Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “circuit breakers”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Logic-controlled solid state switchgear for 270 volts dc

A feasibility study to design and demonstrate solid state switchgear in the form of circuit breakers and a power transfer switch is described. The switchgear operates on a nominal 270 V dc circuit and controls power to a load of up to 15 amperes. One circuit breaker may be interconnected to a second breaker to form a power transfer switch. On-off and transfer functions of the breakers or the transfer switch are remotely controlled. A number of reclosures with variable time delay between tripout and reclosure are programmed and controlled by integrated analog and COSMOS logic circuits. A unique commutation circuit, that generates only minimal transient disturbance to either source or load, was developed to interrupt current flow through the main SCR switching element. Laboratory tests demonstrated performance of the solid state circuit breakers over specified voltage and temperature ranges.

Sundberg, G. R.↗

Integral Battery Power Limiting Circuit for Intrinsically Safe Applications

A circuit topology has been designed to guarantee the output of intrinsically safe power for the operation of electrical devices in a hazardous environment. This design uses a MOSFET (metal oxide semiconductor field-effect transistor) as a switch to connect and disconnect power to a load. A test current is provided through a separate path to the load for monitoring by a comparator against a preset threshold level. The circuit is configured so that the test current will detect a fault in the load and open the switch before the main current can respond. The main current passes through the switch and then an inductor. When a fault occurs in the load, the current through the inductor cannot change immediately, but the voltage drops immediately to safe levels. The comparator detects this drop and opens the switch before the current in the inductor has a chance to respond. This circuit protects both the current and voltage from exceeding safe levels. Typically, this type of protection is accomplished by a fuse or a circuit breaker, but in order for a fuse or a circuit breaker to blow or trip, the current must exceed the safe levels momentarily, which may be just enough time to ignite anything in a hazardous environment. To prevent this from happening, a fuse is typically current-limited by the addition of the resistor to keep the current within safe levels while the fuse reacts. The use of a resistor is acceptable for non-battery applications where the wasted energy and voltage drop across the resistor can be tolerated. The use of the switch and inductor minimizes the wasted energy. For example, a circuit runs from a 3.6-V battery that must be current-limited to 200 mA. If the circuit normally draws 10 mA, then an 18-ohm resistor would drop 180 mV during normal operation, while a typical switch (0.02 ohm) and inductor (0.97 ohm) would only drop 9.9 mV. From a power standpoint, the current-limiting resistor protection circuit wastes about 18 times more power than the switch and the inductor configuration. In the fault condition, both the resistor and the inductor react immediately. The resistor reacts by allowing more current to flow and dropping the voltage. Initially, the inductor reacts by dropping the voltage, and then by not allowing the current to change. When the comparator detects the drop in voltage, it opens the switch, thus preventing any further current flow. The inductor alone is not sufficient protection, because after the voltage drop has settled, the inductor would then allow the current to change, in this example, the current would be 3.7 A. In the fault condition, the resistor is flowing 200 mA until the fuse blows (anywhere from 1 ms to 100 s), while the switch and inductor combination is flowing about 2 A test current while monitoring for the fault to be corrected. Finally, as an additional safety feature, the circuit can be configured to hold the switch opened until both the load and source are disconnected.

Burns, Bradley M.↗

Architecture, Voltage, and Components for a Turboelectric Distributed Propulsion Electric Grid (AVC-TeDP)

The purpose of this effort was to advance the selection, characterization, and modeling of a propulsion electric grid for a Turboelectric Distributed Propulsion (TeDP) system for transport aircraft. The TeDP aircraft would constitute a miniature electric grid with 50 MW or more of total power, two or more generators, redundant transmission lines, and multiple electric motors driving propulsion fans. The study proposed power system architectures, investigated electromechanical and solid state circuit breakers, estimated the impact of the system voltage on system mass, and recommended DC bus voltage range. The study assumed an all cryogenic power system. Detailed assumptions within the study include hybrid circuit breakers, a two cryogen system, and supercritical cyrogens. A dynamic model was developed to investigate control and parameter selection.

power↗

Solid state power controllers

The rationale, analysis, design, breadboarding and testing of the incremental functional requirements are reported that led to the development of prototype 1 and 5 Amp dc and 1 Amp ac solid state power controllers (SSPC's). The SSPC's are to be considered for use as a replacement of electro-mechanical relays and circuit breakers in future spacecraft and aircraft. They satisfy the combined function of both the relay and circuit breaker and can be remotely controlled by small signals, typically 10 mA, 5 to 28 Vdc. They have the advantage over conventional relay/circuit breaker systems in that they can be located near utilization equipment and the primary ac or dc bus. The low level control, trip indication and status signals can be circuited by small guage wire for control, computer interface, logic, electrical multiplexing, unboard testing, and power management and distribution purposes. This results in increased system versatility at appreciable weight saving and increased reliability.

Gibbs, R. S.↗

Logic-controlled solid-state switchgear for 270 volt dc.

A feasibility study to design and demonstrate solid-state switchgear composed of circuit breakers and a power transfer switch is described. The switchgear operates on a nominal 270 Vdc circuit and controls power to a load up to 15 A. One circuit breaker may be interconnected to a second to form a power transfer switch. Breaker or switch on-off and transfer functions can be remotely controlled. Automatic overload trip-out is provided through an ultimate current trip and an I squared t trip for transient overcurrents lower than the ultimate current trip level. A number of reclosures with variable time delay between trip-out and reclosure are programmed and controlled by integrated analog and COSMOS logic circuits. A commutation circuit that creates minimal transient disturbances to either source or load was developed to interrupt current flow through the main SCR switching element.-

Waddington, D.↗

Software Testbed for Developing and Evaluating Integrated Autonomous Subsystems

To implement fault tolerant autonomy in future space systems, it will be necessary to integrate planning, adaptive control, and state estimation subsystems. However, integrating these subsystems is difficult, time-consuming, and error-prone. This paper describes Intelliface/ADAPT, a software testbed that helps researchers develop and test alternative strategies for integrating planning, execution, and diagnosis subsystems more quickly and easily. The testbed's architecture, graphical data displays, and implementations of the integrated subsystems support easy plug and play of alternate components to support research and development in fault-tolerant control of autonomous vehicles and operations support systems. Intelliface/ADAPT controls NASA's Advanced Diagnostics and Prognostics Testbed (ADAPT), which comprises batteries, electrical loads (fans, pumps, and lights), relays, circuit breakers, invertors, and sensors. During plan execution, an experimentor can inject faults into the ADAPT testbed by tripping circuit breakers, changing fan speed settings, and closing valves to restrict fluid flow. The diagnostic subsystem, based on NASA's Hybrid Diagnosis Engine (HyDE), detects and isolates these faults to determine the new state of the plant, ADAPT. Intelliface/ADAPT then updates its model of the ADAPT system's resources and determines whether the current plan can be executed using the reduced resources. If not, the planning subsystem generates a new plan that reschedules tasks, reconfigures ADAPT, and reassigns the use of ADAPT resources as needed to work around the fault. The resource model, planning domain model, and planning goals are expressed using NASA's Action Notation Modeling Language (ANML). Parts of the ANML model are generated automatically, and other parts are constructed by hand using the Planning Model Integrated Development Environment, a visual Eclipse-based IDE that accelerates ANML model development. Because native ANML planners are currently under development and not yet sufficiently capable, the ANML model is translated into the New Domain Definition Language (NDDL) and sent to NASA's EUROPA planning system for plan generation. The adaptive controller executes the new plan, using augmented, hierarchical finite state machines to select and sequence actions based on the state of the ADAPT system. Real-time sensor data, commands, and plans are displayed in information-dense arrays of timelines and graphs that zoom and scroll in unison. A dynamic schematic display uses color to show the real-time fault state and utilization of the system components and resources. An execution manager coordinates the activities of the other subsystems. The subsystems are integrated using the Internet Communications Engine (ICE). an object-oriented toolkit for building distributed applications.

Testbed↗

Lockout/Tagout (LOTO) Simulator

The Lockout/Tagout (LOTO) Simulator is a portable training aid, or demonstration tool, designed to physically illustrate real-time critical-safety concepts of electrical lockout/tagout. The objective is to prevent misinterpretations of what is off and what is on during maintenance and repair of complex electrical systems. The simulator is designed in the form of a hinged box that opens up and stands on its own as an easel for demonstrations. On the outer face of the unit is a simulated circuit breaker box housing the switches. The breakers control the main power to the unit, a light bulb, and an electrical control cabinet. The light bulb is wired so that either of two breakers can provide power to it. When power is sent to the electrical control cabinet, a red indicator light illuminates. Inside the cabinet is the power supply from a personal computer. The power supply produces a 12-V dc output that is sent over to a small fan next to it, also from a computer, and an amber light on the front of the cabinet illuminates. A separate switch powers the fan on and off. The power supply is behind a plastic shield to protect against exposure to live conductors. Electrical banana jacks are mounted in the plastic shield to allow a voltmeter to be connected safely when opening the cabinet and taking a meter reading to verify de-energization as part of a simulation exercise. This LOTO simulator prototype is designed and fabricated as an all-in-one unit. All accessories can be stored inside the hinged case, and there is a handle on top for ease of transport. The circuit breaker labels attach with hook and loop fasteners so that they may be moved and changed to fit the training or demonstration scenario. The warning signs and labels on the electrical control box are magnetic, allowing for easy reconfiguration to emulate different equipment setups. A specially designed magnetic cover was made to disguise the indicator lights for demonstrations when these indicators are not used. The cover is disguised as an arc flash safety label that would typically be found on such a cabinet. One indicator light has a separate switch that can take it offline. This is to allow for demonstration to trainees on why it is important not to completely rely on indicator lights, but that they should always take a meter reading at the exposed conductors to absolutely verify de-energization before exposure. A clear plastic barrier and banana jacks inside the cabinet provide a safe way to plug in a voltmeter for demonstrations without exposure to the hazards of energized equipment. A small remote control unit is wired into the fan circuit. The remote allows the demonstrator to turn the fan on and off, provided that all of the breakers and switches leading to it are configured on as well. The remote feature was added in order to demonstrate the importance of starting the lockout/tagout task with energized equipment, then powering it down, isolating it, and locking it out to ensure that the correct breakers have been locked out.

Scheer, Jennifer↗

Power-Switching Circuit

Functions of circuit breakers, meters, and switches combined. Circuit that includes power field-effect transistors (PFET's) provides on/off switching, soft starting, current monitoring, current tripping, and protection against overcurrent for 30-Vdc power supply at normal load currents up to 2 A. Has no moving parts.

Praver, Gerald A.↗

Study of feasibility of solid-state electric switch gear for aircraft and spacecraft

The design of a solid-state circuit breaker that can be interconnected to a second breaker to form a transfer switch is presented. The breaker operates on a nominal 270-V dc circuit and controls power to loads of up to 15 A. Automatic overload trip is provided as a function of excess energy measured through the breaker and/or excess current through the breaker. After an overload trip, up to nine preprogrammable attempts to reclose may be tried with programmable delays between each attempt. The breaker or switch is remotely controllable. Test data on performance in the laboratory over temperatures from -45 to 100 C are provided. The feasibility of solid-state switch gear has been established.

Buchanan, E.↗

Voltages and currents induced by lightning

Indirect effects of lightning, the damage to or malfunction of electrical equipment that results from lightning flashes, were considered. These effects range from tripped circuit breakers to computer upset, to physical damage to input or output circuits of electronic equipment. Voltages and currents induced by lightning on the electrical wiring of the aircraft were emphasized regardless of whether or not such voltages and currents cause damage or upset of electrical equipment.

Franklin A Fisher↗

Designing a 25-kilowatt high frequency series resonant

The feasibility of processing 25 kW of power with a single, transistorized, 20 kHz, series resonant converter stage has been demonstrated by the successful design, development, fabrication, and testing of such a device. It employs four Westinghouse D7ST transistors in a full-bridge configuration and operates from a 250-to-350-Vdc input bus. The unit has an overall worst-case efficiency of 93.5% at its full rated output of 1000 V and 25 A dc. A solid-state dc input circuit breaker and output-transient-current limiters are included in and integrated into the design. Circuit details of the converter are presented along with test data.

Robson, R. R.↗

The 25 kW resonant dc/dc power converter

The feasibility of processing 25-kW of power with a single, transistorized, series resonant converter stage was demonstrated by the successful design, development, fabrication, and testing of such a device which employs four Westinghouse D7ST transistors in a full-bridge configuration and operates from a 250-to-350 Vdc input bus. The unit has an overall worst-case efficiency of 93.5% at its full rated output of 1000 V and 25 A dc. A solid-state dc input circuit breaker and output-transient-current limiters are included in and integrated into the design. Full circuit details of the converter are presented along with the test data.

Robson, R. R.↗

It's a Go

The Electrical Power Distribution Control Team takes on the task of determining power failures throughout the Orbiter. The Displays and Controls Team takes on the task of determining distribution, circuit breakers, and switch failures that might occur on the Orbiter or displays that stop working. This paper will identify the circuit packages I have put together for the D&C group, the redesigning of a Hybrid Driver Controller box, and the web designing the Displays and Controls website for easier access to information which can range from indicators to switches.

Welker, Joshua T.↗

Current-limiting voltage regulator

Voltage regulator, which operates within preset current limits, acts as a circuit breaker to prevent overload failure, and automatically resets when the overload is removed. The power dissipated in the series transistor of the circuit is constant from normal load to short circuit condition.

Cleveland, E. F.↗