Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “REFRIGERATION”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 343 records · Page 19

Chemical stability investigation of haloolefin refrigerants and their blends with lubricants

This paper examines the findings of highly accelerated life tests (HALT), conducted according to ASHRAE Standard 97 sealed glass tube methodology for R-123 like, R-134a like and R-410A/R-404A like lower global warming potential (GWP) alternatives. Additionally, possible chemical breakdown pathways are reviewed for the new haloolefin refrigerants. Note, compositions for the following blends are shown as percent by weight. For R-123 like refrigerants, R-1336mzz(Z), R-1336mzz(E), R-514A (74.7% R-1336mzz(Z)/25.3% R-1130(E)), R-1233zd(E), and R-1224yd(Z) were examined with and without lubricants. R-1233zd(E) and R-1224yd(Z) were evaluated with mineral oil and the rest were evaluated with polyalkylene glycol (PAG), polyolester (POE) and polyvinyl ether (PVE) lubricants. For R-134a like refrigerants, R-1234ze(E), R-450A (42% R-134a/58% R-1234ze(E)), R-515B (91.1% R-1234ze(E)/8.9% R-227ea), R-1234yf, R-513A (56% R-1234yf/44% R-134a), and R-516A (77.5% R-1234yf/8.5% R-134a/14.0% R-152a) were examined with and without PAG, POE, and PVE lubricants. For R-410A/R-404A like, R-454B (68.9% R-32/31.1% R-1234yf), R-454C (21.5% R-32/78.5% R-1234yf), R-455A (3.0% R-744/21.5% R-32/75.5% R-1234yf), and R-468A (3.5% R-1132a/21.5% R-32/75.0% R-1234yf) were also examined with PAG, POE and PVE lubricants. R-466A (49% R-32/11.5% R-125/39.5% CF 3 I) was part of this study but will not be covered since it does not contain a haloolefin component.

37 INORGANIC, ORGANIC, PHYSICAL, AND ANALYTICAL CH↗

Performance Testing of the 4kW ESR 2 Refrigerator at JLab

Abstract The End Station Refrigerator 2 (ESR2), a refurbished cryoplant, will replace the ESR1. ESR2 is comprised of the cold box and compressors from the Superconducting Super Collider’s 4 kW, 4.5 K ASST-A plant. It also features a new 10 kL liquid helium dewar, a cryogenic distribution system and new control and utility systems. This plant was reconfigured to provide a cold helium supply at 15 K, 12 K, and 8 K for the experimental hall’s hydrogen targets. The most significant load will be during the MOLLER experiment, which will see a total hydrogen target load of 5 kW at 15 K. This paper details the commissioning results of the 4.5 K refrigeration system in various modes (maximum refrigeration, maximum liquefaction, and a 50/50 mix) at both 100 % and 50 % capacity. We will also evaluate the performance with an expected MOLLER load. Current performance will be compared with the historical commissioning data from the ASST-A plant.

Perry, C. [Cryogenics Department, Thomas Jefferson↗

Tablelike magnetocaloric effect and enhanced refrigerant capacity in EuO 1- δ thin films

The effect of electron doping of EuO 1- δ thin films through oxygen vacancies ( δ = 0, 0.025, and 0.09) upon the magnetocaloric response is presented here. The films each showed a paramagnetic to ferromagnetic transition around 65 K, with an additional magnetic ordering transition at higher temperatures in the oxygen deficient samples. All transitions are observed to be of second order. A maximum magnetic entropy change of 6.4 J/kg K over a field change of 2 T with a refrigerant capacity of 223 J/kg was found in the sample with δ = 0, and in all cases the refrigerant capacities of the thin films under study were found to exceed that reported for bulk EuO. Adjusting the oxygen content was shown to produce tablelike magnetocaloric effects, desirable for ideal Ericsson-cycle magnetic refrigeration. These films are thus excellent candidates for small-scale magnetic cooling technology in the liquid nitrogen temperature range.

36 MATERIALS SCIENCE↗

STRESS AND FATIGUE ANALYSIS OF AIR-TO-REFRIGERANT HEAT EXCHANGERS WITH NON-ROUND TUBE SHAPES

Air-to-refrigerant heat exchangers are fundamental components in Heating, Ventilation, Air Conditioning, and Refrigeration (HVAC&R) systems. Recent research has shown that heat exchangers utilizing small hydraulic diameter, non-round, shape-optimized tubes to be promising next design update. Such tubes can improve performance, reduce material and lower refrigerant charge. However, such tube designs may be more susceptible to fatigue issues. Therefore, stress and fatigue analyses of such heat exchangers are critical to ensure structural integrity, reliability, and manufacturability. In the present work, a mechanical model is developed to obtain the stress distributions in heat exchangers with round, ellipse, and airfoil-shaped tubes. The results indicate that under 3.45 MPa internal pressure, the maximum stresses don't surpass 190 MPa.

Zhang, Mingkan↗

Development and Evaluation of a Sandia Cooler-based Refrigerator Condenser

This report describes the first design of a refrigerator condenser using the Sandia Cooler, i.e. air - bearing supported rotating heat - sink impeller. The project included baseline performance testing of a residential refrigerator, analysis and design development of a Sandia Cooler condenser assembly including a spiral channel baseplate, and performance measurement and validation of this condenser system as incorporated into the residential refrigerator. Comparable performance was achieved in a 60% smaller volume package. The improved modeling parameters can now be used to guide more optimized designs and more accurately predict performance.

42 ENGINEERING↗

Alternative Refrigerant Evaluation for High-Ambient Temperature Environments: R-22 and R-410A Alternatives for Mini-Split Air Conditioners

The Oak Ridge National Laboratory (ORNL) High-Ambient Temperature Testing Program for Low-GWP Refrigerants aims to develop an understanding of the performance of low-Global Warming Potential (low-GWP) alternatives to Hydrochlorofluorocarbon (HCFC) and Hydrofluorocarbon (HFC) refrigerants in mini-split air conditioners under high ambient temperature conditions. This interim working paper describes the parties involved, the alternative refrigerants selection process, the test procedures, and the preliminary results.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Benefits of Leapfrogging to Superefficiency and Low Global Warming Potential Refrigerants in Room Air Conditioning

Hydrofluorocarbons (HFCs) emitted from uses such as refrigerants and thermal insulating foam, are now the fastest growing greenhouse gases (GHGs), with global warming potentials (GWP) thousands of times higher than carbon dioxide (CO2). Because of the short lifetime of these molecules in the atmosphere,1 mitigating the amount of these short-lived climate pollutants (SLCPs) provides a faster path to climate change mitigation than control of CO2 alone. This has led to proposals from Africa, Europe, India, Island States, and North America to amend the Montreal Protocol on Substances that Deplete the Ozone Layer (Montreal Protocol) to phase-down high-GWP HFCs. Simultaneously, energy efficiency market transformation programs such as standards, labeling and incentive programs are endeavoring to improve the energy efficiency for refrigeration and air conditioning equipment to provide life cycle cost, energy, GHG, and peak load savings. In this paper we provide an estimate of the magnitude of such GHG and peak electric load savings potential, for room air conditioning, if the refrigerant transition and energy efficiency improvement policies are implemented either separately or in parallel.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Design of a Dry Dilution Refrigerator for MMC Gamma Detector Arrays

The goal of this LCP is to develop an ultra-high resolution gamma detector based on magnetic microcalorimeters (MMCs) for accurate non-destructive analysis (NDA) of nuclear materials. For highest energy resolution, we will introduce erbium-doped silver (Ag:Er) as a novel sensor material to replace current Au:Er sensors. The detector sensitivity will be increased by developing arrays of 32 Ag:Er pixels read out by 16 SQUID preamplifiers. MMC detectors require operating temperatures of ~15 mK and thus the use of a dilution refrigerator, and the desire for user-friendly operation without cryogenic liquids requires that this refrigerator use pulse-tube pre-cooling to ~4 K. For long-term reliability, we intend to re-design the heat switch that is needed to apply the magnetizing current to the Ag:Er sensor and that used to fail in earlier designs after months of operation. A cryogenic Compton veto will be installed to reduce the spectral background of the MMC, especially at low energies where ultra-high energy resolution is most important. The goals for FY16 were 1) to purchase a liquid-cryogen-free dilution refrigerator and adapt it for MMC operation, and 2) to fabricate Ag:Er-based MMC γ-detectors with improved performance and optimize their response. This report discusses the design of the instruments, and progress in MMC detector fabrication. Details of the MMC fabrication have been discussed in an April 2016 report to DOE.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Max Tech Efficiency Electric HPWH with low-GWP Halogenated Refrigerant

A scoping-level analysis was conducted to determine the maximum performance of an electric heat pump water heater (HPWH) with low GWP refrigerants (hydroflouroolefins (HFO), hydrofluorocarbons (HFC), and blends). A baseline heat pump water heater (GE GeoSpring) deploying R-134a was analyzed first using the DOE/ORNL Heat Pump Design Model (HPDM) modeling tool. The model was calibrated using experimental data to match the water temperature stratification in tank, first hour rating, energy factor and coefficient of performance. A CFD modeling tool was used to further refine the HPDM tank model. After calibration, the model was used to simulate the performance of alternative refrigerants. The parametric analysis concluded that by appropriate selection of equipment size and condenser tube wrap configuration the overall performance of emerging low GWP refrigerants for HPWH application not only exceed the Energy Star Energy Factor criteria i.e. 2.20, but is also comparable to some of the most efficient products in the market.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Feasibility analysis of a Commercial HPWH with CO 2 Refrigerant

A scoping-level analysis has conducted to establish the feasibility of using CO 2 as refrigerant for a commercial heat pump water heater (HPWH) for U.S. applications. The DOE/ORNL Heat Pump Design Model (HPDM) modeling tool was used for the assessment with data from a Japanese heat pump water heater (Sanden) using CO 2 as refrigerant for calibration. A CFD modeling tool was used to further refine the HPDM tank model. After calibration, the model was used to simulate the performance of commercial HPWHs using CO 2 and R-134a (baseline). The parametric analysis concluded that compressor discharge pressure and water temperature stratification are critical parameters for the system. For comparable performance the compressor size and water-heater size can be significantly different for R-134 and CO 2 HPWHs. The proposed design deploying a gas-cooler configuration not only exceeds the Energy Star Energy Factor criteria i.e. 2.20, but is also comparable to some of the most efficient products in the market using conventional refrigerants.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Extending ORNL HPDM Capabilities for Design and Optimization of New Refrigerant Blends – FY19 1st Quarterly Milestone Report: Development of Heat Pump System Models (Space Heating) for HFO Blends

We recently published numerous heat pump system models at the HPDM website, in the category of “Space Heating”. The published system configurations include single-stage heat pumps using TXV for expansion or a short-tube fixed-orifice coupled with a suction line accumulator, a two-stage heat pump system putting two compressors in series, single state heat pump using two parallel compressors (tandem), vapor injection systems with a vapor injection compressor coupled with an intermediate economizer or a flash tank. These configurations should cover all the residential heat pump products on the market. Additionally, to accelerate the refrigerant transition and make thousands of existing compressor maps reusable by the new refrigerants, ORNL created a mathematical approach to scale typical vapor injection compressor maps, developed from one baseline refrigerant to be used by the new HFO refrigerants/blends.

42 ENGINEERING↗

Cost-Benefit Analysis for Energy Efficient Refrigerators and Freezers in Uganda

Refrigeration appliances and equipment available on the market are manufactured with a wide range of energy performance. The goal of this report is to perform a cost-benefit analysis, providing policy recommendations to develop standards and labels for refrigerators in Uganda: in particular, an analysis of the cost-effectiveness of adopting the UNEP U4E MRG for refrigerators given the local context in Uganda.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Aleut Community Store Refrigeration Efficiency Retrofit with Heat Recovery (Final Report)

The Project Goal is to improve the energy efficiency of the Aleut Community Store by installing deep energy retrofits. Project Objectives are: 1) Replace refrigeration equipment and display cases with an energy efficient refrigeration system and energy efficient refrigeration display cases; utilize waste heat to heat the building; and 2) Lower cost of energy and maintenance for Aleut Community Store by $44,385 (energy and maintenance)

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Driving the Shift to Energy-Efficient and Climate-Responsible Commercial Refrigeration Equipment in Chile

This report provides an overview of global and Chile-specific market trends, technological advancements, and policy developments related to commercial refrigeration equipment, with an emphasis on refrigerated display cabinets. Section 2 examines CRE market trends at the global and Chilean levels. Section 3 presents CRE energy consumption and the latest technological options for improving energy performance. It also discusses low global warming potential (GWP)1 refrigerant options for CRE. Section 4 provides a cost-effectiveness analysis. Section 5 reviews other regional energy efficiency standards and labeling programs and offers potential standard requirements for Chile. Section 6 concludes the report by summarizing key findings and conclusions. Finally, Appendix A provides detailed guidelines intended as a starting point to inform policies and programmes.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Ultra-clear Aerogels for Insulated Glass in Refrigeration Doors (CRADA Final Report)

Display refrigerators commonly employ glass doors to provide product visibility; however, these doors exhibit significantly poorer thermal insulation than solid doors, resulting in increased heat transfer and higher energy consumption. To address this limitation, this project investigated the use of silica aerogel as a transparent insulating medium for refrigerator glass doors, with the objective of enhancing thermal performance without compromising visual clarity. In Phase I of the project, we assessed the feasibility of silica aerogel insulation through laboratory and full-scale studies, including material characterization, durability testing, and heat transfer measurements, along with the development and performance evaluation of prototype glass doors under realistic operating conditions. In Phase II, the project focused on scaling the technology toward practical deployment. This included scaling up the manufacturing process to achieve a surface area roughly 20 times larger for commercial applications, developing full-scale prototypes that integrated silica aerogel into standard display refrigerator doors, and conducting field evaluations to assess thermal performance, energy savings, and operational durability under real-world conditions.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Heat Transfer, Refrigeration and Heat Pumps

The Special Issue entitled “Heat Transfer, Refrigeration and heat Pumps” accepted papers covering a wide range of topics related to heat pumps, thermal energy storage, and low-Global Warming Potential (GWP) alternative refrigerants. Heat pumps play a vital role in providing space conditioning and water heating while utilizing the energy of the environment. Since heat pumps use renewable thermal energy from the environs to provide the desired utility, they contribute to the portfolio of technologies that mitigate carbon footprint. The heat pump may be considered a truly renewable technology if the electricity it uses comes entirely from a renewable source. More accurately, a heat pump is a “low carbon technology”. These perspectives make heat pumps an indispensable option for the future in order to reduce the nocuous human impact on the environment. More efficient heat pumping technologies are being developed for the residential, commercial, and industrial sectors of the economy. Another R&D thrust is heat pumps for cold climates. Hardware components, use of low-GWP refrigerants, and identification of systemic inefficiencies are active research areas. This article is a synopsis of the papers submitted to the Special Issue.

42 ENGINEERING↗

Mathematical analysis of a Vuilleumier refrigerator.

A comprehensive analysis of the Vuilleumier refrigerator was conducted. This analysis includes the effects of nonisothermal gas heat addition and rejection, hot and cold regenerator inefficiencies, conduction losses, and gas leakage losses. A computer program was written which solves the equations resulting from the analysis. The program calculates internal pressures, temperatures, and gas flow rates as functions of refrigerator crank angle, as well as overall refrigerator cooling load and power input. Comparisons between the program results and available data show good agreement, with a marked improvement over the predictions of the ideal model.

Sherman, A.↗

Space shuttle orbiter mechanical refrigeration system

A radiator/condenser was designed which is efficient in both condensation (refrigeration) and liquid phase (radiator) operating modes, including switchover from the refrigeration mode to the radiator mode and vice versa. A method for predicting the pressure drop of a condensing two-phase flow in zero-gravity was developed along with a method for predicting the flow regime which would prevail along the condensation path. The hybrid refrigeration system was assembled with the two radiator/condenser panels installed in a space environment simulator. The system was tested under both atmospheric and vacuum conditions. Results of the tests are presented.

Williams, J. L.↗