Sensitivity Effects of High Temperature Overhead Conductors to Line Rating Variables
For traditional overhead transmission lines, the maximum allowable conductor operating temperature on ASCR, AAC, or AAAC lines for determining the static line ratings can be quite low, typically well under 100 C. At these low temperatures, the primary driver for determining static line ratings are assumptions made about the wind speed and direction and the ambient temperature. Assumptions for solar loading and emitted thermal radiation, driven by line emissivity and absorptivity, are secondary factors, and only provide small changes to the static ratings. However, when considering newer high temperature conductors such as ACSS, ACCR, ZTACIR, and ACCC® the maximum allowable conductor temperatures can be significantly higher, up to 250° C. This higher temperature shifts the importance of the emissivity assumptions of the overhead transmission line, due to the nature of the T4 dependence of the radiative heat loss compared to the T1 dependence of the convective heat loss, as well as shifting the dependency on local wind conditions. Typical assumptions in the United States for the emissivity/absorptivity of overhead transmission lines in determining the static ratings are to use a value of 0.5 for both parameters or set a value in the range of 0.7 to 0.9. Recent experimental tests at EPRI have shown that higher emissivity aging assumptions may not be valid in some regions of the US, and that actual values may be much lower (0.25-0.45) than older studies have predicted (0.8-0.9). Here, the assumptions of different US Regional Transmission Operators (RTOs) and different utilities within RTOs are examined for the static ratings for traditional lower operating temperatures up to 100° C as well as with the higher maximum temperature conductors associated with newer conductor designs at 250° C. The sensitivity of the static ratings is examined at both lower and higher temperature conductors with respect to overhead line emissivity and absorptivity, wind speed, wind direction, and solar loading, and ambient temperature. It is shown that the effects of the conductor absorptivity, solar flux and ambient temperature on the static rating are increased when the transmission line has a lower maximum conductor temperature. The effects of the conductor emissivity, wind direction and wind speed have increased effects on the static rating when the transmission line has a higher maximum conductor temperature. In addition, example weather data is used to calculate the conductor temperature with different line emissivity and absorptivity assumptions. This shows the effect of assumptions made for emissivity only has a minor impact for low temperature lines, but for high temperature transmission lines can cause a 150-200° C temperature swing.