Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “Cascading Failure”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

From Ensemble Climate to Ensemble Impacts

Many climate-risk tools rely on ensemble mean projections or endpoint climate snapshots to characterize future hazards. Although convenient for communication, these representations remove the statistical, temporal, and physical information that real infrastructure systems respond to. Infrastructure degradation and failure arise from extremes, sequences, cumulative stress, compound hazards, and nonlinear fragility relationships, none of which survive ensemble averaging or temporal compression. Power-system failure statistics and cascading failure models further show that infrastructure risk is dominated by tail events and path-dependent dynamics rather than by mean conditions. This paper demonstrates why ensemble mean or endpoint-only climate representations are mathematically and physically inconsistent with engineering-grade risk analysis. We outline a model-resolved, time-series-based workflow that preserves extremes, variability, and sequencing by propagating each climate-model realization independently through hazard formation, exposure, fragility, and cascading failure mechanisms. Taking the ensemble of impacts—rather than the ensemble of climate—provides a defensible, physically coherent foundation for infrastructure resilience planning, regulatory compliance, and long-term investment decisions.

54 - ENVIRONMENTAL SCIENCES/GLOBAL CLIMATE CHANGE ↗

An Integrated High-performance Computing and Digital Real-time Simulation Testbed to Benchmark Closed-loop Load Shedding Algorithms in Power Systems

An integrated testbed using digital real-time simulator (DRTS) and a high-performance computing (HPC) cluster is presented here to compare speed and performance of computational schemes to mitigate time-critical issues in electric power systems. The first approach in this testbed validation is taken by running a set of closed-loop load shedding algorithms to compare and contrast two paradigms of arresting cascading failure propagation. Two algorithms involve solving DC and AC power flow model-based optimization problems to compute load shedding at different buses, while a model-based stochastic search using parallel computing provides a viable alternative. The algorithms are implemented in the DRTS-HPC testbed for the IEEE 14-bus benchmark transmission system. As a proof of the concept, simulation results are presented for implementation of closed-loop load-shedding algorithms for cascading failures in the DRTS-HPC testbed

24 POWER TRANSMISSION AND DISTRIBUTION↗

Representation and Impact of Water Head on Power System Planning and Operation

Representing water head information in power system model files, can provide a more realistic model of the system and thereby inform operation and planning personnel in the decision-making process. This article describes a procedure for modifying the power system model files (steady-state and dynamic) to represent water head information. Additionally, the impact of representing the water head on power system reliability studies including contingency analysis, cascading failure analysis and dynamic frequency response analysis has been investigated, using the modified power system models. This paper considers the detailed Western Electricity Coordination Council model during summer and winter conditions as the test system for the impact analysis. Results show that under reduced water head: 1) the number of critical voltage and branch flow violations increases; 2) chances of cascading failure and island formation increases; and 3) frequency nadir decreases as compared to those of the base cases where the water head information is not represented.

13 - HYDRO ENERGY↗

Failure Probability Constrained AC Optimal Power Flow

Despite cascading failures being the central cause of blackouts in power transmission systems, existing operational and planning decisions are made largely by ignoring their underlying cascade potential. This paper posits a reliability-aware AC Optimal Power Flow formulation that seeks to design a dispatch point which has a low operator-specified likelihood of triggering a cascade starting from any single component outage. By exploiting a recently developed analytical model of the probability of component failure, our Failure Probability-constrained ACOPF (FP-ACOPF) utilizes the system's expected first failure time as a smoothly tunable and interpretable signature of cascade risk. Here, we use techniques from bilevel optimization and numerical linear algebra to efficiently formulate and solve the FP-ACOPF using off-the-shelf solvers. Extensive simulations on the IEEE 118-bus case show that, when compared to the unconstrained and N-1 security-constrained ACOPF, our probability-constrained dispatch points can significantly lower the probabilities of long severe cascades and of large demand losses, while incurring only minor increases in total generation costs.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Nonnuclear Experimental Capabilities to Support Design, Development, and Demonstration of Microreactors

This work provides a summary of selected experimental capabilities being developed to support nonnuclear testing and demonstration of technology in support of microreactors under the U.S. Department of Energy’s (DOE’s) Microreactor Program. Major capabilities include the Single Primary Heat Extraction and Removal Emulator (SPHERE) and the Microreactor Agile Non-nuclear Experimental Test Bed (MAGNET). The SPHERE facility allows for controlled testing of the steady-state and transient heat rejection capabilities of a single heat pipe using electrical heaters that simulate nuclear heating. The facility is capable of monitoring axial temperature profiles along the heat pipe and surrounding test articles during startup, steady-state operation, and transients. Instrumentation includes noncontact infrared thermal imaging, surface thermocouples, spatially distributed fiber optic temperature and strain sensors, electrical power meters, and a water-cooled, gas-gap calorimeter for quantifying heat rejection from the heat pipe. The facility can be operated under both vacuum and inert-gas conditions. The MAGNET facility is a large-scale, 250-kW electrically heated microreactor test bed to enable nonnuclear experimental evaluation of a variety of microreactor concepts. It can be supplied to electrically heat a scaled section of a microreactor and further test the capabilities of heat rejection systems. The initial MAGNET experiments will support technology maturation and reduce uncertainty and risk associated with the design, operation, and deployment of monolithic heat pipe–based reactors. However, this test bed can broadly be applied to multiple microreactor concepts to evaluate a wide range of thermal-hydraulic and structural phenomena such as interface coupling with power conversion units and other collocated systems. MAGNET can evaluate integral thermomechanical effects during electrical heating of an array of heat pipes in a larger test article. Examples of initial testing will include thermal stresses in the monolith and the impact of debonding of a heat pipe from the core block and how that failure could impact surrounding heat pipes, i.e., understanding the potential for cascading failure. This work also discusses some modeling capabilities that can support experiment design, analysis, and interpretation, including the heat pipe code Sockeye and a comparison of thermal-structural simulations performed using ABAQUS and STAR-CCM+.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Mitigating commutation failures in HVDC systems with SFCL deployment

Commutation failures represent a prevalent issue encountered in line-commutated-converter high voltage direct current (LCC-HVDC) systems. As the widespread deployment of HVDC systems continues, the risk associated with commutation failures increases, posing a growing threat to power grids due to their potential to trigger severe consequences, including cascading failures and widespread blackouts. This research paper aims to address the significant issue of commutation failure within direct current (DC) systems through advocating for the use of resistive-type Superconducting Fault Current Limiters (R-SFCLs). To substantiate the efficacy of this proposed strategy, an array of simulations are executed using the PSCAD/EMTDC software. This comprehensive study investigates the performance characteristics of R-SFCLs configured with varying resistance values, scrutinizing their response under diverse fault resistance scenarios and distinct fault initiation times within the LCC-HVDC system. The outcomes of these simulations are that SFCLs confer significant advantages for mitigating commutation failures, surpassing traditional mitigation methods in terms of effectiveness. Consequently, SFCLs emerge as an optimal solution to prevent commutation failures in the HVDC systems.

Commutation failure↗

Dispersion of stored energy within a battery system at risk of failure

A method and system for dispersing stored energy in an energy storage system to delay or arrest propagation of thermal runaway and thermally-induced cascading failures. The system includes a plurality of battery sub-assemblies and DC-DC converters connected to a shared DC bus through which energy may be exchanged. The system may be interfaced to an AC power grid or DC power system through an additional power converter. The method of dispersing stored energy uses this system to charge and discharge sub-assemblies such that the system is less susceptible to propagation of thermal runaway. The method determines, based on awareness of current system state, battery types, and electrical and thermal structure, the sequence of charging and discharging actions to best inhibit thermal runaway while preserving the system's ability to perform subsequent energy redistribution.

Mueller, Jacob↗

Data Requirements for Application of Risk-Based Dynamic Contingency Analysis to Evaluate Hurricane Impact to Electrical Infrastructure in Puerto Rico

This paper presents a risk-based dynamic contingency analysis framework that was used to evaluate the hurricane impact to electrical infrastructure in Puerto Rico. PNNL developed a scalable risk-based framework for identifying high-voltage transmission resilience improvements by classifying and prioritizing high-risk power grid contingencies (system failures) under hurricane impact. The risk-based framework is founded on grid outage definitions with their associated probabilities of occurrence from hurricane events, in combination with an impact assessment derived from detailed dynamic cascading failure analysis. This paper focuses on a discussion around data requirements for transmission resilience planning for hurricane events, derived from the development of the risk-based framework and its application to Puerto Rico. This paper launches an important first step in encouraging the engineering community and power system industry to move towards establishing resilience planning as a routine practice. Since actual results for Puerto Rico contain sensitive information, sample simulation results will be used to illustrate the data requirements and risk-based dynamic cascading framework on the Puerto Rico power grid, as well as demonstrate the potential for such a simulation framework. The paper includes a discussion on the lessons learned, importance and need for improved datasets that are not usually considered in traditional power system planning. The paper will also elaborate on how the scalable simulation framework and datasets might be expanded to larger footprints and leveraged for modelling other types of natural disasters.

DCAT, Puerto Rico, hurricane, Power System Stabili↗

Predicting cell-to-cell failure propagation and limits of propagation in lithium-ion cell stacks

Thermal runaway of lithium-ion batteries is a risk that is magnified when stacks of lithium-ion cells are used for large scale energy storage. When limits of propagation can be identified so that systems can be designed to prevent large scale cascading failure even if a failure does occur, these systems will be safer. This work addresses the prediction of cell-to-cell failure propagation and the propagation limits in lithium-ion cell stacks to better understand and identify safe designs. A thermal-runaway model is presented based on recent developments in thermochemical source terms. It is noted that propagating failure is characterized by temperatures above which calorimetry data is available. Results show high temperature propagating failure predictions are too rapid unless an intra-particle diffusion limit is included, introducing a Damköhler number limiter into the rate expression. This new model form is evaluated against cell-to-cell failure propagation where the end cell of a stack is forced into thermal runaway through a nail-induced short circuit. Limits of propagation for this configuration are identified. Results show cell-to-cell propagation predictions are consistent with measurements over a range of cell states of charge and with the introduction of metal plates between cells to add system heat capacity representative of structural members. This consistency extends from scenarios where propagation occurs through scenarios where propagation is prevented.

25 ENERGY STORAGE↗

A Methodology to Evaluate the Grid Reliability Impact of Oscillations Induced by Large Loads

The rapid growth of hyperscale AI data centers is bringing renewed attention to the reliability risk that sustained forced oscillations pose to bulk power systems, with cyclic computational workloads emerging as a new forcing source. Unlike the broadband, stochastic disturbances from traditional industrial loads such as arc furnaces, AI training and inference facilities can inject large active power swings concentrated at specific frequencies over extended durations - characteristics that existing grid planning practices do not account for. While the North American Electric Reliability Corporation (NERC) has recognized this gap and called for system-level studies of large load interconnections, no standardized methodology exists to screen, simulate, and quantify these risks at the planning stage. This report presents the Risk Assessment Tool for Large Load-induced Events (RATLLE), a Python-based, publicly available script suite developed at the Pacific Northwest National Laboratory to evaluate bulk power system reliability risks from data center-induced oscillations. RATLLE implements a three-module workflow: a screening module that identifies vulnerable interconnection locations and excitable system modes; a simulation module that models cyclic data center load behavior using a commercial positive sequence simulation platform; and an analysis module that computes risk metrics and generates interactive visualization dashboards. The risk metrics, formulated around simulation observables, map oscillation impacts to a three-stage severity scale spanning latent equipment fatigue through imminent cascading failure. The methodology is demonstrated on two Western Electricity Coordinating Council (WECC) system models: a publicly available 240-bus reduced representation and a detailed 2031 Heavy Winter planning case. Case studies illustrate that even modest 50 MW forced oscillations at resonant frequencies can produce wide-area power swings, N-1 security constraint violations, and cascading generator trips through protection actions - outcomes that would not occur under normal operating conditions without oscillations present. The results underscore the need for standardized oscillation impact assessment in large load interconnection studies and provide a reproducible, extensible framework for utilities to adopt or customize within their existing planning workflows.

Biswas, Shuchismita↗

Identification of Critical Infrastructure via PageRank

Assessing critical infrastructure vulnerabilities is paramount to arranging efficient plans for their protection. Critical infrastructures are cyber-physical systems that can be represented as a network consisting of nodes and edges and highly interdependent in nature. Given the interdependent nature of critical infrastuctures, failure in one node may cause failure in many others resulting in a cascade of failures. In this paper, we propose a node criticality metric that uses Google’s PageRank algorithm to identify nodes that are likely to fail (are vulnerable), nodes whose failure may cascade to many other sites in the network (are important), and nodes that are both vulnerable and important (are critical). We then present a series of experiments to understand how protecting certain critical nodes can help mitigate massive cascading failures. Simulating failures in a real-world network with and without critical node protections demonstrates the importance of identifying critical nodes in an infrastructure network.

Kay, Bill↗

Solar Photovoltaic (PV) Damage Assessment After Typhoon Mawar: Findings and Recommendations for Resilient PV on Guam

A team from the National Renewable Energy Laboratory (NREL) visited Guam in August 2023 to assess failure modes of solar photovoltaic (PV) systems after Typhoon Mawar and to provide recommendations to increase the resilience of PV systems on Guam. The team visited 30 systems: commercial and utility scale, and rooftop and ground-mounted. The team observed systems with no apparent damage, as well as systems that were completely lost. Systems fared very well overall. The average failure rate of rooftop systems was 18%, with a median failure rate of 2%, meaning the few systems that suffered total loss pulled up the average. Only eight 8 of the 25 rooftop systems suffered more than 5% damage. All ground-mounted systems suffered less than 0.5% damage, aside from a carport that lost 16% of its modules. PV systems at Andersen Air Force Base suffered 5% damage on average, with a median system failure of 0.6%. In almost all cases, failures were the result of: (1) Inadequate clamping of the module frame to the mount, (2) Module mounting clamps rotating out of underlying support rail (i.e., T-bolt that rotates free at less than 60 degrees of rotation), (3) An object hitting the panel resulting in a fracture, and in some cases leading to a cascading failure of several more panels, and (4) Excessive tilt angle (in Guam, greater than 5 degrees can be a risk due to wind speed, and power production trade-offs are insignificant).

14 SOLAR ENERGY↗

Networked Microgrid Topology Reconfiguration to Promote Fairness in Proactive Load Shedding

Increasing occurrences of natural disasters and grid emergency events consistently challenge the safe and reliable operations of power systems. During such emergency situations, system operators may proactively shed load to mitigate risks. However, uncoordinated implementation of load shedding may disrupt electricity supply and even lead to cascading failures. Meanwhile, it is crucial to address potential biases affecting different customers when executing load shedding. This paper addresses the dynamic topology reconfiguration problem for networked microgrids with distributed energy resources under emergency conditions. Specifically, we propose a novel rolling-horizon optimization model that integrates fairness-aware constraints into the networked microgrid topology reconfiguration. Unlike existing approaches that focus solely on efficiency or apply fairness considerations in static settings, our method explicitly incorporates temporal fairness constraints to restrict repeated or excessive load curtailment for load blocks. Moreover, the fairness-aware constraints are specifically developed for the context of dynamic networked microgrid topology reconfiguration, and are designed to be convex or amenable to linear reformulations, which offers a more tractable alternative to traditional models with non-convex formulations. Numerical studies on a modified IEEE 13-bus system and a larger-sized SMART-DS networked microgrid system demonstrate the performance of the proposed algorithm towards more fairness-aware networked microgrid topology reconfiguration decision-making.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Compressible battery foams to prevent cascading thermal runaway in Li-ion pouch batteries

Lithium-ion battery packs require thermal management to achieve optimum life and safety. This is becoming crucial for battery packs composed of high-energy-density cells. Pouch cells themselves achieve highest packaging efficiency but require additional structural support and thermal management when grouped into modules, especially under abusive conditions such as thermal runaway. Novel foam battery pads have demonstrated to cushion volume changes of pouch cells and are reengineered in this study to mitigate cell-to-cell thermal runaway propagation. The compressible pads are made of polyurethane foams incorporating flame-retardant additives or coatings, including intumescent and fire wall materials. Here their performances were evaluated by conducting nail penetration tests on modules composed of pouch cells at 100% state of charge (SOC), with the foams placed in between the cells. Experimental results show cascading thermal runaway was considerably delayed by polyurethane foams incorporating flame-retardant additives or coatings. Complete prevention of cascading failure was achieved with dense polyurethane foams with multilayered coatings of both fire wall and intumescent materials.

25 ENERGY STORAGE↗

High-Fidelity Multiphysics Modeling of a Heat Pipe Microreactor Using BlueCrab

Researchers who are actively developing nuclear microreactors are planning to employ innovative designs and features using traditional commercial modeling tools that may be inadequate for their design and licensing activities. The codes developed under the U.S. Department of Energy Office of Nuclear Energy Advanced Modeling and Simulation (NEAMS) program provide flexibility in terms of geometry modeling and multiphysics coupling and are particularly well suited for modeling novel microreactor concepts. To test the maturity of these codes, this paper introduces a conceptual heat pipe microreactor (HP-MR) designed to gather various technologies of interest to microreactor developers such as control drums, heat pipes, and hydride moderators. Here, the objective of this effort is to demonstrate NEAMS tools capability to perform high-fidelity multiphysics simulations, using coupled neutronics (via the Griffin code), heat conduction (via the BISON code), heat pipe modeling (via the Sockeye code), and hydrogen redistribution in hydride metal moderator (via the SWIFT code). Codes are coupled in-memory through the Multiphysics Object-Oriented Simulation Environment (MOOSE) framework, which permits flexible multiphysics data transfer schemes. The analysis confirmed two key aspects of the HP-MR concept: (1) its ability to follow the power load requested from the heat pipe and (2) its ability to avoid heat pipe cascading failure unless designed with high power close to operating failure limits of its heat pipes. The developed computational model was distributed publicly on the Virtual Test Bed for training purposes to accelerate adoption by industry and to provide a high-fidelity multiphysics solution for benchmarking against other tools. Additional multiphysics analyses including other transients and coupled physics were identified as necessary future work, together with a focus on validating multiphysics behavior against experiments.

Microreactor↗

Finite-time correlations boost large voltage angle fluctuations in electric power grids

Abstract Decarbonization in the energy sector has been accompanied by an increased penetration of new renewable energy sources in electric power systems. Such sources differ from traditional productions in that, first, they induce larger, undispatchable fluctuations in power generation and second, they lack inertia. Recent measurements have indeed reported long, non-Gaussian tails in the distribution of local voltage frequency data. Large frequency deviations may induce grid instabilities, leading in worst-case scenarios to cascading failures and large-scale blackouts. In this article, we investigate how correlated noise disturbances, characterized by the cumulants of their distribution, propagate through meshed, high-voltage power grids. For a single source of fluctuations, we show that long noise correlation times boost non-Gaussian voltage angle fluctuations so that they propagate similarly to Gaussian fluctuations over the entire network. However, they vanish faster, over short distances if the noise fluctuates rapidly. We furthermore demonstrate that a Berry–Esseen theorem leads to the vanishing of non-Gaussianities as the number of uncorrelated noise sources increases. Our predictions are corroborated by numerical simulations on realistic models of power grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Load Shed Recovery With Transmission Switching and Intentional Islanding Methods After (N-2) Line Contingencies

Changing power system configuration may result in load shed recovery (LSR) because topology change can provide power flow control in meshed network. Some topologies may favor generation redispatch as compared to others and can eliminate line congestion which leads to LSR. One of the known methods for topology change is called transmission switching (TS) and research conducted in the past showed that TS is an effective means of mitigating load shedding. Another method of topology control is intentional islanding (IIS). In this manuscript, we explore IIS as a potential solution for LSR. IIS based on generator coherency has been presented in literature for mitigating cascading failures. However, IIS has not been explored solely as a LSR mechanism. In this paper, we compare the LSR based on IIS with well known LSR algorithm based on TS. The comparison is performed for IEEE 39-bus system and IEEE 118- bus system. The results show that IIS has a potential to perform better than TS in terms of computational efficiency and LSR.

42 ENGINEERING↗

Bayesian Structural Time Series for Behind-the-Meter Photovoltaic Disaggregation: Preprint

Distributed photovoltaic (PV) generation often occurs ``behind the meter": a grid operator can only observe the net load, which is the sum of the gross load and distributed PV generation. This lack of observability poses a challenge to system operation at both bulk level and distribution level. The lack of real-time or near-future disaggregated estimates of gross load and PV generation will lead to over scheduling of energy production and regulation reserves, reliability constraints violations, wear and tear of controller devices, and potentially cascading failures of a system. In this paper we propose the use of a Bayesian Structural Time Series (BSTS) model with local solar irradiance measurements to disaggregate the summed PV generation and gross load signals at a downstream measurement site. BSTSs are a highly expressive model class that blends classic time series models with the powerful Bayesian state space estimation framework. Disaggregation is done probabilistically, which automatically quantifies the uncertainties of the estimated PV generation and gross load consumption. Depending on the data availability in real-time, it can be used to disaggragate PV and gross load at customer site, or can be used at the feeder level. In this paper, we focus on solving the problem at feeder level. We compare the performance of a BSTS model as well as a handful of state-of-the-art methods on a Pecan Street AMI dataset, using the National Solar Radiation Database (NSRDB) to estimate local irradiance.

Bayesian structural time series↗