Development and evaluation of a multi-functional heat pump with embedded thermal storage

We developed and tested a novel multi-functional packaged vertical heat pump designed for multi-family buildings, capable of providing space cooling, space heating, water heating, and energy storage integration. The system employs a 3-speed scroll compressor and supports energy-efficient cooling and heating across different ambient conditions, while utilizing both indoor and outdoor air sources for water heating. Key performance metrics include an integrated energy efficiency ratio of 18.0 for cooling, a heating seasonal performance factor of 10.0, and a coefficient of performance (COP) of 2.1 for heating in cold climates down to −15 ˚C. Additionally, the system delivers an annual water heating COP greater than 4.0, with outstanding performance in combined space cooling and water heating modes, achieving a total COP of 8.8 by recovering condenser waste heat. The heat pump also demonstrated thermal energy storage capabilities, integrating with phase change material systems to store heating and cooling energy. Furthermore, this versatile system offers a promising solution for improving energy efficiency and sustainability in multi-family buildings, providing high-performance heating, cooling, and water heating across a range of climates.

COP↗

Impacts of common faults on an air conditioner with a microtube condenser and analysis of fault characteristic features

Split system air conditioners are widely used to cool residential buildings, because of their low cost and simplicity. However, their efficiency is impacted by installation faults, which include: improper refrigerant charge (undercharge or overcharge), improper evaporator airflow, liquid line restrictions (LL), and the presence of non-condensable gas (NC) in the refrigerant. No known previously published research has studied the effect of these four faults on a system equipped with a microtube condenser, which has smaller tube size than a traditional condenser and therefore holds less refrigerant charge, but has a different configuration than a microchannel. Furthermore, very few have studied the impacts of LL and NC. Herein this paper describes laboratory fault tests of a microtube-equipped system, compares the fault impacts with those of a traditional system, and considers the characteristic fault features. The tested system uses R-410A refrigerant and has a scroll compressor, a fixed orifice expansion device, and two fin-tube heat exchangers. The tests were carried out under steady operation with a range of fault intensities and operating conditions. The microtube system’s performance degradation from faults is similar to systems with traditional heat exchangers, despite the reduced capacity to hold refrigerant charge.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Life cycle cost analysis comparing redesigned CCHP to existing heat pump systems for cities in cold climates

This report indicates that the project progress has met the Go criterion, i.e. demonstrating favorable results of life cycle cost assessment for the redesigned CCHPs. Considering the market price of a baseline heat pump, and required improvements in heat exchangers, fans and an electronic expansion valve of the CCHPs, we estimated that the CCHP using a 3-stage scroll compressor will incur with a cost increment of $\$386$ per rated cooling tonnage, and the CCHP using tandem compressors will increase by $\$770$. Based on the energy savings of the CCHPs, simulated by EnergyPlus, the two CCHPs achieve payback periods less than 4 years among all the cold climate cities. Within a typical heat pump life cycle of 20 years, the CCHPs can achieve cost savings around $\$2000$ per rated cooling tonnage, and the savings are even higher for the extremely cold cities like Duluth and Fairbanks.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Cost-Optimized CCHP Model Developed Using HPDM Meeting Performance Targets

This report documents the equipment design and analysis work to meet the first project milestone (M1). Our industry partner, Emerson Commercial & Residential Solutions recently developed a 3-stage scroll compressor product, able to deliver capacity at three levels without using an inverter. Based on ORNL’s previous cold climate heat pump (CCHP) prototype and the preliminary compressor performance data, the CCHP was redesigned for cost reduction and better performance. The 3-stage compressor, using the middle capacity level to deliver the rated capacity of the heat pump (HP), will replace the previous tandem compressors, using one single-speed compressor to deliver the rated capacity. In this way, it will reduce the compressor footprint to fit in most residential HPs’ chassis. The compressor replacement increases the nominal capacity by 17%. Approximately, 30% cost reduction in the compressor and 17% reduction in the heat exchangers per nominal tonnage can be achieved relative to the prior tandem compressor design. Advanced features using an electronic expansion valve for head pressure control and an Ebm-papst variable-speed, backward-curved indoor blower can be adopted for higher efficiency.The DOE/ORNL Heat Pump Design Model (HPDM) was used to model and redesign the CCHP. Following AHRI 210/240, heating and cooling performance results were predicted at the conditions for certifying a 2-stage CCHP, regarding various design scenarios. The predicted HSPF reaches 12.0, and predicted SEER reaches16.2.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Experimental Investigation on Heating Performance of a Cold Climate Thermoelectric-Assisted Heat Pump

To accelerate the electrification of air source heat pumps (ASHPs) in cold climates across the United States, various initiatives have been launched to enhance the effectiveness of ASHPs. One avenue of research involves incorporating thermoelectric (TE) technology into vapor compression refrigeration cycles. This study aims to assess the heating performance of a cold climate ASHP by employing TE modules as a liquid line subcooler. The tested system is a nominal 4.5-ton split heat pump utilizing R410A, equipped with a scroll compressor and an accumulator. An electronic expansion valve was employed for both cooling and heating modes. Two configurations of TE sub-coolers, one utilizing 2 TE bundles and the other 4 TE bundles, were integrated into the liquid line of the tested system. The heating performance of these configurations was evaluated. The results revealed that activating the TE subcooler led to a notable increase in total heat capacity, reaching 1318 W at -15.0 °C and 1164 W at -19.0 °C. The corresponding TE coefficients of performance (COPs) were 1.76 and 1.63, respectively. The activation of the TE sub-cooler resulted in a slight reduction in the overall system COP, with a decrease ranging from -2.6% to -4.2% for these two temperatures. The system COPs were measured at 2.10 and 1.86 for -15.0 °C and -19.0 °C, respectively. This prototype demonstrated a significant augmentation in heating capacity with a minimal sacrifice in COP.

Hu, Yifeng↗

Building Technologies Office 03.02.02.38 Milestone Report—Compressor Technology Development for Refrigerants with <150 Global Warming Potential

The major purpose of this project is to enable the development of compressors specifically designed for compatibility with low–global warming potential (GWP) refrigerants (with GWP values below 150). These compressors are intended for applications in residential and light commercial air-conditioning and heat pump systems. This report contains an exhaustive review of the existing literature with the intention of discerning the most efficacious methodologies currently in use for compressor modeling. This fundamental stage was designed to foster a comprehensive understanding of the intricate dynamics and mechanics of compressors. As a result, a model (PDSim) was selected to simulate scroll, rotary and linear compressor technologies.

42 ENGINEERING↗

PDRD Project 19039 - All metal vacuum scroll pump development for tritium

Currently the United States relies on a single source, foreign company, Eumeca (formerly Normetex) for the supply of an all metal vacuum scroll pump to process tritium. This “one of a kind”, all metal, vacuum scroll pump utilizes no “wetted”, polymeric materials that degrade prematurely when exposed to tritium. U.S. based vacuum scroll pump suppliers typically utilize a polymer, Teflon®, as a tip seal material at the edge of the scroll impellers for proper pump function. Teflon® is known to degrade within a relatively short time frame (approximately 1 year) when continually exposed to tritium gas. This degradation results in “flaking” of the Teflon® material which results in particulate contamination of the process gas stream. While filtration of the particulate is possible, doing so requires additional maintenance which is costly in a glovebox environment. In addition, filtration can degrade pumping system performance as particulate collects in the filter media over time. To date, all of the well established U.S and European based vacuum scroll pump manufacturers have been uninterested in developing an all metal vacuum scroll pump that does not use a polymeric scroll tip seal. This position is taken as the vacuum scroll pump manufacturers do not see a large enough market to make it profitable for them to develop and market an all metal vacuum scroll pump. In the mid 2000s, one company, Air Squared, Inc., a small Original Equipment Manufacturer (OEM) specializing in design and fabrication of custom scroll vacuum pumps and compressors, was willing to pursue the effort. The first design effort incorporated Vespel® as a polymeric tip seal material. Results of this effort led to realizing the affect that the Met-Bel MB-601 metal bellows pump has on performance when used as a backing pump for an all metal vacuum scroll pump without a scroll tip seal. As a result, Air Squared subsequently designed an all metal vacuum scroll pump without a tip seal material for evaluation. Although the initial, all metal version of the Air Squared pump was found deficient in regard to scroll impeller stiffness, which resulted in scroll contact, general design and pump performance was verified to be adequate. SRS PDRD Project 19039 was launched in 2019 as a 3rd attempt with Air Squared, Inc. in regard to development of an all metal vacuum scroll pump for consideration as an equivalent to the Eumeca/ Normetex pump. The effort specified 300 series stainless steel for the scroll impellers, all metal sealing, and design to meet tritium throughput and ultimate vacuum requirements. In addition, a 60 psig design pressure rating requirement was specified for the pump containment boundary. The 3rd generation Air Squared pump has been designed, fabricated, and has received preliminary testing. Preliminary testing has indicated proper leak tightness and pump performance. However, work continues regarding development of a pumping chamber containment bellows that can be subjected to 66 psig without damage to the bellows. Work will continue in 2020 and 2021 to pursue a pumping chamber containment bellows that meets the pressure rating requirement.

11 NUCLEAR FUEL CYCLE AND FUEL MATERIALS↗

Research, Development and Demonstration of Micro-CHP System for Residential Applications

ECR International and its joint venture company, Climate Energy, are at the forefront of the effort to deliver residential-scale combined heat and power (Micro-CHP) products to the USA market. Part of this substantial program is focused on the development of a new class of steam expanders that offers the potential for significantly lower costs for small-scale power generation technology. The heart of this technology is the scroll expander, a machine that has revolutionized the HVAC refrigerant compressor industry in the last 15 years. The liquid injected cogeneration (LIC) technology is at the core of the efforts described in this report, and remains an excellent option for low cost Micro-CHP systems. ECR has demonstrated in several prototype appliances that the concept for LIC can be made into a practical product. The continuing challenge is to identify economical scroll machine designs that will meet the performance and endurance requirements needed for a long life appliance application. This report describes the numerous advances made in this endeavor by ECR International. Several important advances are described in this report. Section 4 describes a marketing and economics study that integrates the technical performance of the LIC system with real-world climatic data and economic analysis to assess the practical impact that different factors have on the economic application of Micro-CHP in residential applications. Advances in the development of a working scroll steam expander are discussed in Section 5. A rigorous analytical assessment of the performance of scroll expanders, including the difficult to characterize impact of pocket to pocket flank leakage, is presented in Section 5.1. This is followed with an FEA study of the thermal and pressure induced deflections that would result from the normal operation of an advanced scroll expander. Section 6 describes the different scroll expanders and test fixtures developed during this effort. Another key technical challenge to the development of a long life LIC system is the development of a reliable and efficient steam generator. The steam generator and support equipment development is described in Section 7. Just one year ago, ECR International announced through its joint venture company, Climate Energy, that it was introducing to the USA market a new class of Micro-CHP product using the state-of-the-art Honda MCHP gas fired internal combustion (IC) engine platform. We now have installed Climate Energy Micro-CHP systems in 20 pilot demonstration sites for the 2005/2006 heating season. This breakthrough success with IC engine based systems paves the way for future advanced steam cycle Micro-CHP systems to be introduced.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Evaluation of Low Environmental Impact Distributed Scroll Booster Technology for Supermarket Refrigeration

A distributed scroll booster refrigeration system is proposed as an alternative for current refrigeration systems used in supermarket applications. The distributed scroll booster system is configured to enable the use of low-pressure refrigerants such as R-1234yf, which has a global warming potential (GWP) of less than 1, in a cycle configuration that employs a two-stage compression process. This scroll booster system is comprised of medium-temperature compressors (high stage) coupled with low-temperature compressors (low stage). This two-stage system architecture allows both low-temperature and medium-temperature refrigerated display cases to be integrated in the same system. By design, this system reduces the refrigerant charge, produces higher efficiencies (two-stage compression), uses existing components minimizing cost impact, and will be able to use ultra-low GWP class A2L (low toxicity and low flammability) refrigerants such as R-1234yf when standards and building codes are updated (expected by 2025).

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Energy Efficient Commercial Refrigeration with Carbon Dioxide Refrigerant and Scroll Expanders

Current supermarket refrigeration systems are built around conventional fluorocarbon refrigerants – HFC-134a and the HFC blends R-507 and R404A, which replaced the CFC refrigerants, R-12 and R-502, respectively, used prior to the Montreal Protocol phase out of ozone depleting substances. While the HFC refrigerants are non-ozone depleting, they are strong greenhouse gases, so there has been continued interest in replacing them, particularly in applications with above average refrigerant leakage. Large supermarket refrigeration systems have proven to be particularly difficult to maintain in a leak-tight condition. Refrigerant charge losses of 15% of total charge per year are the norm, making the global warming impact of refrigerant emissions comparable to that associated with the energy consumption of these systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗