Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “Building Stock”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 343 records · Page 19

ComStock Measure Documentation: Ideal Thermal Air Loads

This study provides hypothetical thermal heating and cooling loads for ComStock models representing the U.S. commercial building stock. This measure scenario removes all HVAC models from the baseline ComStock building model and instead uses "ideal air" to meet loads. "Ideal air" can be thought of as an HVAC unit that mixes air at the zone exhaust condition with the specified amount of outdoor air, and then adds or removes heat and moisture at 100% efficiency to produce a supply air stream at the specified conditions. The resulting ideal thermal loads are represented under the "district" fuel type for both heating and cooling and can be found in both annual and timeseries results in the ComStock public dataset. This measure scenario does not represent any real technology or improvement, but rather, serves as a resource for thermal heating and cooling loads for buildings.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Conditional distribution estimation of building characteristics with diffusion models for urban energy modeling

Understanding current energy consumption behavior in communities is critical for informing future energy use decisions and enabling efficient energy management. Urban energy models, which are used to simulate these energy use patterns, require large datasets with detailed building characteristics for accurate outcomes. However, such detailed characteristics at the individual building level are often unknown and costly to acquire, or unavailable. Through this work, we propose using a generative modeling approach to generate realistic building attributes to fill in the data gaps and finally provide complete characteristics as inputs to energy models. Our model learns complex, building-level patterns from training on a large-scale residential building stock model containing 2.2 million buildings. We employ a tabular diffusion-based framework that is designed to handle heterogeneous (discrete and continuous) features in tabular building data, such as occupancy, floor area, heating, cooling, and other equipment details. We develop a capability for conditional diffusion, enabling the imputation of missing building characteristics conditioned on known attributes. We conduct a comprehensive validation of our conditional diffusion model, firstly by comparing the generated conditional distributions against the underlying data distribution, and secondly, by performing a case study for a Baltimore residential region, showing the practical utility of our approach. Our work is one of the first to demonstrate the potential of generative modeling to accelerate building energy modeling workflows.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Systems Packages for Washington State Building Performance Standard Incentive Program: Phase 1 Analysis

Starting in 2026 Washington State building performance standards will come into effect that require commercial buildings larger than 50,000 sf to meet site energy use intensity targets. To support a state incentive program designed to encourage building owners to start complying early, we characterized the building stock energy use of 11 building types, analyzed 43 energy upgrade measures, and developed seven packages of energy upgrade measures using the ComStock energy analysis tool. Each energy upgrade package included from 4 to 17 energy measures consisting of lighting, HVAC, and envelope upgrades. Package savings were calculated for four priority building types using a sample of 35,000 buildings characterized by four building area bins, three climate zones, and two county types (urban and rural). Of the 28 package and building type combinations analyzed, 17 (61%) met or exceeded program energy savings targets and two packages met targets for all four building types.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

An Energy Calculator for Simple Commercial Buildings

According to the EIA, simple commercial buildings account for 97% of total commercial building stock. However, most simple commercial buildings for example small- to mid-sized offices, retail, schools and warehouses do not benefit from the data-driven decision-making capabilities of whole-building energy modeling. The high cost of custom modeling limits the use of energy modeling of simple buildings for new construction or retrofit measures. Lack of tools providing helpful information on interactive savings estimates creates difficulties in meeting aggressive decarbonization and energy efficiency goals for simple building designers and utility program managers. This paper reviews a beta phase Simple Building Calculator with the ability to generate relatively accurate and interactive modeling results based on a limited but robust set of inputs. It can evaluate whole-building or single measure savings in new or existing buildings, compare measure package choices, or provide simplified performance modeling for energy codes and utility incentives. The tool combines physical (annual whole building prototype simulation) and statistical modeling techniques to predict annual energy performance. It supports a variety of building characteristics for envelope, HVAC, and lighting with parameters ranging from vintage to max tech configurations, as well as support for single-zone and simple multi-zone HVAC systems. The Simple Building Calculator was designed to provide immediate feedback for otherwise computationally intensive tasks like measure comparison, development of multiple measure package combinations, or verification that measures meet efficiency targets—all with the goal of providing a tool for quick annual energy simulation of simple commercial buildings.

Hart, Reid↗

Long-Term Assessment of Commercial Building Energy and Carbon Emissions in the Northwestern Region Under Future Weather Trend

The future climate significantly impacts building performance and increases uncertainties in energy simulations. A rising temperature trend is expected to heighten cooling loads during summer and result in more carbon emissions. Understanding the impact of future climate on building performance is significant for policymakers to make informed decisions. Building retrofit measures can improve building energy efficiency and reduce operational carbon emissions, yet their effects under future climate conditions have not been fully investigated so far. Thus, we proposed an assessment methodology for evaluating long-term energy consumption and operational carbon reduction potential using a building stock dataset. For this study, commercial buildings in the northwestern (NW) region were utilized to assess the impacts of future climate and building retrofit. In addition, we selected Montana with a cold and dry climate as an example to analyze and discuss the carbon emission reduction potential in buildings. The main findings are: (1) Under future climate trends, changes in energy use intensity (EUI) will fluctuate due to variations in heating and cooling degree-days (HDDs and CDDs) and increasing HDDs will lead to increasing EUI. (2) After applying annual building retrofitting, the long-term EUI reduction potential of buildings in the NW region will decrease with the increasing retrofitting degree, and the short-term EUI reduction potential will be impacted by the change of heating and cooling degree days. (3) In Montana, the long-term carbon intensity reduction potential of retrofitted buildings will decrease under future climate trends with the increasing renewable energy penetration.

building energy modeling↗

End-Use Savings Shapes Measure Documentation: Heat Pump Rooftop Units With Exhaust Air Energy Recovery

This technical report documents the Advanced Rooftop Unit Control End Use Savings Shapes (EUSS) measure, including providing a description of the technology, modeling methods, and the energy savings calculated from applying the measure to applicable across the US commercial building stock using ComStock to quantify its potential. This measure replaces gas furnace and electric resistance rooftop units with high-efficiency variable speed heat pump rooftop units (HP-RTU) that include exhaust air heat or energy recovery. The measure uses the same assumptions and technology as the variable speed HP-RTU measure from EUSS 2023 release 1 but adds energy recovery to precondition outdoor ventilation air to reduce HVAC loads. The HP-RTU compressor lockout temperature is modeled as 0 degrees Fahrenheit; below this temperature, the heat pump is set to shut off. The unit is sized based on the design cooling loads, with backup electric resistance heating addressing any remaining loads including heating hours below the compressor lockout temperature when there is no heat pump heating.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

GHG policy impacts for Seattle’s buildings: targets, timing, and scope

Many US cities are addressing climate change by setting goals to reduce their greenhouse gas (GHG) emissions by a specified amount within a specified time period. In order to achieve these goals, reducing emissions from existing buildings is crucial. Many cities are passing legislation to target existing buildings through benchmarking, auditing, retuning, or energy or emissions performance standards. As cities design legislation, they must consider the timing of the policies, how to prioritize building types and sizes, and how these design decisions will impact the city’s emissions. This paper addresses these questions for one particular US city: Seattle, Washington. A model of Seattle’s building stock was created with benchmarking and tax assessor data. It was then used to predict GHG emissions reductions due to different policy implementations for existing commercial and multifamily buildings. Key findings are: (1) the proposed emissions policy is expected to reduce cumulative emissions from buildings by 19% between 2020 and 2050; (2) delaying the implementation of the policy by five years could limit savings to 12%; and (3) including smaller buildings in the policy could increase savings to 34%. The lessons learned and how this can be used by other cities are discussed.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

ComStock Measure Documentation: Photovoltaics With 40% Rooftop Coverage

This study investigates the impact of adding 40% rooftop coverage of photovoltaics to the U.S. commercial building stock. Panels are modeled as higher performance with 21% rated efficiency, 96% inverter efficiency, 1.10 DC/AC ratio,14% system losses, and azimuth/tilt angles that vary by location. Total panel area is modeled at 40% of the roof area for each model. Total rated PV power for a building is based on the calculated total panel area and the assumed efficiency of 21%. This measure is applied to all buildings modeled in ComStock.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Automatic and rapid calibration of urban building energy models by learning from energy performance database

Urban building energy modeling (UBEM) is attracting increasing attention in the energy modeling filed. Unlike modeling a single building using detailed building systems information, UBEM generally uses limited high-level building stock data to infer default assumptions about building characteristics and operations. Additionally, this practice inherently brings uncertainty to UBEM. This study introduced a novel method of automatic and rapid calibration of UBEM based on the annual electricity and natural gas energy use data by learning the correlations between crucial model input parameters and the building energy use from the reference building models. A case study was presented to calibrate 72 large office buildings built before 1978 in San Francisco. Seventeen model parameters were selected and Monte Carlo sampling was used to create 1000 samples that reasonably represent the parameter space. Then 1000 simulations were performed for the reference building model to create an energy performance database. The results showed that by learning from the energy performance database, it took less than four simulation runs on average to calibrate a building model. After the calibration, the distributions of each parameter were obtained to replace their single predefined default values. For example, the default lighting power density of 21.39 W/m 2 was calibrated to be 7.50 W/m 2 on average. The case study successfully demonstrated the effectiveness of the novel calibration method for UBEM in the mild climate. The method will be further tested in future for other climate zones and other building types.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Experimental investigation on thermal inertia characterization of commercial buildings for demand response

Characterizing the thermal inertia of commercial buildings is of great importance in quantifying demand flexibility. Experimental tests can be used to investigate the thermal inertia of commercial buildings. However, existing studies tend to be qualitative and have limited scope. In this study, a comprehensive field test has been performed to assess the thermal inertia of commercial buildings. In this field test, six buildings are selected with different sizes, vintages, and types of heating, ventilation, and air conditioning (HVAC) systems to represent the majority of the U.S. commercial building stock. We quantify the thermal inertia with building operation data collected under various thermostat excitation signals. We then studied the relationship between thermal inertia and intrinsic properties, such as floor area, HVAC system, etc., as well as the operation condition indicators such as outdoor air temperature, zone temperature, and occupancy. The testing results indicate that the median values of the normalized charge response time and the normalized discharge response time of the five buildings are 1~5 hr/ °C and -5~-1 hr/ °C, respectively. The results also show that the thermal inertia of commercial buildings may be sensitive to the HVAC system type but not the floor area or location of zones, i.e., core vs. perimeter. Finally, our results suggest that the relationships between the charging/discharging normalized response time and the zone/outdoor temperature may vary among zones and be highly nonlinear.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Addressing the Split Incentive Challenge for Enhanced Solar Adoption in Multifamily Rental Properties [Abstract]

The split incentive problem is particularly pronounced in rental markets, where landlords prioritize investments that directly increase property value or rental income. Since energy savings from solar photovoltaic (PV) systems primarily benefit tenants, landlords may perceive little return on investment unless mechanisms exist to recapture some of the financial gains. The primary objective of this project is to develop a publicly available, web-based tool to analyze the U.S. Department of Energy’s ResStock database, which models the U.S. residential building stock. The tool allows users to filter buildings by location, type, HVAC system, square footage, and other characteristics, and outputs typical electric load profiles. By leveraging location-specific electric load data, Fram Energy aims to advance business strategies that address the split incentive barrier and promote the adoption of solar PV installations in rental properties. In addition, a machine learning model will be developed to weigh the marginal contribution of building features across the dataset in predicting electricity demand, supporting guided decision making in forecasting electric load profiles. Lastly, based on each building’s location, load profile, and utility’s electricity rate, an optimized solar photovoltaic array and battery energy storage system will be sized to provide energy arbitrage opportunities.

14 SOLAR ENERGY↗

ResStock Measure Documentation: Cold Climate Air-Source Heat Pump

This report is part of series describing a variety of different ResStock™ measures. "Measures" refers to energy efficiency retrofits that can be applied to buildings during modeling. This documentation covers the "Cold Climate Air-Source Heat Pump" measure upgrade methodology and briefly discusses key results. All results can be accessed on the ResStock Open Energy Data Initiative "End-Use Load Profiles for the U.S. Building Stock" data lake and on the data viewer at resstock.nlr.gov.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

ComStock Measure Scenario Documentation: Laboratory-Informed Modeling of Standard Performance Heat Pump Rooftop Units

This measure scenario replaces gas and electric resistance RTUs in the U.S. commercial building stock with standard efficiency commercial off the shelf heat pump rooftop units. This study uses performance data informed by NREL laboratory testing of a standard efficiency 7.5-ton heat pump RTU. This is the key distinction between this measure scenario and a similar ComStock measure scenario - Standard Performance Heat Pump Rooftop Units - that uses published manufacturer data tables to inform performance. These two scenarios are compared in this report.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A rapid embodied carbon assessment tool for priority materials

Embodied carbon limits within building materials are a driving factor in global trade, generating new research and analysis tools in industry. These product assessments, which require utilizing life-cycle assessment (LCA) across broad supply chains, can be expensive, time and data-intensive, and subject to significant variations. Existing methods and tools, such as specific environmental product declarations, typically do not capture these variations and dynamics in supply and manufacturing. Moreover, models and tools must enable stakeholders to assess customized supply chains and future scenarios. In this study, we present the Rapid Embodied Carbon Assessment and Target-setting for Emissions-intensive Materials (REDuCE) tool for building materials. We developed a tool that allows users to select production technologies, transportation mode and distances, concrete carbonation, fuel sources, and regional electricity mixes to supply customization for cement and concrete produced and consumed in California. We generated and integrated a material demand model using residential building stock projections. We provide the user with a wide range of mitigation alternatives through low-carbon production pathways, material use efficiency, transportation modes, and projected electricity grid mixes. In a case study application through four mitigation scenarios, we find emission savings up to 80% by maximizing user mitigation alternatives, primarily driven by reductions in material use intensities. This work represents a foundation for expanding LCA and embodied carbon tools to better enable stakeholders to rapidly and accurately assess customized supply chains while meeting trade requirements.

building materials↗

Analysis of the Financial Impacts of Building Performance Standard Penalties on Commercial Buildings in Aurora, Colorado

Buildings are responsible for 30% of total energy consumption worldwide. To address building energy, jurisdictions in the USA have enacted Building Performance Standards (BPS) legislation. The objective of BPS is to reduce energy consumption in buildings, thereby reducing the energy burden on utility infrastructure and other externalities. This is accomplished by setting mandatory energy use limits coupled with penalties for exceeding those limits. One of the key questions in BPS policymaking is how these penalties might impact the finances of building owners and tenants. This paper presents an analysis of BPS penalties in Aurora, Colorado, specifically targeting buildings impacted by the adopted statewide BPS legislation. Several BPS penalty structures were applied to the affected building stock in Aurora, and the potential impacts on building owner returns and tenant rents were estimated. The results show that for some combinations of building types and penalty structures, potential rent increases due to penalties could match or exceed typical yearly rent increases. The results also show that in most cases, for Aurora, there was no statistically significant difference in impact between buildings located in under-resourced and well-resourced areas.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

CityBES v2021

City Buildings, Energy, and Sustainability (CityBES) is a web-based data and computing platform, focusing on energy modeling and analysis of a city's building stock to support district or city-scale building energy efficiency programs. CityBES uses an international open data standard, CityGML, to represent and exchange 3D city models. CityBES employs EnergyPlus to simulate building energy use and savings from energy efficient retrofits. Other CityBES features include energy benchmarking, district heating and cooling system modeling, rooftop PV analysis, building performance visualization, heat resilience modeling, as well as urban scale mapping of microclimate and heat vulnerability at census tract level. Different from other tools, CityBES uses integrated open and standard 3D city building data and models each individual building using EnergyPlus. CityBES can be used by urban planners, city energy managers, building owners, utilities, energy consultants and researchers.

Hong, Tianzhen↗

Envelope-driven comfort risk in residential demand response

Residential demand response (DR) is a valuable resource for grid reliability, but remains challenging because the highly heterogeneous residential building stock leads to widely varying and hard-to-predict load and comfort responses during DR events. Although prior research has estimated the technical potential of DR-capable technologies for achieving energy demand savings, little is known about how they affect thermal comfort. In particular, it remains unclear how indoor thermal conditions due to DR depend on the thermal envelope characteristics of the housing stock. To address this gap, this study provides a systematic, location-specific assessment of indoor thermal performance during DR-events across the US housing stock using both typical DR weather data and detailed building metadata. We evaluate how envelope characteristics influence indoor temperatures during realistic simulated summer and winter DR events across 37 US locations, applying both temperature threshold and rate of temperature change criteria to estimate region-level probabilities of discomfort. Additionally, we show the impact of distinct weather patterns that intensify or abate thermal stress on comfort outcomes. Results show a near-universal overheating risk in summer DR events, where comfort outcomes are strongly influenced by rapid risk of comfort violations. In contrast, overall winter DR discomfort risk is lower, risk escalation is more gradual and shows greater sensitivity to event duration. These findings offer a data-driven quantification of comfort risk across diverse climates and building envelopes, demonstrating the need for region-specific DR scheduling and discomfort mitigation strategies tailored to local weather patterns and the performance of existing residential buildings.

Demand response↗

Modeling of transient conduction in building envelope assemblies: A review

As buildings age, retrofits are becoming an increasingly important topic for the ever-growing and aging existing building stock. To compare designs or evaluate in-service building envelopes, thermal modeling is utilized to evaluate the thermal performance of envelope assemblies; however, it can be difficult to model the thermal performance of as-built assemblies due to degradation or missing documentation. To address this issue, inverse modeling can be applied to infer the properties of as-built envelope assemblies. This paper presents a review of the literature and published methods to model and infer the transient conductive performance of building envelopes. This review serves as a survey of existing transient conduction algorithms to evaluate performance, computational speed, and relevance for inverse modeling applications. In addition to the literature review, this work also evaluates the computational performance of the most prevalent transient conduction algorithms against the ASHRAE 1052RP toolkit to assess inverse modeling potential. This methodology serves as a foundation for future research to characterize the transient thermal performance of as-built building envelope assemblies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗