LANL Investigation Report: Magnet Fire Event at TA-53, Line D South
On May 21, 2014, at approximately 2350, an electric magnet fire occurred in the Line D South area of Technical Area 53. Smoke detectors in the supply and return ventilation system ducts activated, sending alarms to the Emergency Operations Support Center (EOSC). Approximately 7 minutes later, a single fire suppression sprinkler actuated. Upon receipt of multiple flow alarms, the Los Alamos Fire Department (LAFD) was dispatched. These first responders concluded this was a false alarm and left the scene prior to the arrival of LANL, or TA-53 personnel. Because of the continued flow of the fire suppression water through the actuated sprinkler, local Radioactive Liquid Waste (RLW) tanks later alarmed on high-level. Further response by the Utilities and Infrastructure (UI) Facility Supervisor and TA-53 facility personnel was focused on stopping the flow of water. These personnel believed the sprinkler actuation and subsequent RLW high level alarms were due to a failed sprinkler head (not an actual fire event).