Adaptive Protective Relay Settings – A Vision to the Future

Adaptive relaying utilizes the continuously changing status of the power system as the basis for online adjustment of the power system relay settings. Fundamentally they are protection schemes that adjust settings and/or logic of operations based on the prevailing conditions of the system. These adjustments can include, but are not limited to, the logging of data for post-mortem analysis, communication throughout the system, as well as changing relay parameters. Adaptive relaying considers the fact that the status of a power system can change. These include system configuration changes, load effect, cold load pickup, end-of-line protection, transformer protection, and automatic reclosing. In this research, the author focus on the need for a secure, selective, and reliable system for adaptive overcurrent protection in T&D and Distributed Energy Systems. Various types of adaptive methods are presented and explained along with some pros and cons of each.

Mukherjee, Srijib↗

Comparison of Sequence Component-Based Fault Detection and Relay Coordination Algorithms in Inverter-Based Networks

Protection of inverter-based microgrids using sequence component-based relaying schemes is a promising solution. These methods offer several advantages, including lower computational requirements, compatibility with commercial relay systems, and cost-effectiveness compared to communication-based approaches. This article investigate the performance of various sequence component based schemes with the objective of identifying the algorithms that provide the best fault detection and relay coordination, solely relying on local voltages and current at relay terminals. Positive, negative and zero sequence impedance, admittance and power detection algorithms were tested on modified IEEE 13 bus test network for various shunt faults (LG, LL, LLG, LLL). Hardware-in-the-loop validation was achieved using the Typhoon real-time simulator, interfacing with a SEL 751 relay. This research demonstrates that while several algorithms are capable of detecting faults with sufficient accuracy, only a few are effective in achieving proper coordination. Validation results indicate that the negative sequence power approach provides the best performance in both fault detection and coordination.

Patel, Deepika [ORNL] (ORCID:0000000341099994)↗

Random Forest Regressor-Based Approach for Detecting Fault Location and Duration in Power Systems

Power system failures or outages due to short-circuits or “faults” can result in long service interruptions leading to significant socio-economic consequences. It is critical for electrical utilities to quickly ascertain fault characteristics, including location, type, and duration, to reduce the service time of an outage. Existing fault detection mechanisms (relays and digital fault recorders) are slow to communicate the fault characteristics upstream to the substations and control centers for action to be taken quickly. Fortunately, due to availability of high-resolution phasor measurement units (PMUs), more event-driven solutions can be captured in real time. In this paper, we propose a data-driven approach for determining fault characteristics using samples of fault trajectories. A random forest regressor (RFR)-based model is used to detect real-time fault location and its duration simultaneously. This model is based on combining multiple uncorrelated trees with state-of-the-art boosting and aggregating techniques in order to obtain robust generalizations and greater accuracy without overfitting or underfitting. Four cases were studied to evaluate the performance of RFR: 1. Detecting fault location (case 1), 2. Predicting fault duration (case 2), 3. Handling missing data (case 3), and 4. Identifying fault location and length in a real-time streaming environment (case 4). A comparative analysis was conducted between the RFR algorithm and state-of-the-art models, including deep neural network, Hoeffding tree, neural network, support vector machine, decision tree, naive Bayesian, and K-nearest neighborhood. Experiments revealed that RFR consistently outperformed the other models in detection accuracy, prediction error, and processing time.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Novel Protection Scheme for Unbalanced Faults in Inverter Dominated Networks: A Computationally Efficient Algorithm for Entry-Level Relays

Microgrids are now a common practice in distribution systems to increase resilience and reliability. However, microgrid protection remains a critical challenge, considering its requirement to operate in both grid connected and islanded, and the variability in fault characteristics under each mode of operation. This paper presents unbalanced power (S unb ) based fault detection algorithm, which considers local voltage and current unbalances to determine faults in the system. S unb is a computationally efficient fault detection algorithm that is suitable for implementation in the programmable logic of entry level protective relays. In addition, the difference in current and voltage unbalance (D n ) is used to determine the fault type. The proposed method demonstrates high sensitivity and selectivity for line-to-ground (LG), line-to-line (LL), and double line-to-ground (LLG) faults, representing the most common faults in distribution systems. It also allows relay coordination with upstream and downstream protection devices in both island and grid connected operation, while preserving grading margins. The same pickup and time multiplier settings of a particular relay for both modes of operation eliminates the need for adaptive settings, which rely on communication networks. Validation was performed with a hardware-in-the-loop (HIL) setup using Typhoon HIL real time simulator interfaced with three entry-level, SEL 751 relays. Results confirmed the algorithm’s ability to discriminate fault conditions, and determine the fault type under both operating modes, maintain fast detection times, and ensure proper protection coordination.

fault classification↗

Real-Time Testbed for Transmission Line Protection

Hardware in the loop (HIL) testing is crucial for designing and managing electric power grids. These grids are becoming larger and more complex. The importance for students to have safe and intuitive ways to interact with the devices associated with the power grids has never been more crucial. Since most of these tests involve high voltages, this can be a deterrent for instructors and students in undergraduate programs. HIL testing is a solution to these common issues. This method has become one of the most popular methods for testing these power systems. With the use of Western Michigan University’s (WMU) Real-Time Digital Simulator (RTDS) and SEL-421-7 protection relay, a HIL testbed has been created. These devices were interconnected using the communication protocol known as Generic Object-Oriented Substation Event (GOOSE). A simulated transmission line system was modeled in an RTDS software RSCAD as the basis for this testbed. This model simulated different types of faults that could occur in a transmission line while in operation. The SEL-421-7 relay is connected to the RSCAD simulation via GOOSE to protect our simulated transmission line. This testbed was set up to give students a clear understanding of how distance protection works as well as how the SEL-421-7 will react to various kinds of faults, in addition to how useful the RTDS can be when testing different power systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Electrogenetic signaling and information propagation for controlling microbial consortia via programmed lysis

To probe signal propagation and genetic actuation in microbial consortia, we have coopted the components of both redox and quorum sensing (QS) signaling into a communication network for guiding composition by “programming” cell lysis. Here, in this paper, we use an electrode to generate hydrogen peroxide as a redox cue that determines consortia composition. The oxidative stress regulon of Escherichia coli, OxyR, is employed to receive and transform this signal into a QS signal that coordinates the lysis of a subpopulation of cells. We examine a suite of information transfer modalities including “monoculture” and “transmitter-receiver” models, as well as a series of genetic circuits that introduce time-delays for altering information relay, thereby expanding design space. A simple mathematical model aids in developing communication schemes that accommodate the transient nature of redox signals and the “collective” attributes of QS signals. We suggest this platform methodology will be useful in understanding and controlling synthetic microbial consortia for a variety of applications, including biomanufacturing and biocontainment.

59 BASIC BIOLOGICAL SCIENCES↗

Dynamic Interference Management for UAV-Assisted Wireless Networks

Here, we investigate a transmission mechanism aiming to improve the data rate between a base station (BS) and a user equipment (UE) through deploying multiple relaying UAVs. We consider the effect of interference incurred by another established communication network, which makes our problem challenging and different from the state of the art. We aim to design the 3D trajectories and power allocation for the UAVs to maximize the data flow of the network while keeping the interference on the existing communication network below a threshold. We utilize the mobility feature of the UAVs to evade the (un)-intended interference caused by (un)-intentional interferers. To this end, we propose an alternating-maximization approach to jointly obtain the 3D trajectories and the UAVs transmission powers. We handle the 3D trajectory design by resorting to spectral graph the power allocation through convex optimization techniques. We also approach the problem from the intentional interferer’s perspective where smart jammers chase the UAVs to effectively degrade the data flow of the network. We also extend our work to the case for multiple UEs. Finally, we demonstrate the efficacy of our proposed method through extensive simulations.

42 ENGINEERING↗

Outage Analysis for Cooperative mmWave UAV Communications With Beam Training Overhead

In this letter, we investigate the tradeoff between reliability and beam training overhead in cooperative millimeter wave (mmWave) unmanned aerial vehicle (UAV) communications. In particular, we analyze how outage probability varies with the number of neighboring UAVs being probed as potential relays for relay selection. Unlike existing work, the limited number of UAV beams as well as UAV orientations are explicitly considered in our analysis. Here we derive the outage probability in closed form and verify our analysis via simulations. The results facilitate us to understand the fundamental limits of cooperative mmWave UAV communications.

99 GENERAL AND MISCELLANEOUS↗

Remote Entanglement via Adiabatic Passage Using a Tunably Dissipative Quantum Communication System

Effective quantum communication between remote quantum nodes requires high fidelity quantum state transfer and remote entanglement generation. Recent experiments have demonstrated that microwave photons, as well as phonons, can be used to couple superconducting qubits, with a fidelity limited primarily by loss in the communication channel. Adiabatic protocols can overcome channel loss by transferring quantum states without populating the lossy communication channel. In this work, we present a unique superconducting quantum communication system, comprising two superconducting qubits connected by a 0.73 m-long communication channel. Significantly, we can introduce large tunable loss to the channel, allowing exploration of different entanglement protocols in the presence of dissipation. When set for minimum loss in the channel, we demonstrate an adiabatic quantum state transfer protocol that achieves 99% transfer efficiency as well as the deterministic generation of entangled Bell states with a fidelity of 96%, all without populating the intervening communication channel, and competitive with a qubit-resonant mode-qubit relay method. We also explore the performance of the adiabatic protocol in the presence of significant channel loss, and show that the adiabatic protocol protects against loss in the channel, achieving higher state transfer and entanglement fidelities than the relay method.

71 CLASSICAL AND QUANTUM MECHANICS, GENERAL PHYSIC↗

Protection of Distribution Circuits with High Penetration of Solar PV: Distance, Learning, and Estimation-Based Methods

The results of DOE Solar Energy Technologies Office project 34233 are presented. The newest version of IEEE Standard 1547 enables photovoltaic inverters to ride through voltage disturbances, improving bulk system reliability, at the expense of removing undervoltage trip as a fast method of de facto fault detection in high PV adoption scenarios. The project explored new methods of fault detection that don't rely on communication systems and could be available quickly, including distance-based schemes, focused directional relays, and two different data-driven schemes. The schemes were evaluated with fast-phasor simulation, electromagnetic transient simulation, and field data collection at partner utilities Chattanooga Electric Power Board and Dominion Energy Virginia. Accomplishments and possible paths forward are summarized.

14 SOLAR ENERGY↗

Fermilab PIP-II CDS & CM Cryogenic Controls System

Details on Final design for Cryogenic Electrical & Controls System for Fermilab' s next-gen particle accelerator PIP-II. Electrical Controls System includes instrumentation and controls of Cryogenics Distribution System and Cryomodules. Design includes Siemens PCS7 Controls System with 26 Remote IO Rittal Cabinets and 48 Relay Racks for Temperature Readouts, Valve Positioners, Level, Heater Controls etc. Electrical Drawings and Design have been completed with focus now on fabrication of the 26 Rittal Cabinets and 48 Relay Racks. All materials have been procured. EPICS will be used as a SCADA system communicating to S7 Controllers via OPC UA.

Patel, Pratik [Fermilab]↗

Fermilab PIP-II CDS and CM Cryogenic Controls System

Details on Final design for Cryogenic Electrical & Controls System for Fermilab' s next-gen particle accelerator PIP-II. Electrical Controls System includes instrumentation and controls of Cryogenics Distribution System and Cryomodules. Design includes Siemens PCS7 Controls System with 26 Remote IO Rittal Cabinets and 48 Relay Racks for Temperature Readouts, Valve Positioners, Level, Heater Controls etc. Electrical Drawings and Design have been completed with focus now on fabrication of the 26 Rittal Cabinets and 48 Relay Racks. All materials have been procured. EPICS will be used as a SCADA system communicating to S7 Controllers via OPC UA.

Patel, Pratik [Fermilab]↗

Innovation in Radiological Security, Part 2 of 2 – Insights into Developing a Cloud-hosted Security Technology

A Sentry Remote Monitoring System (Sentry-RMS) is a stand-alone security system that provides detection, assessment, and communication of priority alarms as an additional means of thwarting internal and external threats to sites that maintain radiological material. The SEntry-RMS CommUnications and REsponse (Sentry-SECURE) platform is an optional feature of the Sentry-RMS that relays priority alarm information to the identified response stakeholders. Sentry-SECURE is hosted in a cloud environment that abstracts the data owner’s and data consumer’s platforms to allow for greater information sharing. This promotes situational awareness amongst authorized users and enables future innovation among modern response platforms. When securely architecting a cloud solution such as this, the use of design paradigms can be an effective tool to increase the accuracy and reliability of cyber- and information-security-related decisions made throughout the development process. This approach also supports the categorization of design considerations into three levels: industry concepts, project approaches, and data protections for digital processes. Industry concepts consist of the notional underpinnings that guide or motivate a security process, system, or design but often lack any tangible attributes. Project approaches represent decisions made during the design and development process to prioritize a solution, method, or practice above another that may provide a comparable functional output but lacks a desired security benefit. Data protections for digital processes represent the selection, integration, and implementation of specific controls for a given asset. This paper will explore specific examples of how Sentry-SECURE has been designed to account for considerations at each of these three levels, while balancing the operational intent of the platform with the security enhancements necessary to maintain data integrity, availability, and confidentiality.

assessment, RMS, security, physical, cloud, Cyber ↗

Effect of GPS Manipulation to Traditional and Next Generation Relay Protection

This project’s objective is to test the effect of GPS timing variations on relay protection algorithms to determine vulnerabilities and the associated hazards to the electric grid. This will focus on differential protection which utilizes peer to peer communication between substations to determine if the current is not equivalent. This requires the use of GPS to sync the two substations and can be vulnerable to GPS manipulation. However, the effects of GPS manipulation are not a commonly known risk. Therefore, this LDRD will address the risks of GPS manipulation for such a widely implemented technology. For differential protection a GPS resilient architecture was implemented and tested for differential protective relays through a direct serial fiber connection between the two relays. This allows for one relay to be the master and provide synchronization outside of timestamp for differential protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimizing Non-Terrestrial Hybrid RF/FSO Links With Reinforcement Learning: Navigating Through Clouds

In the pursuit of ubiquitous broadband connectivity, there has been a significant shift towards the vertical expansion of communication networks into space, particularly through the exploitation of low Earth orbit (LEO) satellite constellations, which are favored for their relatively low latency. However, this approach faces many challenges that need to be addressed, including atmospheric turbulence, high path loss, and dynamic cloud formations. High-altitude pseudo-satellites (HAPS) have emerged as promising relaying layers between LEO satellites and ground stations, enhancing coverage, latency, and direct terrestrial user connectivity. While radio frequency (RF) bands suffer from congestion and limited bandwidth, free space optical (FSO) communications offer higher data rates, but are susceptible to misalignment and weather-induced signal degradation. To address these challenges, a hybrid RF/FSO approach has been proposed to take advantage of both technologies by dynamic switching between RF and FSO based on propagation channel conditions. This paper introduces a reinforcement learning-based algorithm designed to optimize the trajectory of HAPS, maneuver around cloudy areas, and seamlessly switch between the RF and FSO communication modes to maximize the achievable capacity. The proposed approach aims to maximize system performance by intelligently adapting to environmental conditions and offering a promising solution for next-generation space communication networks.

actor-critic algorithm↗

Reconfigurable Real-Time Power Grid Emulator for Systems With High Penetration of Renewables

Novel power system control and new utility devices need to be tested before their actual deployment to the power grid. To assist with such a testing need, real-time digital emulators such as RTDS and Opal-RT can be used to connect to the physical world and form a hardware in the loop (HIL) emulation. However, due to the limitations of today's computational resources, the accuracy and fidelity suffer from different levels of model reductions in purely digital simulations. CURENT has developed a reconfigurable electric grid hardware testbed (HTB) to overcome the limitations of digital emulators. The HTB has been used to develop measurement, control, modeling, and actuation techniques for a national grid with a high penetration of renewables. The power electronic-based system includes emulators for synchronous generators; photovoltaics with grid-interfacing inverter; wind turbines; induction motor loads, ZIP loads, power electronic loads; batteries; ac and dc transmission lines; short circuit faults and grid relay protection; and a multiterminal HVDC overlay including power electronics interfaces. The system contains real elements of power flow, measurement, communication, protection, and control that mimic what would be seen in an actual electric grid. This paper presents an overview of the HTB and several scenarios that have been run to determine control and actions needed for the future power grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Theoretical foundations of waste factor and waste figure with applications to fixed wireless access and relay systems

The growing energy demands of next-generation wireless systems call for unified, system-level metrics to evaluate and optimize energy efficiency. This paper advances the concept of the Waste Factor (W), or Waste Figure (WF) in decibel scale, as a general framework for modeling power loss across cascaded communication components. By integrating W into the Consumption Factor (CF)–the ratio of data rate to consumed power–we reveal how component inefficiencies influence the minimum achievable energy per bit. Closed-form expressions are derived for energy-per-bit consumption in both direct and relay-assisted links, along with a decision rule for selecting the more energy-efficient path. While not explicitly modeled, Reflective Intelligent Surfaces (RIS) are shown to fit naturally within this framework. The analysis is further applied to a Fixed Wireless Access (FWA) scenario, where asymmetries in traffic direction and hardware inefficiencies are jointly considered, demonstrating the utility of the Waste Factor in guiding energy-aware system design.

Sevim, Nurullah [Texas A&M University, College Sta↗

Assessment of the Electrical Substation-Grid Testbed with Inside/Outside Devices and Distributed Ledger Technology

The electrical substation-grid testbed was created to integrate the GOOSE and/or DNP (Distributed Network Protocol) messages with time synchronized sources and Distributed Ledger Technology (DLT). The objective was to study the impact of faults and cyber-events at an electrical substation with inside (protective relays) and outside (power meters) substation devices. The electrical substation-grid testbed was based on the design of a 34.5/ 12.47 kV electrical substation (sectionalized bus configuration) with two power transformers, connected to radial power lines and load feeders. The electrical substation-grid testbed was installed at 252 lab space (Advanced Power System Protection), Grid Research Integration and Deployment Center (GRID-C), Oak Ridge National Laboratory. This testbed was created for Task 5, DarkNet project. The electrical substation-grid testbed was created to simulate fault and/or cyber events that could potentially result in damage to the electrical infrastructure. In addition, tests were run that are usually not allowed to be performed in an operational electrical power grid, because these test scenarios could trip breakers and/or generate fault situations that could potentially damage equipment. The number of tests performed in the electrical substation-grid testbed were executed in a better way than in a real electrical substation and/or power grid, because multiple tests could be run in a short period of time, and complex permits, and safety/ schedule restrictions like in a real electrical substation environment were not needed. The electrical substation-grid testbed was created using real measurement, communication, and protection devices that are used by electrical utilities, to have same conditions that we could observe in a real power grid or electrical substation. The electrical substation-grid testbed was based on using a real time simulator and expansion box with amplifiers that were wired to electrical substation-grid devices. This hardware-in-the-loop (HIL) was provided by protective relays, power meters, ethernet switches, remote terminal units, synchronized timing network clock, DLT devices, workstations, and servers. This report includes the design, installation, and assessment of the electrical substation-grid testbed that was similar to an operational electrical substation, integrating the power system protection, communication, and control systems. The results for the electrical substation-grid testbed were based on:• verifying the analog signals for protective relays and power meters, • observing the synchronized time source frame at devices, • authenticating the GOOSE (IEC 61850) and DNP messages from power meters and protective relays, and • verifying the trip conditions of protective relays at fault tests with the power system fault event detection, using DLT devices. For future work, the electrical substation-grid testbed with protective relays and power meters, using DLT and synchronized time source from DarkNet, will be used to study the impact of cyber-events at inside and outside substation devices. Advanced algorithms for detecting cyber-events produced by non-desired protective relay settings will be studied, to improve the detection and reliability of protection, control, and communication systems at power grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗