Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “PMUs”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

GPS signal loss in the wide area monitoring system: Prevalence, impact, and solution

The phasor measurement unit (PMUs), equipped with Global Positioning System (GPS) receivers for precise time synchronization, provides measurements of voltage and current phasors at different nodes of the wide area monitoring system. However, GPS receivers are likely to lose satellite signals due to various unpredictable factors. The prevalence of GPS signal loss (GSL) on PMUs is first investigated using real PMU data. The historical GSL events are extracted from a phasor data concentrator (PDC) and FNET/GridEye server. The correlation between GSL and time, spatial location, solar activity are explored via comprehensive statistical analysis. Furthermore, the impact of GSL on phasor measurement accuracy has been studied via experiments. Finally, several potential solutions to mitigate the impact of GSL on PMUs are discussed and compared.

47 OTHER INSTRUMENTATION↗

Coherency-Based Detection Algorithm for Synchrophasor Cyberattacks

The wide area monitoring system (WAMS) is critical for power system situational awareness, but represents a growing cybersecurity vulnerability. Malicious adversaries may seek to compromise one or more PMUs in order to effect control decisions that unnecessarily disrupt typical grid operations. One example of a particularly pernicious attack vector is the spoofing or replaying of a fault event using one or more compromised PMUs. This work documents the development and validation of a coherency-based cyberattack detection algorithm that integrates a sliding-window singular value decomposition (SVD) with physics-based partitioning analysis to achieve accurate classification of events. Special consideration is given to discerning a sophisticated fault-replay or fault spoofing attack from actual faults. A software-based cybersecurity testbed has been developed for rigorous testing of the algorithm. The algorithm is further validated using simulated synchrophasor datasets obtained from a MinniWECC 63-bus test system. Results show that the algorithm can successfully detect fault-replay attacks even when over half of the PMUs are compromised.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Multi-Objective PMU Allocation for Resilient Power System Monitoring

Phasor measurement units (PMUs) enable better system monitoring and security enhancement in smart grids. In order to enhance power system resilience against outages and blackouts caused by extreme weather events or man-made attacks, it remains a major challenge to determine the optimal number and location of PMUs. In this paper, a multi-objective resilient PMU placement (MORPP) problem is formulated, and solved by a modified Teaching-Learning-Based optimization (MO-TLBO) algorithm. Three objectives are considered in the MORPP problem, minimizing the number of PMUs, maximizing the system observability, and minimizing the voltage stability index. The effectiveness of the proposed method is validated through testing on IEEE 14-bus, 30-bus, and 118-bus test systems. The advantage of the MO-TLBO-based MORPP is demonstrated through the comparison with other methods in the literature, in terms of iteration number, optimality and time of convergence.

Multi-Objective Optimization↗

Immunity Study: Port Impedance Measurement of PMU and PCI testing under EMP

With the increased requirements of real-time grid monitoring, disturbance location, and situation awareness, Phasor Measurement Units (PMUs) have become more critical for the Wide Area Measurement System (WAMS). However, the vulnerability of PMUs has not been well studied, especially under electromagnetic pulse (EMP) scenarios. The stable operation of the power system will be affected directly once EMP damages them. Therefore, studying their immunity to EMP events is urgent and necessary. In this paper, the effective impedance measurement scheme and pulsed current injection (PCI) testing are proposed for the port impedance measurement and immunity levels of PMUs. The equivalent non-uniform transmission line model is established to eliminate the impact of the fixture in the de-embedding process. Then, the circuit of the pulsed current generator is set to generate a damping sinusoid, and the double exponential wave is applied to the port. Finally, using measured impedance as a generator load, the voltage and current responses of different ports are calculated in the PCI testing simulation. In conclusion, results reveal the characteristics of port impedance, waveforms of voltage and current, and distribution of accumulative energy. The relation between port impedance and the waveforms is discussed.

42 ENGINEERING↗

Alignment Method for Synchronized Phase Angle Measurement With Presence of Practical Time Shift

Synchronized Phase Angle Measurements (SPAMs) are widely used in power systems in the applications of situational awareness. However, the practical time shifts can lead to unexpected angle differences among Phasor Measurement Units (PMUs) manufactured from various vendors. Moreover, since most of PMUs calculate phase angle via Discrete Fourier Transform based approaches, this issue becomes even worse under the off-nominal frequency condition. To mitigate the impact of practical timing shift, this letter presents a fast method to rectify the SPAM for appropriate alignment. To verify the performance of the proposed method, laboratory and field tests have been conducted by implementing the method in PMUs and phasor data concentrators, respectively. The results demonstrate that the standard deviations of the phase angle differences have significantly decreased to 0.1$^{\circ }$ order with the adoption of the proposed method.

42 ENGINEERING↗

Situational Awareness in Distribution Grid Using Micro-PMU Data: A Machine Learning Approach

The recent development of distribution-level phasor measurement units, a.k.a. micro-PMUs, has been an important step towards achieving situational awareness in power distribution networks. The challenge however is to transform the large amount of data that is generated by micro-PMUs to actionable information and then match the information to use cases with practical value to system operators. This open problem is addressed in this paper. First, we introduce a novel data-driven event detection technique to pick out valuable portion of data from extremely large raw micro-PMU data. Subsequently, a datadriven event classifier is developed to effectively classify power quality events. Importantly, we use field expert knowledge and utility records to conduct an extensive data-driven event labeling. Moreover, certain aspects from event detection analysis are adopted as additional features to be fed into the classifier model. In this regard, a multi-class support vector machine (multi-SVM) classifier is trained and tested over 15 days of real-world data from two micro-PMUs on a distribution feeder in Riverside, CA. In total, we analyze 1.2 billion measurement points, and 10,700 events. Here, the effectiveness of the developed event classifier is compared with prevalent multi-class classification methods, including k-nearest neighbor method as well as decision-tree method. Importantly, two real-world use-cases are presented for the proposed data analytics tools, including remote asset monitoring and distribution-level oscillation analysis.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Synchrophasor Based Tracking Three-Phase State Estimator and It's Applications

Electric power infrastructure is one of the critical resources of the nation. Its reliability in the face of natural or man-made catastrophes is of paramount importance for the economic and public health wellbeing of a modern society. Maintaining high levels of security for the high voltage transmission back bone of the electric supply network is a task requiring access to modern monitoring tools. These tools have been made particularly effective with the advent of synchronized phasor measurement units (PMUs) which became available in late 1990s, and have now become an indispensable for optimal monitoring, protection and control of the power grid. The present project was launched with an objective of demonstrating the value of the Wide Area Measurement System (WAMS) using PMUs and its applications on the Dominion Virginia Power High Voltage transmission grid. Virginia Tech is the birth place of PMUs, and was chosen to be the Principal Investigator of this project. In addition to Dominion Virginia Power, Quanta Technology of Raleigh, NC was selected to be co-Principal Investigators of this project.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Scoping Study on Research and Development Priorities for Distribution-System Phasor Measurement Units

This report addresses the potential use of phasor measurement units (PMUs) within electricity distribution systems, and was written to assess whether or not PMUs could provide significant benefit, at the national level. We analyze examples of present and emerging distribution-system issues related to reliability, integration of distributed energy resources, and the changing electrical characteristics of load. We find that PMUs offer important and irreplaceable advantages over present approaches. However, we also find that additional research and development for standards, testing and calibration, demonstration projects, and information sharing is needed to help industry capture these benefits.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Measurement Adequacy for Monitoring Data Center Oscillations

Artificial intelligence (AI) training data centers with periodic load profiles can induce sustained grid oscillations across a wide frequency range, making accurate monitoring essential for reliable power system operation. This report evaluates the adequacy of existing measurement systems for monitoring such oscillations, focusing on phasor measurement units (PMUs) and point-on-wave (POW) measurement systems. The analysis shows that while PMUs are highly effective for monitoring low-frequency electromechanical oscillations, they have inherent limitations in accurately representing higher-frequency oscillations due to constraints imposed by reporting rates and the bandwidth of phasor estimation filters. Even when configured with higher reporting rates, the filtering inherent in the phasor estimation process can significantly attenuate oscillation magnitudes, potentially leading to underestimation of oscillatory behavior. This has important implications for compliance and performance monitoring of large loads. To address the limitations associated with PMU-based monitoring, the report examines the use of high-resolution POW measurements, which can capture oscillations across a broader frequency range. However, continuous POW monitoring introduces practical challenges related to large data volumes, communication bandwidth, and real-time data processing. For this reason, the report also discusses emerging approaches that use POW measurements as a complementary capability alongside PMUs to improve observability of oscillations from large data center loads.

47 OTHER INSTRUMENTATION↗

Feature-Based PMU Event Classification under Variable PMU Participation and Overlapping Events

Danovo Energy Solution's presented its paper named: Feature-Based PMU Event Classification under Variable PMU Participation and Overlapping Events at the 2026 Georgia Tech Fault & Disturbance Analysis Conference. The full paper can be found at OSTI ID# 3169150 Paper Abstract—Phasor Measurement Units (PMUs) stream time synchronized, high-resolution measurements from the grid, enabling data-driven techniques for event detection and classification. Accurate event classification improves grid reliability and stability. Events can be detected by varying numbers of PMUs and exhibit different durations depending on the event type. This variability challenges standard classifiers that require uniform input sizes. Moreover, multiple events may coincide, which increases classification complexity. Standard classifiers assign each instance to the class with the highest predicted probability, whereas overlapping events may exhibit comparable probabilities across multiple classes. In this study, to handle data size variability, we extract a wide range of time–frequency domain features from all available PMUs for each event into a fixed-length vector, facilitating the application of standard machine learning classifiers, including Random Forest, XGBoost, LightGBM, Support Vector Machine, and Multilayer Perceptron. To account for overlapping events, a probabilistic post-processing step is applied. For a given data instance, if multiple predicted class probabilities exceed 30% and the differences between them are less than 10%, the event is assigned to multiple classes. Experiments using real-world PMU data demonstrate that the Random Forest and XGBoost models achieve the highest accuracy, while the proposed post-processing method yields perfect classification performance on external unseen test sets.

Nematirad, Reza [Danova Energy Solutions]↗

Pattern Mining and Anomaly Detection based on the Power System Synchrophasor Measurements

Real-time monitoring of power system dynamics using phasor measurement units (PMUs) data improves situational awareness and system reliability and potentially can help prevent blackouts due to early anomaly detection. The study presented in the paper is based on the actual PMU measurements of the U.S. western interconnection system. Given the nonlinear and nonstationary PMUs data, we developed a robust anomaly detection framework. Wavelet-based multi-resolution analysis, combined with moving-window-based outlier detection and anomaly scoring, were deployed to identify potential PMU events. The candidate events were evaluated using spatiotemporal correlation analysis, and then classified for a better understanding of the event types. The results demonstrated successful anomaly detection and classification, compared with the recorded real-world events.

Ren, Huiying↗

Line Faults Classification Using Machine Learning on Three Phase Voltages Extracted from Large Dataset of PMU Measurements

An end-to-end supervised learning method is developed to classify transmission line faults in a twoyear field-recorded dataset that includes synchronized measurements of three-phase voltages recorded by 38 Phasor Measurement Units (PMU) sparsely located in in the US Western Grid interconnection. Statistical analysis is performed to extract features from this large dataset to train Support Vector Machine (SVM), Random Forest (RF), and eXtreme Gradient Boosting (XGBoost) classifiers initially. The training further leverages a simulated dataset from a synthetic grid with 12 PMUs to increase the number of faults of types infrequently seen in the field-recorded dataset. Training the classification models with the combined dataset resulted in a classification accuracy of 97.7%. This is a significant improvement over 89.7% to 92.5% accuracy obtained by relying on the field-recorded dataset alone.

47 OTHER INSTRUMENTATION↗

Smart Grid Integrity Attacks: Characterizations and Countermeasures

Real power injections at loads and generators, and real power flows on selected lines in a transmission network are monitored, transmitted over a SCADA network to the system operator, and used in state estimation algorithms to make dispatch, re-balance and other energy management system [EMS] decisions. Coordinated cyber attacks of power meter readings can be arranged to be undetectable by any bad data detection algorithm. These unobservable attacks present a serious threat to grid operations. Of particular interest are sparse attacks that involve the compromise of a modest number of meter readings. An efficient algorithm to find all unobservable attacks [under standard DC load flow approximations] involving the compromise of exactly two power injection meters and an arbitrary number of power meters on lines is presented. This requires O(n2m) flops for a power system with n buses and m line meters. If all lines are metered, there exist canonical forms that characterize all 3, 4, and 5-sparse unobservable attacks. These can be quickly detected in power systems using standard graph algorithms. Known secure phase measurement units [PMUs] can be used as countermeasures against an arbitrary collection of cyber attacks. Finding the minimum number of necessary PMUs is NP-hard. It is shown that p + 1 PMUs at carefully chosen buses are sufficient to neutralize a collection of p cyber attacks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

The Feasibility of Moving PMU Data in the Future Power Grid

The power grid is a complex network connecting electricity providers with their consumers. With an increasing consumer base requiring more resources and the requirement to integrate significant renewable sources, maintaining the network requires new and innovative management solutions. To manage this complexity and provide precise, real-time views of the grid, Phasor Measurement Units (PMUs) are undergoing widespread deployment. These units provide measurements as often as 60 times per second, with an accurate time identifier attached to each reading, enabling real-time monitoring of the network. However, this new capability generates much more data than the current infrastructure is designed to handle. With the expectation that there will eventually be tens of thousands of PMUs monitoring the transmission lines, the power community is looking towards accumulating multiple terabytes of data per day - several orders of magnitude beyond current data acquisition rates. This has led to questions being raised in the power community about whether or not a significant research effort is required to effectively transfer the volume of information generated by these new data streams. This paper answers that question by comparing a worst-case data generation scenario with several alternative networking protocols and historical trends in protocol advancement. Based on this analysis we are able to conclude that transferring the information between the PMUs and the resulting data repositories is feasible. We recognize that there are issues beyond transferring the data that need to be addressed such as effective access to historical data, data transfer latency, cyber security, and data analysis. There is also an extensive engineering trade-off that the power companies will need to make to decide the best mix of networking protocols for their particular PMU deployments, since that requires significant assumptions about proprietary information including deployment cost, deployment schedules, PMU locations, and available resources.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Feature-Based PMU Event Classification under Variable PMU Participation and Overlapping Events

This paper is the basis for a presentation help at the 2026 Georgia Tech Fault & Disturbance Analysis Conference, which can be found at OSTI # 3168287 Paper Abstract—Phasor Measurement Units (PMUs) stream time synchronized, high-resolution measurements from the grid, enabling data-driven techniques for event detection and classification. Accurate event classification improves grid reliability and stability. Events can be detected by varying numbers of PMUs and exhibit different durations depending on the event type. This variability challenges standard classifiers that require uniform input sizes. Moreover, multiple events may coincide, which increases classification complexity. Standard classifiers assign each instance to the class with the highest predicted probability, whereas overlapping events may exhibit comparable probabilities across multiple classes. In this study, to handle data size variability, we extract a wide range of time–frequency domain features from all available PMUs for each event into a fixed-length vector, facilitating the application of standard machine learning classifiers, including Random Forest, XGBoost, LightGBM, Support Vector Machine, and Multilayer Perceptron. To account for overlapping events, a probabilistic post-processing step is applied. For a given data instance, if multiple predicted class probabilities exceed 30% and the differences between them are less than 10%, the event is assigned to multiple classes. Experiments using real-world PMU data demonstrate that the Random Forest and XGBoost models achieve the highest accuracy, while the proposed post-processing method yields perfect classification performance on external unseen test sets.

Nematirad, Reza [Danovo Energy Solutions]↗

Closed-Form Solution for Synchrophasor Data Correction under GPS Spoofing Attack

Phasor Measurement Units (PMUs) are increasingly being deployed to augment monitoring, protection and control applications in the power grid. PMUs rely on the Global Positioning System (GPS) for generation of time-synchronized and accurate measurements. However, civilian GPS signals, being unencrypted, are susceptible to GPS spoofing attacks (GSA). Hence ensuring the integrity of GPS-timing dependent synchrophasor data has become critical. In this paper, a closed-form analytical solution for estimating the GSA phase shift has been proposed and integrated to the spoofing detection & correction framework. Extensive simulations have been performed in order to verify the accuracy of the solution in determining the location and the phase shift of the compromised PMU. Time domain dynamic simulations presented in this paper demonstrate the applicability of the proposed solution for near-real-time detection of GSA, and this will enable faster detection and correction of phase angles of compromised synchrophasor data.

Synchrophasor, PMUs, GPS, Spoofing, Data Correctio↗

Applications of synchrophasor technologies in power systems

Synchrophasors are time-synchronized electrical measurements that represent both the magnitude and phase angle of the electrical sinusoids. Synchrophasors are measured by fast time-stamped devices called phasor measurement units (PMUs) to constitute the basis of real-time monitoring and control actions in the electric grid. Due to its enhanced situational awareness capabilities, many applications of PMUs are presented in the literature in the past decades. This paper presents a comprehensive summary of synchrophasor technology, its architecture, optimal placement techniques and its applications in electric power transmission and distribution systems. These applications include wide-area situational awareness and monitoring, state estimation, fault location and protective relaying, islanding detection etc. This review also covers some of the existing challenges in its implementation and its potential applications.

24 POWER TRANSMISSION AND DISTRIBUTION↗