Experimental test of model predictive control in a variable air volume system
Model predictive control (MPC) has been widely studied as a promising approach for improving energy efficiency and operational flexibility in buildings, yet its real-world performance for commercial variable air volume (VAV) systems remains insufficiently characterized. In particular, the impacts of model mismatch on control robustness, real-time computational burden, and device-level operation are rarely evaluated using long-term field data. Here, this study presents a comprehensive experimental evaluation of MPC applied to a full-scale VAV system in Oak Ridge National Laboratory’s Flexible Research Platform-2 building with constant cooling/heating temperature setpoints and no occupancy. The study offers three key advantages over existing work: (1) it uses a representative building in a full-scale experimental test, capturing realistic system dynamics and complexity; (2) it evaluates a relatively sophisticated MPC formulation using two different optimization solvers (Gurobi and PSO), fully accounting for computational complexity and methodological diversity; and (3) it systematically assesses potential negative impacts on various building devices, benchmark against a well-established baseline, ASHRAE Guideline 36 (G36). To isolate zone- and air-handling-unit–level supervisory control effects, the supply fan was operated with a fixed static pressure setpoint under all strategies, and the trim-and-response static pressure reset in G36 was not enabled. Results show that MPC maintained thermal comfort while improving energy efficiency. Abrupt solar radiation variations degraded performance. Computation times ranged from ∼1 s (Gurobi) to ∼ 70 s (PSO). Compared with G36, MPC achieves 33% energy savings and reduces median reheat coil output by approximately a factor of 5–10 for a representative cooling day under matched weather conditions. However, it increases the maximum discomfort deviation from 0.5 to 1°C and results in a 32% increase in staging frequency. In addition, PSO-based MPC introduced damper oscillations, also affecting actuator longevity.