Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “load tap changer”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

22 records · Page 2

Tapless Voltage Regulating Transformer. Final Report

Voltage regulation is a common practice in power grid operation. The conventional voltage regulation methods have been facing ever increasing challenges as the penetration of renewable generations deepens in the grid. The intermittent nature of the renewable sources may result in sudden rise or drop of power generation, possibly breaking the generation-load balance. A lack of adequate voltage control not only affects the power quality but is detrimental to the system operation with the potential for large economic losses. Most conventional voltage regulation devices rely on mechanical tap changers to impose the regulation in a step-wise manner. Although sufficient for normal operations, the mechanical tap changers can be easily worn out in the challenging situations created by renewables. In this project, a novel technology called tapless voltage regulating transformer (TAREX) was proposed and investigated. It has the potential to excel at addressing the new voltage regulation challenges and replace the conventional regulating transformers. TAREX is based on the concept of the saturable-core reactor (SCR). The voltage of a TAREX can be smoothly and continuously regulated in a reasonable range by using a low rating power electronics based controller. It uses control of the transformer core magnetization to regulate the voltage on the windings, and thus eliminates the mechanical tap changer. This project is to prove the principle of TAREX, understand the voltage regulation mechanism, and preliminarily understand its impacts on the power systems through modeling, prototyping, and testing.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Flexible Transformers for Resilient and Adaptable Power Systems

This paper presents experience with grid ready flexible transformer unit, which is in service for two years without any difficulty. Transformer unit is capable of changing short circuit impedance on load and it is equipped with state-of-the-art monitoring system.

field validation↗

Advanced Solar and Load Forecasting Incorporating HD Sky Imaging (Phase III)

Due to rapidly changing sky conditions, the available solar irradiance for energy generation is subject to wide swings in amplitude. As the market penetration of solar energy continues to increase rapidly, these variations in solar power generation are beginning to have an impact on grid stability and increased wear on power switches. Solar power forecasting plays a critical role in operations for Independent System Operators (ISOs) and utilities. Accurate forecasts help maintain grid reliability, optimize generation from renewables, and reduce operating costs. Of particular interest to the ISOs and utilities are sudden changes in solar irradiance, termed “ramp events,” due to the movement of clouds. One significant impact of ramp events on the grid is additional ancillary service requirements necessary to manage such variability. Ramp events can also cause voltage fluctuations in the distribution grids and trigger actions of automated line equipment (e.g., tap changers), leading to additional maintenance costs. In high penetration solar regions, forecasts must be made for both transmission-connected and distribution-connected resources – either behind the meter or in front of it. Particularly for distributed solar energy resources, forecasting can be a challenge due to the lack of visibility of the energy resource. Brookhaven National Laboratory (BNL) has been working towards nowcasting Global Horizontal Irradiance (GHI) using low-cost technologies for several years now. The Solar NowCasting technology being developed by BNL is a 0 – 30 min solar “nowcasting” technology applicable to a scale covering both large generating facilities and residential, distributed solar installations that relies on a network of ground-based high-definition (HD) cameras and surface pyranometers. GHI forecasts are being produced for both regions using 8 ground-based HD cameras and at least 2 surface pyranometers. When stitched together, the camera images can be used to forecast the impact of clouds on available solar irradiance over a domain of ~50 km 2 . Phase I of the project was the engineering scale up conceptual design stage. Phase II was the initial field test and demonstration, in which the technology was scaled up by a factor of 20 times and successfully demonstrated in eastern Long Island. In Phase III, an additional forecasting network was added in upstate NY and both networks are currently being operated until at least a full year of data is gathered by the Albany network to allow for the collection of sufficient data to evaluate performance against the persistence and smart persistence models using the Solar Arbiter.

14 SOLAR ENERGY↗

Probabilistic Voltage Sensitivity based Preemptive Voltage Monitoring in Unbalanced Distribution Networks

With increasing penetration of renewable energy and active consumers, control and management of power distribution networks has become challenging. Renewable energy sources can cause random voltage fluctuations as their output power depends on weather conditions. Conventional voltage control schemes such as tap changers and capacitor banks lack the foresight required to quickly alleviate voltage violations. Thus, there is an urgent need for effective approaches for predicting and mitigating voltage violations as a result of random fluctuations in power injections. This work proposes a novel voltage monitoring approach based on low-complexity, data-driven probabilistic voltage sensitivity analysis. The usefulness of this work is not only in predicting voltage violations in unbalanced distribution grids, but also in opening up the door for optimal voltage control. Using system data and forecasts, the proposed approach predicts the distribution of system node voltages which is then used to to identify nodes that may violate the nominal operational limits with high probability. The method is tested on the IEEE 37 node distribution system considering integrated distributed solar energy sources. The method is validated against the classic load flow based method and offers over 95% accuracy in predicting voltage violations.

Abujubbeh, Mohammad↗