version of the original non-convex problem. Case studies on IEEE 39-bus system are performed to demonstrate the usage of the proposed framework.

Marinovici, Laurentiu D.↗

Stabilize High-IBR Power Systems with Grid-Forming Inverters

The increasing share of IBRs challenges the stable operation of our power systems. Leveraging an oscillation event in Kaua`i Island as an example, we showcase the root cause of this event and highlight the potential of grid-forming inverters to reduce the stability risks in high-IBR power systems.

grid-forming inverters↗

Forced Oscillation Grid Vulnerability Analysis and Mitigation Using Inverter-Based Resources: Texas Grid Case Study

Forced oscillation events have become a challenging problem with the increasing penetration of renewable and other inverter-based resources (IBRs), especially when the forced oscillation frequency coincides with the dominant natural oscillation frequency. A severe forced oscillation event can deteriorate power system dynamic stability, damage equipment, and limit power transfer capability. This paper proposes a two-dimension scanning forced oscillation grid vulnerability analysis method to identify areas/zones in the system that are critical to forced oscillation. These critical areas/zones can be further considered as effective actuator locations for the deployment of forced oscillation damping controllers. Additionally, active power modulation control through IBRs is also proposed to reduce the forced oscillation impact on the entire grid. The proposed methods are demonstrated through a case study on a synthetic Texas power system model. The simulation results demonstrate that the critical areas/zones of forced oscillation are related to the areas that highly participate in the natural oscillations and the proposed oscillation damping controller through IBRs can effectively reduce the forced oscillation impact in the entire system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Localized Cyber Threat Mitigation Approach For Wide Area Control of FACTS

We propose a localized oscillation amplitude monitoring (OAM) method for the mitigation of cyber threats directed at the wide area control (WAC) system used to coordinate control of Flexible AC Transmission Systems (FACTS) for power oscillation damping (POD) of active power flow on inter-area tie lines. The method involves monitoring the inter-area tie line active power oscillation amplitude over a sliding window. We use system instability - inferred from oscillation amplitudes growing instead of damping - as evidence of an indication of a malfunction in the WAC of FACTS, possibly indicative of a cyber attack. Monitoring the presence of such a growth allows us to determine whether any destabilizing behaviors appear after the WAC system engages to control the POD. If the WAC signal increases the oscillation amplitude over time, thereby diminishing the POD performance, the FACTS falls back to POD using local measurements. The proposed method does not require an expansive system-wide view of the network. We simulate replay, control integrity, and timing attacks for a test system and present results that demonstrate the performance of the OAM method for mitigation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Visualization of the Oscillatory Dynamics of an Island Power System

In this work, we discuss the design of visualizations for understanding the complex oscillatory dynamics of an island power system with renewable generation sources after the loss of a large oil power plant. As more renewable generation sources are added to power systems, the oscillatory dynamics will change, which requires new visualization techniques to determine causes and strategies to avoid unwanted behaviors in the future. Our approach integrates geographic views, time-series plots, and novel oscillatory-trajectory curves, providing unique insights into the interdependent oscillatory behaviors of multiple state variables and generators over time. By enabling multi-node and multivariate comparisons over time, users can qualitatively determine drivers of oscillations and differences in generator dynamics, which is not possible with other commonly used visualization techniques.

inverters↗

Visualization of the Oscillatory Dynamics of an Island Power System: Preprint

In this work, we discuss the design of visualizations for understanding the complex oscillatory dynamics of an island power system with renewable generation sources after the loss of a large oil power plant. As more renewable generation sources are added to power systems, the oscillatory dynamics will change, which requires new visualization techniques to determine causes and strategies to avoid unwanted behaviors in the future. Our approach integrates geographic views, time-series plots, and novel oscillatory-trajectory curves, providing unique insights into the interdependent oscillatory behaviors of multiple state variables and generators over time. By enabling multi-node and multivariate comparisons over time, users can qualitatively determine drivers of oscillations and differences in generator dynamics, which is not possible with other commonly used visualization techniques.

inverters↗

Data Center Power Systems: Architectures, Impact on Grid Reliability, Modeling Considerations, and Megawatt-Scale Hardware Testing [Slides]

This slide deck describes typical power systems of large datacenters along with reliability problems to bulk power systems from large-scale integration of datacenters. The slide deck covers the architecture of datacenter power systems, different power electronic converters used inside datacenters, their operation modes, and R&Dopportunities in maintaining grid stability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

System Modeling and Robust Stability Region Analysis for Multi-inverters Based on VSG

As the number of inverter-interfaced distributed generators (IIDGs) increases, the decrease in the inertia of the microgrid affects the stability of microgrid voltage and current. The virtual synchronous generator (VSG) control method simulates the output characteristics of the synchronous machine to improve the inertia and damping of the microgrid. However, low-frequency oscillations can occur in systems with multi-VSGs connected in parallel, primarily when operating in island mode. Therefore, this article develops the small-signal state-space model for multi-inverters based on VSG and analyses the robust stability region (RSR) of the control parameters. Firstly, an extensible small-signal state-space model is established and simplified in the dq axis, which is a necessary preprocessing for the subsequent stability analysis. Secondly, the guardian map method based on bialternate product operation is constructed, and the RSR is established through translation mapping and rotation mapping. Therefore, the solution of RSR is transformed into the problem of identifying the Hurwitz matrix. Finally, the simulations and experiments verify that the calculated region can ensure stable operation during startup and meet the requirement to suppress low-frequency oscillations. In conclusion, the method of solving RSR proposed in this paper provides a basis for selecting controller parameters in practical engineering.

24 POWER TRANSMISSION AND DISTRIBUTION↗