Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “IBR Model”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Protection of Inverter-Dependent Transmission Systems (PROTECT-IT)

This presentation highlights the overall objectives of the SETO funded protection project. The main technical approaches are also highlighted. This high impact project produces multiple innovative outcomes, including comprehensive impact study of how IBR affects protection elements, simplified low-order IBR model for protection engineers, enhanced and data-driven protection design, co-design concept for coordination protection and IBRs.

14 SOLAR ENERGY↗

Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Standard Library Plant Controller Model Specification for a Grid-Forming Hybrid Control Inverter-Based Resource (REPCGFM_C1)

This document describes a standard library plant controller model to interface with the grid-forming hybrid control inverter-based resource (IBR) model. The initial version of model specification was jointly developed by Pacific Northwest National Laboratory (PNNL), Tesla Energy, and EPRI, and it was revised multiple times later to incorporate suggestions from WECC MVS members. Tesla Energy provided main control algorithms to support the development of this model specification. This standard library model is developed to help the utility industry better understand the GFM technology. The model could be used to represent equipment for long-term planning studies where vendor-specific models are not available. As equipment matures and improves, standard library models will be updated to capture the new functionalities of GFMs. It is not intended that these models will always remain representative of all future GFM technologies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Standard Library Grid-Forming Hybrid Control Inverter-Based Resource Model Specification (REGFM_C1)

This document describes a standard library grid-forming (GFM) hybrid control inverter-based resource (IBR) model. The GFM hybrid control approach implements both a typical GFM control and a typical grid-following (GFL) control inside one single inverter simultaneously, so that it can take advantage of both methods without comprising the benefits of a typical GFM. The initial version of model specification was jointly developed by Pacific Northwest National Laboratory (PNNL), Tesla Energy, and EPRI, and it was revised multiple times later to incorporate suggestions from WECC MVS members. Tesla Energy provided main control blocks to support the development of this model specification. This standard library model is developed to help the utility industry better understand the GFM technology. The model could be used to represent equipment for long-term planning studies where vendor-specific models are not available. As equipment matures and improves, standard library models will be updated to capture the new functionalities of GFMs. It is not intended that these models will always remain representative of all future GFM technologies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Transmission Data-Driven User-Defined Model for Inverter-based and Conventional Power Plants

Recent events in Odessa [1], [2] have shed light on the complexities of integrating large Inverter-Based Resource (IBR) plants with the transmission system, prompting NERC to stress continuous performance monitoring by transmission operators. Challenges such as plant control updates, IBR model revisions, Phase-locked loop loss of synchronism, and protection events have been identified, underscoring the need for enhanced monitoring protocols by regulatory bodies. The recent FERC 901 order underscores the importance of accurate data exchange regarding IBRs for reliability studies. However, limited access to IBR plant-related data hampers effective decision-making for transmission operators (TOP). This paper proposes a method for constructing data-driven User-Defined dynamic Models (UDM) for power plants for validating multiple-event data using field measurements from interconnection bus locations. The problem is formulated as a power plant model identification problem and a multi-task learning approach under partial input observability assumptions is proposed in this work. This approach aims to predict aggregated responses of conventional and IBR power plants during various dynamic physical events which is useful for planning studies under diverse disturbance conditions. Ultimately, this methodology emphasizes the importance of plant visibility to operators in addressing power system challenges, facilitating improved planning and operational studies.

Mahapatra, Kaveri [BATTELLE (PACIFIC NW LAB)]↗

DQ Admittance Model Extraction for IBRs via Gaussian Pulse Excitation

While $dq$ admittance models have shown to be very useful for stability analysis, extracting admittance models of inverter-based resources (IBRs) from the electromagnetic transient (EMT) simulation environment using frequency scans takes time. In this letter, a new perturbation method based on Gaussian pulses in combination with the system identification algorithms shows great promise for parametric $dq$ admittance model extraction. We present the $dq$ admittance model extracting method for a type-4 wind turbine. Challenges in implementing Gaussian pulse excitation are also pointed out. In conclusion, the extracted $dq$ admittance model via the new method shows to have a high matching degree with the measurements obtained from frequency scans.

24 POWER TRANSMISSION AND DISTRIBUTION↗

How Inverter-Based Resources (IBRs) Affect Protection Relay Elements

Inverter-based resources (IBRs) exhibit fault responses that differ significantly from those of synchronous generators, which can challenge the reliable operation of many commonly used power system protection elements. The fault response of IBRs is primarily influenced by their control algorithms and configurations, but the impact of these controls on protection relays is not yet fully understood. This presentation provides a comprehensive study of how IBR modeling and controls affect transmission line protection. Key modeling and control aspects include the DC source, inverter model, power level control, current control, and current limiting. The study reveals that certain aspects - such as the type of DC source (battery, PV, or hybrid), inverter model (average vs. switching), and power level control methods (PQ dispatch vs. Vdc-Vac control for grid-following IBRs, and droop vs. VSM for grid-forming IBRs) - do not significantly affect relay response. However, faster control loops, such as current control and current limiting, do influence the relay behavior. Additionally, the study explores the effects of other factors, including momentary cessation, operating points, fast/slow current responses, and grid strength on relay performance. Finally, the study offers recommendations for both IBR and protection engineers to improve IBR fault response and enhance the reliability of protection systems.

14 SOLAR ENERGY↗

Impact of Inverter-Based Resources on Grid Protection: A Review of Negative-Sequence Current Generation

The increasing integration of inverter-based resources (IBRs) in power grids poses challenges to traditional protection systems, primarily due to their different fault current signatures compared to conventional synchronous generators. Unlike synchronous generators whose fault response is dictated by their physical design, IBRs exhibit a wide range of fault characteristics due to manufacturer-specific control algorithms and settings. This dependence on proprietary control schemes makes modeling IBR behavior during faults significantly more complex, especially considering the rapid evolution of inverter technology and the diverse control strategies employed. While much research has focused on the positive-sequence current injections of IBRs during symmetrical faults, the understanding of negative-sequence current generation during non-symmetrical faults remains limited. This report provides an overview of current research on IBRs' negative-sequence current generation during unbalanced faults and its impact on protection schemes based on negative-sequence components. It covers both type III wind turbines and full-size converter-based IBRs. Additionally, this report reviews strategies for grid-forming controlled inverters to generate negative-sequence current during unbalanced faults, in addition to grid-following controlled ones.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Sleep Disruption Medical Intervention Forecasting (SDMIF) Module for the Integrated Medical Model

The NASA Integrated Medical Model (IMM) assesses the risk, including likelihood and impact of occurrence, of all credible in-flight medical conditions. Fatigue due to sleep disruption is a condition that could lead to operational errors, potentially resulting in loss of mission or crew. Pharmacological consumables are mitigation strategies used to manage the risks associated with sleep deficits. The likelihood of medical intervention due to sleep disruption was estimated with a well validated sleep model and a Monte Carlo computer simulation in an effort to optimize the quantity of consumables. METHODS: The key components of the model are the mission parameter program, the calculation of sleep intensity and the diagnosis and decision module. The mission parameter program was used to create simulated daily sleep/wake schedules for an ISS increment. The hypothetical schedules included critical events such as dockings and extravehicular activities and included actual sleep time and sleep quality. The schedules were used as inputs to the Sleep, Activity, Fatigue and Task Effectiveness (SAFTE) Model (IBR Inc., Baltimore MD), which calculated sleep intensity. Sleep data from an ISS study was used to relate calculated sleep intensity to the probability of sleep medication use, using a generalized linear model for binomial regression. A human yes/no decision process using a binomial random number was also factored into sleep medication use probability. RESULTS: These probability calculations were repeated 5000 times resulting in an estimate of the most likely amount of sleep aids used during an ISS mission and a 95% confidence interval. CONCLUSIONS: These results were transferred to the parent IMM for further weighting and integration with other medical conditions, to help inform operational decisions. This model is a potential planning tool for ensuring adequate sleep during sleep disrupted periods of a mission.

Lewandowski, Beth↗

Preliminary Gap Analysis of Existing IEEE 1547 and IEEE 2800 Standards Towards GFM Technology

This document describes the tests that are conducted on generic grid-forming (GFM) distributed energy resource (DER) and inverter-based resource (IBR) models to check if the performance of the model aligns respectively with the IEEE Std 1547 TM -2018 and IEEE Std 2800 TM -2022 requirements. For the IEEE Std 1547 TM -2018 requirements, specifically the tests related to volt-var requirements and frequency droop requirements are conducted. For the IEEE Std 2800 TM -2022 requirements, specifically the tests conducted are related to reactive- power-voltage control requirements, active-power-frequency response requirements, voltage disturbance ride through requirements and phase jump ride through requirements. This is an initial draft/document. There are many more tests still yet to be done to further verify if the existing standards have a gap or inadvertent barrier to GFM technology.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Review on Protection Challenges on Transmission Lines Connected to Inverter Based Resources

The increased penetration of inverter-based resources (IBRs) connected to transmission grids is challenging how traditional electric power systems operate. Such systems were originally designed based on the dominant presence of synchronous generators. Some main challenges include the increased concerns about system stability due to the reduced system inertia caused by IBRs and the reduced protection reliability caused by the non-deterministic fault current response of IBRs. The protection relays’ algorithms have been designed and validated based on well-known fault current characteristics of synchronous generations, while the short-circuit responses of IBRs heavily depend on their vendor-specific control schemes, which are mainly set to protect inverter semiconductor switches and DC components. The magnitude of short current that IBRs contribute is typically between 1.1–1.5 times the rated current that may behave unstably and incoherently with the voltages. The control scheme of the IBRs also controls the active (P) and reactive (Q) support during system voltage sag and swell conditions. These characteristics challenge not only protective relay schemes but also existing short-circuit software tools to correctly model IBRs for fault studies and protection coordination analyses. Utilities, university researchers, research institutes, and relay manufacturers have performed studies to investigate different aspects of high IBR penetration. Almost all studies support 1) creating international and national standards to regulate the IBRs, 2) revising engineering tools to address shortcomings, and 3) adjusting the protective relay settings to resolve protection problems. This paper summarizes the studies and research conducted in recent years to quantify the impact of IBR penetration on transmission line protection and to identify potential solutions to improve the dependability and reliability of grid protection systems.

14 SOLAR ENERGY↗

A review on protection challenges of Transmission Lines connected to Inverter Based Resources

The increased penetration of inverter-based resources (IBRs) connected to transmission grids is challenging how traditional electric power systems operate. Such systems were originally designed based on the dominant presence of synchronous generators. Some main challenges include the increased concerns about system stability due to the reduced system inertia caused by IBRs and the reduced protection reliability caused by the non-deterministic fault current response of IBRs. The protection relays’ algorithms have been designed and validated based on well-known fault current characteristics of synchronous generations, while the short-circuit responses of IBRs heavily depend on their vendor-specific control schemes, which are mainly set to protect inverter semiconductor switches and DC components. The magnitude of short current that IBRs contribute is typically between 1.1–1.5 times the rated current that may behave unstably and incoherently with the voltages. The control scheme of the IBRs also controls the active (P) and reactive (Q) support during system voltage sag and swell conditions. These characteristics challenge not only protective relay schemes but also existing short-circuit software tools to correctly model IBRs for fault studies and protection coordination analyses.

14 SOLAR ENERGY↗

A Review on Protection Challenges of Transmission Lines Connected to Inverter-Based Resources

The increased penetration of inverter-based resources (IBRs) connected to transmission grids is challenging how traditional electric power systems operate. Such systems were originally designed based on the dominant presence of synchronous generators. Some main challenges include the increased concerns about system stability due to the reduced system inertia caused by IBRs and the reduced protection reliability caused by the non-deterministic fault current response of IBRs. The protection relays’ algorithms have been designed and validated based on well-known fault current characteristics of synchronous generations, while the short-circuit responses of IBRs heavily depend on their vendor-specific control schemes, which are mainly set to protect inverter semiconductor switches and DC components. The magnitude of short current that IBRs contribute is typically between 1.1–1.5 times the rated current that may behave unstably and incoherently with the voltages. The control scheme of the IBRs also controls the active (P) and reactive (Q) support during system voltage sag and swell conditions. These characteristics challenge not only protective relay schemes but also existing short-circuit software tools to correctly model IBRs for fault studies and protection coordination analyses

14 SOLAR ENERGY↗

Estimating the Need for Medical Intervention due to Sleep Disruption on the International Space Station

During ISS and shuttle missions, difficulties with sleep affect more than half of all US crews. Mitigation strategies to help astronauts cope with the challenges of disrupted sleep patterns can negatively impact both mission planning and vehicle design. The methods for addressing known detrimental impacts for some mission scenarios may have a substantial impact on vehicle specific consumable mass or volume or on the mission timeline. As part of the Integrated Medical Model (IMM) task, NASA Glenn Research Center is leading the development of a Monte Carlo based forecasting tool designed to determine the consumables required to address risks related to sleep disruption. The model currently focuses on the International Space Station and uses an algorithm that assembles representative mission schedules and feeds this into a well validated model that predicts relative levels of performance, and need for sleep (SAFTE Model, IBR Inc). Correlation of the resulting output to self-diagnosed needs for hypnotics, stimulants, and other pharmaceutical countermeasures, allows prediction of pharmaceutical use and the uncertainty of the specified prediction. This paper outlines a conceptual model for determining a rate of pharmaceutical utilization that can be used in the IMM model for comparison and optimization of mitigation methods with respect to all other significant medical needs and interventions.

Myers, Jerry G.↗

End-To-End Decentralized Transmission Line Protection in IBR-Dominated Weak Grids Using Interpretable Data-Driven Methods

Traditional transmission line protection relies on predictable synchronous-based fault signatures, which frequently fail under the non-standard, current-limited fault characteristics of Inverter-Based Resources (IBRs). This study investigates how to achieve secure, communication-free fault isolation in IBR-dominated weak grids without relying on opaque, computationally heavy "black-box" machine learning algorithms. To address this, we propose a novel, standalone, and inherently interpretable data-driven protection framework. Unlike centralized methods requiring multi-terminal communication, this decentralized approach relies solely on local measurements using a hierarchical linear-kernel Support Vector Machine (SVM). The methodology decomposes the protection task into four sequential stages that mimic traditional protection elements: fault detection and fault direction identification, fault type classification, zone classification, and location estimation. This multi-stage architecture allows for specialized feature engineering at each stage, combining high computational efficiency with logic traceability. The framework's end-to-end performance was validated via C-code and PSCAD/EMTDC co-simulation, utilizing a real-world utility network and an OEM black-box IBR model. The proposed relay achieves 97.2% overall accuracy and provides a reliable trip decision within a 2.5-cycle window. The results confirm 100% accuracy in fundamental fault detection, reliable zone selectivity across low to moderate fault resistances, and robust security against non-fault transients, proving its immediate viability for integration into commercial numerical relays.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Fault Contribution of Grid-Following and Grid-Forming Inverters Considering Generic Inverter Controls and Ride-through Requirements

Gradual transformation of the synchronous generator (SG)-dominated power systems to inverter-based resource (IBR)-dominated power systems is bringing new challenges regarding power system protection. Increasing IBR’s penetration will reduce the reliability of protection coordination, originally developed for SG-dominated power systems, potentially leading to less accurate calculation or even mis-operation. Thus, new protection schemes compatible with IBR-dominated power systems should be established. Prior to establishing the protection schemes, research on the fault contribution of generic IBR models should be conducted considering interconnection requirements. This paper conducts fault current contribution analysis of generic grid-following (GFL) and grid-forming (GFM) inverters considering interconnection requirements using an electromagnetic transient (EMT) simulation tool. To do this, EMT-based generic GFL models have been developed with the ride-through requirements from IEEE-1547 standards. In addition, the major functions of the generic models are explained. Then, the fault current analysis was conducted using GFL and GFM inverters in a single-inverter-infinite-bus system and a modified IEEE 34-node system considering different grid, fault, inverter control parameters.

Kim, Jinho [BATTELLE (PACIFIC NW LAB)]↗

Assessing the Feasibility of Bordered Block Diagonal Reordering in Power System Matrices using Fully Convolutional Network

In electromagnetic transient (EMT) simulations for power systems and inverter-based resources (IBRs), the arrangement of states within the system's linear equations, represented by matrix A in Ax=b, is critical. The state ordering in matrix A can highlight distinct characteristics of the system's graph, and identifying an optimal state ordering is crucial for efficient computation. The choice of state ordering, however, is dependent on the solver used, as each solver may perform optimally with different matrix patterns. With a wide array of matrix reordering algorithms available, selecting the most suitable one becomes challenging without insights into the matrix's ideal configuration. To address this, the paper proposes a fully convolutional network (FCN) to evaluate the reordering potential of the A matrix into a bordered block diagonal (BBD) pattern, which is commonly observed in power system and IBR modeling. The FCN's assessment aims to streamline the solver's operation, which in turn could substantially reduce the computational time required to find a solution.

Xia, Qianxue↗

Photovoltaic Analysis and Response Support (PARS) Platform for Solar Situational Awareness and Resiliency Services

The project's primary objective is to develop a digital-twin based Photovoltaic (PV) Analysis and Response Support (PARS) platform, which aims to provide real-time situational awareness and optimal response plans. This platform is designed to enhance the performance of hybrid PV systems, making them competitive with or even superior to conventional generation resources. The PARS platform enabled the project team to develop and evaluate an extensive suite of grid support functionalities for the hybrid PV systems to enhance grid performance, across key areas including visibility, dispatchability, security, resilience, and reliability. Given the global push toward achieving 100% clean energy by 2035, there is a significant increase in the integration of inverter-based resources (IBRs) throughout the energy grid. Effectively managing the inherent variability and uncertainty associated with IBRs is crucial for ensuring cost-effectiveness, reliability, and security in both the main grid and islanded microgrids. Constrained to a limited array of IEEE test systems or standard feeder models, traditional IBR modeling struggles to assimilate new field data, accurately reflect system dynamics, and adapt to the evolving energy landscape. In our project, we embraced a Digital Twin (DT) strategy for crafting the PARS platform. A digital twin acts as a precise virtual counterpart of a physical system, built on historical data and continuously honed with real-time insights. This enables the high-fidelity DT to accurately mirror current system operations and forecast future scenarios. Consequently, the PARS platform becomes an ideal environment for testing and refining monitoring, control, power, and energy management algorithms designed to boost hybrid PV system performance. The defining feature of the PARS platform, distinguishing it from other advanced simulation tools, is its exceptional adaptability. This is achieved by employing actual network topologies and utilizing real-time field data for fine-tuning and calibration, ensuring a close emulation of real-world conditions. The project deliverables include: 1) High-fidelity IBR models and tools for real-time parameterization, utilizing real-time field measurements to refine IBR models for enhanced accuracy and performance; 2) Grid-forming and Grid-following capabilities to deliver resilience services, including blackstart, voltage and frequency support, cold-load pick-up, power reserves, and three-phase load balancing across grid-connected and microgrid settings; 3) Machine learning-based forecasting tools and methods for generating synthetic data and topologies, creating diverse and realistic simulation environments for evaluating varied operational scenarios; 4) Advanced microgrid power and energy management algorithms for optimizing the integration and operation of PV, storage, and demand response resources within both feeder and community scales. The power grid data sets are provided by four utility companies in North Carolina and the New York Power Administration. Acting as industry advisors, our industry partners communicated stakeholder needs and regulatory standards to the research teams, aiding technology transfer by incorporating the developed methodologies into their daily operations. This collaboration ensures that the PARS platform, functioning as a power system digital twin, enhances our understanding of IBR dynamic behaviors and enables the development and evaluation of IBR control functions that match or exceed the capabilities of conventional synchronous generators.

14 SOLAR ENERGY↗