Digital Twin for Self-Security of Smart Inverters

Smart inverters connected to a communication network are susceptible to man-in-the-middle attacks. In this paper, a self-security approach is implemented using the digital twin concept for smart inverters. The digital twin is formed using the inverter’s normal operating region and the inverter’s dynamic model. Then, the incoming setpoints are autonomously examined using the digital twin, and only the safe setpoints are engaged to the inverter’s local controller. This paper demonstrates how the inverter’s normal operating region and dynamic model are formed. In particular, the normal operation region is experimentally verified by changing the P and Q setpoints engaged to the local controller, using a laboratory setup including a three-phase 3-kVA SiC-MOSFET inverter and a 12-kW NHR 9410 regenerative power grid emulator. The results demonstrate that the self-security technique can potentially protect inverters from man-in-the-middle attacks by examining the incoming commands (new setpoints) using the inverter’s digital twin before engaging the setpoints to the local controller.

Hossen, Tareq↗

How Fisheries Biologists Can Facilitate the Clean Energy Transition

Abstract Fisheries and aquatic biologists play a critical role in creating environmentally protective hydropower flow requirements that govern flow timing, frequency, magnitude, and rate of change. Hydropower's role in the U.S. electrical grid is expected to evolve in response to increased wind and solar generation as hydropower will be called upon to quickly ramp up and down in response to changes in wind and solar generation. For this reason, hydropower is expected to have increased value as fossil generation is phased out, even as rapid flow fluctuations linked with hydropower flexibility may strand fish, alter habitat, and create unsafe recreational conditions. We face a new challenge in facilitating the renewable energy transition—designing environmental flow requirements that protect against the impacts of flow fluctuations while allowing adequate hydropower flexibility to support a stable grid. In this paper, we discuss hydropower environmental flow requirements, operational flexibility, and electrical grid stability, their potential interactions, and opportunities to align environmental and power system needs to support healthy ecosystems, multiple water uses, and decarbonization of the electric grid.

13 HYDRO ENERGY↗

Applications of Solid-State Transformers for Electric Power Grid HEMP/GMD Resilience

A high-altitude electromagnetic pulse (HEMP) or geomagnetic disturbance (GMD) can disrupt power grids by inducing low-frequency common-mode (CM) currents. When these currents flow through grounded transformers, they can bias the magnetic core, driving it into saturation and reducing performance or damaging equipment. This work presents a solid-state transformer (SST) to replace vulnerable assets and improve grid resilience. The paper reviews half-cycle saturation in conventional transformers, then describes an SST architecture that neutralizes and redirects CM currents during HEMP/GMD events. A prototype SST is built and validated, demonstrating stable CM-disturbance operation and protection of nearby transformers. Finally, large-scale simulations show how coordinated SST deployment mitigates CM disturbances and strengthens overall grid resilience.

four-leg inverter↗

Design, Control, and Protection of a 13.2 kV, 1 MVA Solid State Transformer for Electric Vehicle Extreme Fast Charging Station

In this article, a medium-voltage (MV) ac-dc solid state transformer (SST) for electric vehicle (EV) extreme fast charging (XFC) station is proposed. The SST adopts a cascaded H-bridge (CHB)-based structure where the active front end (AFE) power stages are connected in input-series followed by dual active bridge (DAB) converters connected in an output-parallel configuration providing galvanic isolation through a high-frequency transformer (HFT). The SST is rated for 1 MVA and connects directly to a three-phase 13.2 kV MV ac grid through ac switchgear and outputs 750-V dc. At the dc bus, several dc/dc converters are connected, each of which can charge an EV based on its battery capacity. A novel decentralized control architecture of the SST is adopted in this work which simplifies the MV dc link voltage and module-level power balancing. In addition, the local and central protection designs of the SST are presented which identify and respond to the internal fault of the system. Finally, the experimental validations of the SST hardware prototype are presented up to the rated voltage. Furthermore, this article details the design and implementation of the MV SST addressing the challenges of an isolated MV class power converter for connecting directly to the MV ac grid with unique controller architecture, distributed protection framework, and SST constructional features.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Fault Contribution of Grid-Following and Grid-Forming Inverters Considering Generic Inverter Controls and Ride-through Requirements

Gradual transformation of the synchronous generator (SG)-dominated power systems to inverter-based resource (IBR)-dominated power systems is bringing new challenges regarding power system protection. Increasing IBR’s penetration will reduce the reliability of protection coordination, originally developed for SG-dominated power systems, potentially leading to less accurate calculation or even mis-operation. Thus, new protection schemes compatible with IBR-dominated power systems should be established. Prior to establishing the protection schemes, research on the fault contribution of generic IBR models should be conducted considering interconnection requirements. This paper conducts fault current contribution analysis of generic grid-following (GFL) and grid-forming (GFM) inverters considering interconnection requirements using an electromagnetic transient (EMT) simulation tool. To do this, EMT-based generic GFL models have been developed with the ride-through requirements from IEEE-1547 standards. In addition, the major functions of the generic models are explained. Then, the fault current analysis was conducted using GFL and GFM inverters in a single-inverter-infinite-bus system and a modified IEEE 34-node system considering different grid, fault, inverter control parameters.

Kim, Jinho [BATTELLE (PACIFIC NW LAB)]↗

Cyber risk assessment and investment optimization using game theory and ML-based anomaly detection and mitigation for wide-area control in smart grids

The electric power grid is increasingly becoming susceptible to cyber attacks that exploit vulnerabilities in the smart grid control, information, and physical layers. Successful cyber attacks can have catastrophic impacts on the social and economic well-being of any nation all over the globe. It has, thus, become imperative to secure the smart grid against such adversarial actions to ensure stable, secure, and reliable operation of the grid. The existing research and industry practices prove to be inadequate in terms of providing pragmatic and effective defense methodologies and measures for long-term cybersecurity planning and real-time cybersecurity for grid operation. For example, existing works lack models that incorporate uncertain behavior of cyber-attackers and pragmatic defense measures for cyber risk assessment and cybersecurity investment optimization which often provide unreliable and strictly qualitative solutions to these problems. At the same time, with the growing number of cyber incidents in the grid, there still exists a need to develop attack-resilient algorithms for wide-area monitoring, protection, and control (WAMPAC) applications like the wide-area voltage control systems (WAVCS) for Flexible AC Transmissions Systems (FACTS) that lack in scalable and feasible solutions from the cybersecurity perspective. This dissertation proposes novel models and methodologies for: (1) Cybersecurity planning, and (2) Cybersecurity for system operation. The cybersecurity planning is achieved through cyber risk assessment and cybersecurity resource investment optimization for long-term cybersecurity of the grid using game theory and attack-defense trees. Cybersecurity for system operation consists of development of cyber anomaly detection and mitigation algorithms for flexible AC transmission system (FACTS) controller-based wide-area voltage control systems (WAVCS) using machine learning (ML), and software defined networking-based moving target defense network routing for achieving real-time cyber-physical security for grid operations. This is followed by hardware-in-the-loop (HIL) implementation and evaluation of these attack prevention, detection, and mitigation algorithms and methodologies showcasing their feasibility in a close to real-world environment. For cybersecurity planning, a novel approach involving a combination of game theory and attack defense trees (ADT) for optimal cybersecurity resource allocation in the smart grid is proposed. This methodology involves modeling of the cyber-physical smart grid substations as ADTs, defining attacker costs, defense costs, and attack probabilities for attack access points. Using game theoretical formulation, optimal defense strategies for the defender of the system to invest cybersecurity resources in the grid are obtained. Additionally, a game-theoretic framework is developed for quantitative cyber-physical risk assessment of the grid under a dynamically changing cyber threat space and uncertain behavior of cyber attackers which is further used to optimize investments in the smart grid's cybersecurity resources. The attacker, defender, and the smart grid system are modeled while incorporating attacker-stochasticity and federal guidelines for smart grid cybersecurity. This allows quantification of threat, vulnerabilities, and attack impact of the grid for quantitative risk assessment. The defender's budget to invest in the security resources in the grid is optimized based on the strategies leading to minimum system risk. The evaluation of the proposed solutions highlight the feasibility for practical implementation of these methodologies and algorithms in the smart grid, while taking the federal requirements and guidelines for smart grid security into consideration. For achieving cybersecurity for system operation, attack prevention, detection, and mitigation algorithms and methodologies are developed specifically for FACTS-based WAVCS. Anomaly detection and mitigation in the WAVCS are achieved using algorithms based on machine learning which involves offline training and testing of ML models with CPS datasets incorporating physics-based features that allow accurate distinction between system faults and cyber attacks. For attack prevention, a methodology based on software defined network (SDN)-based moving target defense (MTD) network routing is proposed that enables prevention of Denial of Service (DoS) type attacks on the smart grid communication system. Subsequently, these methodologies and algorithms are implemented and evaluated on an HIL testbed that allows for real-time attack prevention, detection, and mitigation of emulated cyber attacks on the WAVCS in a close to real-world environment. The results show highly accurate and efficient performance of the implemented algorithms and methodologies with the smart grid system operating within the NERC's system operation limits even in the presence of DoS and data integrity cyber attacks. This work opens up future research opportunities in other directions such as (1) Expanding cybersecurity planning methodologies to real-time cyber contingency analysis with different game formulations; and (2) Applying the cybersecurity for system operation algorithms to broader categories of wide-area control applications.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Implementing Admittance Relaying for Microgrid Protection

An earlier study evaluated issues with microgrid protection. This highlighted the difficulties with microgrid protection, which include: 1. lack of fault current from inverter-interfaced generation, 2. varying fault current between grid-connected and islanded modes, 3. potential for normally-meshed operation and 4. unbalanced operation due to single-phase loads. It is worth noting that not all microgrid designs will include all these challenges. For example, microgrids could choose to omit meshed operation. Previous work identified differential protection based on the discrete S-transform for line protection and admittance protection for load protection as possible solutions . However, some severe limitations were identified. This included the potential for blinding of the discrete S-transform protection when fault contribution on either end of the line is similar, and loss of protection selectivity for admittance protection in the case of upstream line-ground faults. This report investigates admittance protection as a solution for line and load protection in greater detail by comparing analytical and simulated results. Section 2 describes the protection schemes analyzed and the behavior of inverter-interfaced microgrids under faults in more detail. Section 3 derives sequence networks for the fault cases considered. Section 4 presents a transient model constructed to validate the impedances calculated from the sequence networks. Section 5 compares the results from the sequence networks and transient model. Last, Section 6 presents the conclusions of this study in terms of the suitability of admittance relaying for protection of inverter-interfaced microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Transient Stability-Enhancing Method for Grid-Forming Inverters Under Current Limiting

The primary controller of a grid-forming (GFM) inverter governs the internal reference voltage and angle, which enables the inverter to naturally synchronize and share power with the connected grid; however, during disturbances on the grid caused by, e.g., line faults, overloading, or frequency and phase shifts, a GFM inverter can be pushed into a current-limited operation to protect the device against thermal damage. This can lead to a windup of the internal reference frequency generated by the primary controller and cause a total loss of synchronism with the grid. Here, to make the primary controller of GFM inverters more robust against transient instability, this paper proposes a method that manipulates the reference signals governed by the primary controller by introducing the concept of fictitious power. The fictitious power counteracts the integrator windup in the primary controller, which enables the current-limited inverter to conceive a stable operating point. This method is benchmarked against five state-of-the-art GFM inverter stabilization methods to evaluate its stability-enhancing performance. Full-order electromagnetic-transient simulations and experimental results of a hardware inverter test setup validate the benefits of the method to improve the transient stability of GFM inverters in the face of grid disturbances.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Emulation and Adversarial Analysis of EV Charging Networks

In the effort of decarbonization and evolution of the modern electrical grid, electric vehicles (EVs) play a key part to transform the grid. However, due to the rapid adoption of EVs and the demand of the charging infrastructure required to power said EVs, risk of a cyber-attack may impose serious consequences. There is a need to analyze and protect the charging ecosystem infrastructure from cyber threats before it reaches wide-scale deployment. In an effort to secure vehicle to grid (V2G) communications, standardization is necessary for continued reliable system operation. The protocol ISO 15118 outlines controls and practices that should be implemented for secure vehicle to grid (V2G) communications. The standard is gaining momentum for American markets as the demand for EV infrastructure grows. The adoption of ISO 15118 in American markets poses several challenges: the deployment of a public key infrastructure (PKI) as outlined within the standard, interoperability of charging different EVs with chargers from different manufactures using the PKI, and scaling the ecosystem to meet the demand while managing risks. This project was created to understand potential cyber and scaling challenges of PKI for EV infrastructure through utilizing a series of emulated components mapping to what exists in the EV ecosystem today, and the components of the PKI that are under development. The key nodes within the emulation that are under development are: electric vehicle (EV), electric vehicle supply equipment (EVSE), charge network operator (CNO), certificate authority (CA), and online certificate status protocol (OCSP) that must all interact using secure and trusted communications. With these emulated components and utilizing orchestration methods to rapidly deploy and scale the components, the ability to analyze risks of the ecosystem and address gaps before the PKI ecosystem is fully deployed to production should yield a more robust and mature production charging infrastructure. Our approach will use a modular architecture of virtual machines within an orchestration platform and will target scales of 100s, 1000s, and 10,000s of entities interacting. The core research questions trying to be answered with this scope of work are: what are the impacts of a rogue CA, what are the risks of certificate revocation list (CRL) management, what is the value of OCSP stapling, what components are vulnerable to DOS attacks, and what test effective payloads may impact the components.

charging ecosystem↗

Reduced-Order Parameterized Short-Circuit Current Model of Inverter-Interfaced Distributed Generators

The short-circuit response of inverter-interfaced distributed generators (IIDGs) is not adequately represented in many conventional protection studies. This paper presents an in-depth analysis of IIDG behavior during grid faults and proposes a more accurate reduced-order parameterized short-circuit current (RPSC) model of inverters. Typical inverter components are thoroughly investigated to identify those that play dominant roles during faults. The paper shows that the current limiter is the dominant factor for the steady-state fault-current of inverter; while the inverter filter along with the severity of the voltage disturbance largely determine the initial transient spike of inverter fault current. The proposed model is low-order and can be used in large scale simulations. The parameters of the proposed RPSC model can be extracted from laboratory experiments without requiring proprietary manufacturer information. The proposed fault-current model is analogous to the well-known synchronous machine model that segregates the inverter fault current into subtransient, transient, and steady-state fault currents. Finally, experimental and simulation tests are presented to validate the model.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Inventory of Public Key Cryptography in US Electric Vehicle Charging

Electric vehicles (EVs) and charging infrastructure are networked systems, which employ high-level communications in support of charging and grid service decisions. Public key cryptography (PKC) underlies much of the security and privacy protections of the information exchange. We are entering a new epoch where quantum computing threats must be seriously considered. A sufficiently large quantum computer, so named Cryptographically Relevant Quantum Computer (QRQC), will be able to perform the mathematical operations to efficiently attack the underpinnings of traditional PKC, thus jeopardizing the digital foundations for trust, communications security, and data security. Estimates suggest a QRQC can break public key encryption and digital signatures in the manner of tens to hundreds of hours, compared to traditional computing that would demand more than 10 18 years in a brute force-style attack. A consensus belief of quantum theorists, quantum experimenters, and cryptographers suggest that the quantum threat will be likely realized in the next twenty years. To address the threat, post-quantum cryptography, which is cryptosystems that are designed to be secure against both traditional and quantum computing threats, must be adopted. Migration from traditional PKC to quantum-resilient cryptography is a global undertaking and likely represents the largest transition in computing history. The nascent state of EV public key infrastructure, combined with limited adoption of the vehicle secure charging features, presents an opportunity to establish a preference for quantum-resistant cryptography as a step on the migration path. Delays will stunt the efforts as rapidly accelerating EVs sales and huge infrastructure investments will create large growing bases of long-lived vehicles and infrastructure. Migration preparations can commence while NIST continues the process to standardize post-quantum cryptography (PQC), which are quantum-resilient algorithms designed to be secure against traditional and quantum computing threats. The first step in preparing EV charging is to identify the presence of traditional public key cryptography algorithms and applications. With this objective in mind, this report is intended to advise the vehicle manufacturers, charging station manufacturers, charging station operators, charge network providers and other EV charging stakeholders with information on traditional PKC application and the potential risks when PKC becomes insecure. This report, the first in a series of reports discussing the topics existing at the confluence of post-quantum cryptography adoption and EV charging, identifies traditional public key applications employed and identifies potential consequences of leaving EV charging infrastructure vulnerable to quantum computing. The focus remains squarely on the of EV charging and infrastructure with respect to PKC and is believed by the authors to complement the NIST SP 1800-38 Migration to Post-Quantum Cryptography. While the report is centered on infrastructure, there are implications to vehicles.

33 ADVANCED PROPULSION SYSTEMS↗

Assessment of Envelope- and Machine Learning-Based Electrical Fault Type Detection Algorithms for Electrical Distribution Grids

This study introduces envelope- and machine learning (ML)-based electrical fault type detection algorithms for electrical distribution grids, advancing beyond traditional logic-based methods. The proposed detection model involves three stages: anomaly area detection, ML-based fault presence detection, and ML-based fault type detection. Initially, an envelope-based detector identifying the anomaly region was improved to handle noisier power grid signals from meters. The second stage acts as a switch, detecting the presence of a fault among four classes: normal, motor, switching, and fault. Finally, if a fault is detected, the third stage identifies specific fault types. This study explored various feature extraction methods and evaluated different ML algorithms to maximize prediction accuracy. The performance of the proposed algorithms is tested in an emulated software–hardware electrical grid testbed using different sample rate meters/relays, such as SEL735, SEL421, SEL734, SEL700GT, and SEL351S near and far from an inverter-based photovoltaic array farm. The performance outcomes demonstrate the proposed model’s robustness and accuracy under realistic conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Systematic Framework for Tuning Open-Source Multifunctional IBR Models To Emulate OEM Black-Box Fault Dynamics

This paper presents a systematic framework to tune a generic IBR EMT model to match with an OEM provided balckbox inverter model based on the fault current responses. The key learnings and findings are summarized as follows: The tunable key parameters include inner control loops and current limiters to align the fault current magnitude, sequence content, and phase trajectories with the OEM models across diverse fault type and locations. The tuned model's fidelity is validated through comparative analysis with an OEM blackbox model, assessing both the fault current response and the responses of multiple relay elements. The results demonstrate the tuned generic model can trigger relay decision logic that is identical or near identical to that of the OEM model, thus generating very good match model for fault studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Background Information on the Protection Requirements in IEEE Std 1547-2018

As the DER penetration level has risen significantly in recent times, parameter settings and configuration of installed DERs are having direct impact on local electric distribution utilities as well as bulk power systems during normal and abnormal grid conditions. On the other hand, all grid-connected DERs in the United States of America must conform to the interconnection requirements prescribed in the IEEE Std 1547-2018. Because of these reasons, it is crucial to understand the expected DER performance during abnormal grid conditions considering the requirements of the IEEE Std 1547-2018. The aim of this document is twofold: (1) to summarize requirements in IEEE Std 1547-2018 having direct implications in distribution network protection, and (2) to provide the reader with knowledge and information that will be required for users to apply the requirements specified. Since the focus of this document is on distribution network protection in the presence of DERs, it is assumed that the readers have basic understanding of distribution network protection as well as working principles of DERs. This document starts with a brief introduction on protection systems for distribution network followed by a discussion on the impact of DER on the protection systems. Current practices to provide network protection in the presence of DER is briefly discussed. The document then explores the DER performance requirements in IEEE Std. 1547-2018; especially on those related to distribution network protection. Section 6.1 in IEEE Std. 1547-2018 provides an overview of capabilities and control requirements for DER under abnormal operating conditions. This section also introduces abnormal operating performance categories I, II, III. The DER response to various types of faults and grid conditions such as short-circuit faults and open phase conditions are discussed in section 6.2 in the standard while requirements for coordination with the Area EPS reclosing scheme are provided in section 6.3. Section 6.4 in the IEEE Std 1547-2018 specifies requirements for mandatory voltage tripping and ride-through requirements during low and high voltage disturbances and section 6.5 specifies similar requirements for low and high frequency disturbances. IEEE Std. 1547 requires that the conformance of the DERs to IEEE Std 1547-2018 requirements should be verified in accordance with IEEE Std. 1547. 1. There are several parameters and settings of DERs that need to be properly selected for reliable operation during abnormal grid condition while applying the requirements of IEEE Std 1547-2018. Key decisions for proper selections of parameter and settings are: 1. Determination of required DER abnormal operating performance category, 2. Determination of DER response (shall trip) to abnormal voltages and 3. Determination of DER response (shall trip) to abnormal frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Technology Strategy Assessment: Findings from Storage Innovations 2030 Thermal Energy Storage

The concept of thermal energy storage (TES) can be traced back to early 19th century, with the invention of the ice box to prevent butter from melting. Modern TES development began with building heating and cooling and concentrated solar thermal technologies for power generation in the early 1900s and late 1970s, respectively. TES systems provide many advantages compared with other long-duration energy storage (LDES) technologies, which include low costs, long operational lives, high energy density, synchronous power generation capability with inertia that inherently stabilizes the grid, and the ability to output both heat and electricity. TES Use Cases TES technologies can couple with most renewable energy systems, including wind, photovoltaic, and concentrated solar thermal energy, and can be used for heat-to-heat, heat-to-electricity, electricity-to-heat, and electricity-to-electricity (bidirectional electricity) applications. The three types of TES that have heat as an input or output are grouped together for the purposes of this report. Retrofitting retired thermal power plants can be a potential cost-effective option for TES with electricity output because they both use a similar thermal-to-electricity type of conversion. Additionally, TES can directly serve heat demand for buildings and industrial processes, displacing fossil fuels to achieve broad decarbonization. Bidirectional Electricity Figure 1 shows a bidirectional electricity TES (ETES) architecture that is emerging as a prime technology for LDES at a grid scale. The ETES technology can utilize existing TES technology infrastructures, has no geological limitations (such as mountains and water for pumped storage hydro, underground natural caverns for compressed-air energy storage, etc.), and is capable of deployment anywhere in the United States and the world for broad uses. Particularly, ETES technology can be placed at retired fossil-fueled thermal power plants to reuse decommissioned assets, protect job security in associated communities, and provide resilient and high-inertia (i.e., spinning) power to the grid. Heat Input and Output There also are many ways to integrate TES within heat-to-electricity, heat-to-heat, and electricity-to-heat applications, such as those used in concentrating solar power (CSP), buildings, district heating, and industry process heat applications. These categories can be further classified for low- and high-temperature applications. High-temperature thermal energy storage (HTTES) heat-to-electricity TES applications are currently associated with CSP deployments for power generation. TES with CSP has been deployed in the Southwestern United States with rich solar resources and has proved its value to the electric grid. Electricity-to-heat and heat-to-heat HTTES applications present great potential for decarbonizing energy-intensive industrial process heat applications [8, 9], such as iron ore processing, iron smelting, cement production, glass manufacturing, mineral processing, and chemical production. Some industrial processes require process heat at temperatures > 1,400°C, so HTTES can be utilized to reduce fuel consumption in those processes through fuel, oxidizer, and process material pre-heating. Thermal energy storage for augmenting existing industrial process heat applications makes a much more attractive economic case because the energy penalty due to thermal-to-electric conversion is eliminated. Co-located applications of power production and heat also can add to the value stacking of integrating utility-scale TES; however, these scenarios are very case specific and not practically possible in many cases. These constraints are primarily attributed to the existing infrastructure being designed, developed, and constructed for many decades around the most economically feasible technologies, such as electricity and a selection of fossil fuels for heat input. Low-temperature TES can be utilized for building and district heating and cooling, as well as some process heat applications in electricity-to-heat and heat-to-heat configurations. Lower temperature TES (LTTES) can be added to heat pump equipment (electric input), either directly interacting with the refrigerant in the condenser or evaporator, or through a secondary heat transfer fluid. It also can be integrated in the building envelope or within the ducts of the heating, ventilation, and air conditioning (HVAC) system. Cost-effective integration of TES into buildings adds significant cost, and it is one of the key barriers preventing the commercialization and deployment of TES. The optimal strategy for integrating TES with buildings has yet to be determined for various applications of TES. Nevertheless, thermal storage materials are far less costly per unit of energy stored than electricity storage materials. This means that thermal storage has the potential to reduce the cost to society of energy storage.

25 ENERGY STORAGE↗

Experimental Characterization Test of a Grid-Forming Inverter for Microgrid Applications

Standardized experimental testing protocols for grid forming (GFM) inverters to ensure expected operation under both normal and contingency conditions do not exist. Such protocols increase the confidence of system owner/operators that an inverter deployed in a proposed system will engage in typical behaviors to ensure interoperability with other units and ancillary equipment (e.g. protection equipment). This paper presents systematic and comprehensive test protocols to evaluate the performance of GFM inverters under the following operational configurations: islanded operation, heterogeneous islanded operation (parallel with a synchronous generator), grid-connected operation, and transition operation. A commercial GFM inverter is used to verify the test protocols and to understand the inverter's performance and functionalities. In particular, required configuration and tuning of the inverter will be explained in the full paper to enrich the testing protocol.

black start↗

Hierarchical Data-Driven Protection for Microgrid with 100% Renewable Penetration: Preprint

The accurate detection and isolation of faults is critical for the reliable operation of microgrids (MGs). Traditional protection approaches are even more challenged for 100% renewable MGs because inverter-based resources (IBRs) are the only sources for fault current which are usually low and unpredictable/non-uniform. This calls for new protection scheme that can identify IBR fault responses and detect faults in MGs. Data-driven based protection can learn the pattern of IBR fault responses and make the correct decision to identify faults. Therefore, this paper presents a data-driven approach for fault localization in island MGs. The approach builds a training dataset of comprehensive fault scenarios that can be used to learn fault characteristics from processed measurements. The localization task is modeled as a binary classification problem at each relay, which simplifies the learning process. Then, a hierarchical decision mechanism is used to identify the fault location. The proposed approach is assessed using an exemplary MG with several grid-forming (GFM) and grid-following (GFL) inverters, where accurate estimation of fault location is achieved. The data-driven based protection approach developed in this paper provides a generic framework and useful guidance for power system protection engineers to achieve reliable protection for MGs with 100% renewables.

artificial intelligence↗

Homomorphic Encryption for Electrical Metering Aggregation: Protecting the Privacy of Building Tenants

Electrical meters are devices that measure consumer electricity usage. The data collected by these meters is necessary for utility billing and electrical grid management but can also be used to assess the environmental impact of buildings. Prior research has found that unprotected metering data could potentially be used to infer some information about the behaviors of building tenants by detecting changes in electricity usage. For example, a period of low electricity usage could suggest that the tenants are not in the building. As smart metering becomes more common, there is a growing need for data privacy protections for metering data that do not negatively impact the quality and availability of data used for energy management and billing applications. To identify potential solutions, we developed a Python-based data aggregation platform to analyze the potential efficacy of privacy-enhancing technologies for energy metering applications. This platform aggregates groups of metering sites into virtual buildings, which could potentially detach changes in electrical activity from individual tenants, making it more difficult to track the activity of a specific tenant. To further protect data during analysis, this project utilizes homomorphic encryption as part of its initial approach. Homomorphic encryption offers a means of protecting energy consumption data while permitting mathematical operations to be performed without the need to know the data contents. This allows for data to be processed into usable statistics without revealing energy consumption information. A series of homomorphic encryption libraries were evaluated to determine their applicability and limitations in the context of metering data. The use of these techniques may help to reassure consumers and encourage further adoption of smart grid infrastructure.