Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “high wind penetration”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Ionospheric projections of magnetospheric regions under low and high solar wind pressure conditions

The projection of magnetospheric regions into the dayside ionosphere as determined by particle precipitation characteristics was studied for dependence on solar wind parameters. It was found that the solar wind kinetic pressure p dramatically affected the map of magnetospheric projections. Under the constraint that p greater than or equal 4 nPa(yielding (p) = 5.9 nPa), the area of the cusp (magnetic latitude times magnetic local time extent) was 4.83 degree-hours; whereas under the constraint that p greater than or equal 2 nPa (yielding (p) = 1.5 nPa), the cusp area was only 1.01 degree-hours. The ionospheric footprint of the low-latitude boundary layer was similarly affected. Various possible correlations of p with other solar wind variables, including n, v, and absolute value of B(sub z), proved unable to account for the pressure effect. Because one criterion for identifying the cusp is high fluxes, the effect of nv was investigated with particular care, both in examples and statistically. Again, p itself had by far the most striking effect. Thus we concluded that some physical mechanism is needed to account for the pressure effect. One possibility is that increased direct solar wind plasma penetration of the magnetopause occurs under high-p conditions in the manner suggested by various proponents of impulsive penetration models. An alternative, which we find promising, is that, regardless of the original interplanetary magnetic field (IMF) strength, a high-p solar wind leads to a large compression factor for the magnetosheath field, which is the field actually in contact with the magnetosphere. From this latter viewpoint, the chief effect of high particle pressure is simply to enhance the effectiveness of the interaction of the IMF with the magnetosphere.

Newell, Patrick T.↗

Utility Perspective on Protection Challenges with High IBR Penetration [Slides]

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, this report looks broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the report summarizes on gathered data and internal experiences.

14 SOLAR ENERGY↗

Utility Perspective on Protection Challenges with High Penetration of IBRs

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report / presentation identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, this report looks broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the report summarizes on gathered data and internal experiences.

14 SOLAR ENERGY↗

Cooperative fault management for resilient integration of renewable energy

Cooperative fault management (CFM) is designed herein to control different types of renewable energy resources cooperatively during electrical faults. This paper studies systems with a high penetration of photovoltaic (PV) energy and wind energy. First, CFM leverages power converters of PV farms to boost the ride-through capability of nearby doubly-fed induction generators (DFIGs). By controlling PV farms’ output voltages to change smoothly during both fault initiation and fault clearance, the widely used crowbar in DFIGs is less likely to be activated. Crowbar activation adversely makes DFIGs lose controllability and absorb reactive power. The second contribution is the development of a software-defined CFM controller and a controller in-the-loop demonstration of the real-time performance of this optimization-based CFM. CFM capitalizes on distributed optimization formulation to enable flexibility, plug-and-play, and privacy-preserving. Computation time, however, is a major concern for optimization-based dynamics control. Here, real-time controller-in-the-loop simulation results show optimization-based CFM can output reference values around 60 ms and is quick enough for dynamic control.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Inertia Estimation Under High Penetration of Inverter-based Resources

Many types of renewable energy sources, especially solar and wind generation, are connected to the electric grid through power-electronic-based interfaces (inverters). These inverter-based resources (IBRs) are mechanically decoupled from the grid, which reduces system inertia and thus may compromise its stability and reliability. In this study, we examine the impact of high penetration of IBRs on the power grid’s inertia. To achieve this, we intentionally introduce disturbances into a simulation case study, such as a step load change, to observe and record the system’s frequency responses. This study offers a nuanced understanding of how the integration of IBRs affects grid stability, and it provides essential guidance for future grid management and resilience strategies.

Yadav, Ajay↗

High-Penetration Microgrids Providing Grid Stability Using Frequency Watt Control

The U.S. grid is rapidly transitioning towards utilizing inverter-based renewable energy resources such as solar, wind, and batteries, reducing the carbon emission footprint. Inverter-based microgrid control architectures remain a critical focus to address power system stability issues in future high penetration markets lacking spinning generation assets. Idaho National Laboratory (INL) is researching an active layered inverter based frequency-Watt control scheme that provides distribution level stability in high-penetration markets where grid inertia is lacking. Hardware in the loop case study was implemented using INL’s Microgrid Testbed to combat scalable frequency deviations ranging from 60 Hz down to 50 Hz initialized by a hydropower model implementing step loads using a 540-kW grid emulator. Our research findings demonstrate the importance of distribution level, inverter-based active frequency-Watt controls utilizing a battery energy storage system (BESS) to provide adequate frequency support at the point of common coupling without major power infrastructure upgrades.

14 SOLAR ENERGY↗

High Penetration Microgrids Providing Grid Stability Using Frequency-Watt Control Presentation

The U.S. grid is rapidly transitioning towards utilizing inverter-based renewable energy resources such as solar, wind, and batteries, reducing the carbon emission footprint.Inverter-based microgrid control architectures remain a critical focus to address power system stability issues in future high penetration markets lacking spinning generation assets. Idaho National Laboratory (INL) is researching an active layered inverter based frequency-Watt control scheme that provides distribution level stability in high-penetration markets where grid inertia is lacking. Hardware in the loop case study was implemented using INL’s Microgrid Testbed to combat scalable frequency deviations ranging from 60 Hz down to 50 Hz initialized by a hydropower model implementing step loads using a 540-kW grid emulator. Our research findings demonstrate the importance of distribution level, inverter-based active frequency-Watt controls utilizing a battery energy storage system (BESS) to provide adequate frequency support at the point of common coupling without major power infrastructure upgrades.

13 HYDRO ENERGY↗

Coherent interannual and decadal variations inthe atmosphere-ocean system

We investigate the source of poleward propagating atmospheric zonal wind anomalies, originating at the equator and penetrating to high latitudes in both hemispheres in conjunction with ENSO [Dickey et al.,1992], and report the discovery of similar variability on decadal and longer timescales. Since atmospheric dissipation times are generally on the order of a month or less, we examine the ocean as a 'memory' source for these globally coherent anomalies. This hypothesis is substantiated by the observation of complementaryoscillation in the sea surface temperature (SST) field; further, we detect a robust decadal variability (~1012 yrs)in both the SST and contemporaneous atmospheric angular momentum (AAM) series. Analyzing GISST SST data beginning in 1902, we confirm this decadal mode and find signatures of longer (multidecadal) SST variability centered in the equatorial and North Pacific.

coherent decadal meridional↗

Interaction of comets with the interplanetary medium

The interaction of solar radiation and the solar wind with a comet as it moves around the sun is discussed. The overall structure of the comet-solar wind interaction, which is believed to give rise to a tangential discontinuity surface excluding the solar wind from the cometary ionosphere, a collisionless bow shock serving to decelerate and divert the solar wind, and a weak outer shock, is considered. The variable nature of the interaction as the comet moves around the sun and as solar wind conditions vary is then examined. It is shown that the cometary neutrals play a dominant role in standing off the solar wind, particularly under quiet conditions, making the cometary ionosphere in general highly incompressible. Conditions are found under which cometary neutrals cannot penetrate the ionopause to interact with the solar wind, and the inner shock becomes a hybrid ion-neutral shock. Finally, consideration of the direct interaction of the solar wind and solar ultraviolet radiation with the cometary nucleus indicates that electrostatic charging of the surface is capable of causing transport and blow-off of cometary dust at large heliocentric distances.

Mendis, D. A.↗

Potential Availability of and Supply Curves for Low-Cost, Dispatch-Constrained Electricity

Among other changes, variable renewable energy (VRE) - primarily wind and solar photovoltaics - is achieving a growing share of total generation. High VRE penetrations may result in an increased level of curtailment and thus suppress the value of additional VRE. This VRE, that either would not be built due to price suppression or would be curtailed, can be considered a resource that we define as low-cost, dispatch-constrained electricity (LDE). LDE could be used for various applications which value low-cost electricity and can operate at reduced capacity factors. Examples include electrolytic hydrogen production and carbon capture. This report provides initial estimates of the quantity and availability of the potential LDE resource in the U.S. under scenarios with high VRE penetrations. It also provides supply curves that can be used in subsequent analysis of the opportunity to use the LDE. We modeled several scenarios using capacity expansion and production cost models for LDE prices ranging from $\$ $0/MWh to $\$ $30/MWh. These LDE prices, coupled with low renewable energy cost assumptions, resulted in VRE penetrations ranging from 48-66% in 2050. The resulting LDE supplies range from 100 - 300 TWh/yr at a price of $\$ $0/MWh to 3,500 - 4,200 TWh/yr at $\$ $30/MWh. Increasing LDE prices increases wind and photovoltaics deployment; however, other generation technology capacities do not decrease equivalently in our models. Thus, additional generation is available but the capacity of traditional dispatchable generation is only reduced slightly. The available LDE is concentrated in the central and southwest U.S. regions because of their high wind and solar resources.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimizing the physical design and layout of a resilient wind, solar, and storage hybrid power plant

We report as wind and solar technologies improve and their costs decrease, the share of power produced by these sources will increase. As the market penetration increases, these power sources will need to provide grid services, such as dispatchability, in addition to providing energy. One way to reduce variability, provide higher quality power to the grid, and address local grid stability issues is through colocating wind and solar power plants. In addition to operating reliably during normal operating conditions, in scenarios with high penetrations of renewable generation, it is important that these hybrid plants can withstand production disruptions and continue to supply power despite prolonged resource reduction, extreme weather events, or other disruptions. In this paper, we present a methodology to optimize a wind-solar-battery hybrid power plant down to the component level that is resilient against production disruptions and that can continually produce some minimum required power. We introduce the models and assumptions we used to simulate a hybrid power plant as well as the design variable parameterization and specific methods we used to optimize the plant. We demonstrate the performance of our method by comparing a plant optimized for different objectives, generation outage durations, minimum power requirements, and power purchase agreements. Although the plant design is sensitive to model parameters and various other assumptions, our results demonstrate some of the optimal designs that occur in different scenarios and what one should expect when designing a hybrid wind-solar-storage power plant.

14 SOLAR ENERGY↗

Hybrid Power Plant Bidding in Models of Future Electricity Systems

This paper proposes a stochastic model for hybrid power plants participation in day-ahead electricity markets, considering uncertainty in market prices and renewable generation. Additionally, it presents a methodology to incorporate this hybrid participation into existing production cost models (PCM), allowing the analysis and market design of future systems with high penetration of hybrids. These developments are illustrated using a wind-battery hybrid located in New York Independent System Operator (NYISO) footprint.

Kemp, Julie Mulvaney↗

Stochastic economic dispatch of wind power under uncertainty using clustering-based extreme scenarios

Operation of power systems with high penetrations of renewable energy sources requires tools for robust decision making under uncertainty. Stochastic economic dispatch and stochastic unit commitment are effective techniques for planning and operation under uncertainty, whose effectiveness depends on the cardinality and quality of the scenario set. Here, this article proposes a machine learning method using -means clustering for capturing relevant physical information from a large population of analog scenarios. Extreme scenario samples drawn from the clusters are used in a two-stage stochastic economic dispatch computation. The effectiveness of the proposed approach is assessed on a synthetic 200-bus system with a geographic footprint over Illinois, USA for four months from each season of WIND Toolkit data. The combination of -means clustering with importance sampling is shown to reduce the total operational cost by over 43% compared to sampling from populations based on heuristic clustering-based methods. Additionally, the variability in the mean cost is about 56% lower than the variability using Monte Carlo sampling. Moreover, the operational cost with the presented approach is shown to be close to the cost calculated based on a hindsight exact wind profile, signifying a highly accurate quantification of wind uncertainty by the presented -means clustering based sampling method.

17 WIND ENERGY↗

Modeling and Power-Hardware-in-the-Loop Validation of Synchronous Wind: An Inverterless Grid-Forming Wind Power Plant: Preprint

Grid-forming (GFM) control of Type-3 and Type-4 wind turbine generators has attracted substantial attention in power systems research; however, the limited over-current capability of power electronics converters continues to deteriorate the grid strength of the evolving power systems. Synchronous wind, also known as Type-5 wind turbine generator (WTG), offers a unique GFM solution to address grid integration and grid strength issues by keeping the grid largely synchronous at very high penetration levels of renewable generation. A Type-5 WTG interfaces to the electric grid via a synchronous generator (SG) driven by a variable-speed hydraulic torque converter; hence, the wind rotor operates in variable-speed mode for maximum power generation and the generator shaft remains synchronous to the grid. This paper developed and tested a high-fidelity model of Type-5 WTG under power-hardware-in-the-loop (PHIL) testing environment. The PHIL demonstration showed that a Type-5 WTGs inherently behaves as a GFM unit and can obtain similar performance in terms of power responses, wind rotor dynamics, and efficiency compared to Type-3 WTG in high wind conditions. The developed model also provides further insight on how Type-5 WTGs can benefit the smooth transition to power systems with high integration level of inverter-based resources.

grid strength↗

Coordinated Integration of Renewable Generation and Small Modular Reactors in Puerto Rico – an Initial Study

With a growing interest and awareness to support clean and sustainable sources of energy, several countries have ambitious plans to significantly increase the penetration of renewable energy in the grid. However, the sources of renewable energy, such as solar and wind, are highly intermittent and therefore can pose additional challenges to maintain reliable system operations; one such challenge being flexibility requirement. This paper addresses the concerns of increasing flexibility needs with high renewable penetration, and also study the coordinated integration of nuclear small modular reactor and inverter-based renewable generation sources in a system to achieve high levels of carbon-free and sustainable energy. In this paper, balancing reserve and short-term flexibility requirements were considered for the analysis purpose. Also, methodology was developed to calculate metrics for calculating short-term flexibility requirements in the time-scale of hours. Small modular reactors are considered as potential sources of generation flexibility to complement renewables.

Agrawal, Urmila↗

Solar wind and high energy particle effects in the middle atmosphere

The solar wind variability and high energy particle effects in the neutral middle atmosphere are not much known. These factors are important in the high latitude upper mesosphere, lower thermosphere energy budget. They influence temperature, composition (minor constituents of nitric oxide, ozone), circulation (wind system) and airflow. The vertical and latitudinal structures of such effects, mechanisms of downward penetration of energy and questions of energy abundance are largely to be solved. The most important recent finding seems to be the discovery of the role of highly relativistic electrons in the middle atmosphere at L = 3 - 8 (Baker et al., 1987). The solar wind and high energy particle flux variability appear to form a part of the chain of possible Sun-weather (climate) relationships. The importance of such studies in the nineties is emphasized by their role in big international programs STEP and IGBP - Global Change.

Lastovicka, Jan↗

The Mechanism Responsible for High Concentrations of Be-7 in the Near Space

In 1990 an unexpectedly high concentration of Be-7 was discovered on the LDEF satellite surface, facing in the RAM direction. The search for an explanation of this high concentration of Be-7 which is in thermal equilibrium in the upper atmosphere, led the researchers to the hypothesis of Be-7 transport by vertical turbulent fluxes from deeper layers in the Earth's atmosphere, where Be-7 is produced as a result of nuclear reactions between solar energetic protons (which penetrated there after a solar flare) and terrestrial atmosphere elements. The experiments carried out during 1995-1999 on 'Resource F1' and 'Cosmos' satellites not only confirmed the existence of high Be-7 concentrations at altitudes of about 200 km, but also permitted to establish correlation between the concentration of Be-7 in the upper atmosphere and flare activity on the Sun. More detailed analysis of the whole set of experimental data on Be-7 measurements at satellite altitudes showed, that the appearance of high Be-7 concentrations in the upper atmosphere of the Earth is a more complicated phenomenon. Two more mechanisms , explaining the observed effect can be indicated. Firstly, the observed concentrations could be associated with direct penetration of energetic Be-7 nuclei, originating in flares, into the terrestrial atmosphere. Calculations show, that in solar cosmic rays the flux of Be-7 nuclei should be maximum in comparison to the fluxes of other Beryllium isotopes. Secondly, the high concentration of Be-7 in the upper atmosphere of the Earth could be explained by solar wind penetration through the polar zones. Theoretical analysis of active processes including flares, occurring in the solar atmosphere, leads to the conclusion, that radioactive Beryllium is constantly present in the solar atmosphere, and, possibly, is the main isotope of solar Beryllium.

Panasyuk, M. I.↗

Intelligently Partitioned Phasor-EMT Hybrid Simulations of Large-Scale, High-IBR Power Systems

As the penetration level of power electronics-interfaced renewables such as photovoltaics (PV) and wind has surged in modern electric grids, new operational risks caused by the dynamics of those inverter-based resources (IBRs) are emerging in parallel. Lessons learned from various grid events include that the impact of IBRs on system-level grid stability will become prominent along with the increase of renewables and that the short-timescale dynamic impacts of IBRs on grid stability are not fully captured by current commercial dynamic simulation tools [1] [2]. For example, IBRs can be controlled to mitigate those destabilizing interactions, but conventional phasor-domain tools (e.g. PSS/E, PSLF) often cannot capture that; likewise, the existing electromagnetic transient (EMT) simulation tools (e.g. PSCAD, EMTP) can simulate detailed IBR controls, but for large power systems with many IBRs, slow simulation speeds severely impede the ability to study dynamic events [3] [4]. Massively paralleling simulations using high-performance computing (HPC) can help address this, especially now that cloud-based HPC capability is widely available, but today s EMT tools are not HPC-compatible, and parallelization of dynamic simulation solvers is not trivial because each region can dynamically affect the others. Thus, dynamic simulation of grids with very large numbers of IBRs potentially poses a barrier to the ongoing energy transition.

24 POWER TRANSMISSION AND DISTRIBUTION↗