Smart Grid Integrity Attacks: Characterizations and Countermeasures

Real power injections at loads and generators, and real power flows on selected lines in a transmission network are monitored, transmitted over a SCADA network to the system operator, and used in state estimation algorithms to make dispatch, re-balance and other energy management system [EMS] decisions. Coordinated cyber attacks of power meter readings can be arranged to be undetectable by any bad data detection algorithm. These unobservable attacks present a serious threat to grid operations. Of particular interest are sparse attacks that involve the compromise of a modest number of meter readings. An efficient algorithm to find all unobservable attacks [under standard DC load flow approximations] involving the compromise of exactly two power injection meters and an arbitrary number of power meters on lines is presented. This requires O(n2m) flops for a power system with n buses and m line meters. If all lines are metered, there exist canonical forms that characterize all 3, 4, and 5-sparse unobservable attacks. These can be quickly detected in power systems using standard graph algorithms. Known secure phase measurement units [PMUs] can be used as countermeasures against an arbitrary collection of cyber attacks. Finding the minimum number of necessary PMUs is NP-hard. It is shown that p + 1 PMUs at carefully chosen buses are sufficient to neutralize a collection of p cyber attacks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Performance Evaluation of Data-Enhanced Hierarchical Control for Grid Operations

This paper presents a hardware-in-the-loop (HIL) simulation to evaluate the performance of voltage regulation of Data-Enhanced Hierarchical Control (DEHC). This DEHC uses an advanced distribution management system (ADMS) for grid operations to control legacy and grid-edge devices and coordinate with distributed energy management systems (DERMS) to manage high penetrations of photovoltaics (PV) on a utility distribution system. The HIL platform provides realistic laboratory testing, including accurate modeling (legacy devices, grid-edge devices, and PV) of the real-world distribution system from a utility partner, a real controller (ADMS), software controller DERMS, hardware grid-edge devices, and standard communications protocols. The test results demonstrate functionalities of the integrated platform and the performance of voltage regulation of the coordinated control systems. Based on laboratory testing, the utility can set up the same grid-automation system to manage DERs, legacy devices, and grid-edge devices to achieve their system-level control and operation objectives (e.g., voltage regulation), thus de-risking potential issues such as instability for field deployment.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Development and Experimental Validation of a High-Power DC Distribution Testbed for Advanced Charging Infrastructure and Energy Management

This paper presents the development of a hardware testbed for DC-distributed high-power charging (HPC) stations. As DC distributed solutions emerge as a viable solution to optimize HPC site operations, challenges such as interoperability, protection, and seamless integration of distributed energy resources (DER) persist. These issues underscore the need for a robust testing facility to investigate compliance of available commercial off-the-shelf (COTS) market devices. The developed testbed features a DC-distributed charging hub including a charger, emulated energy storage system (ESS), and site level communication and controller implementation. It facilitates the testing of COTS hardware, charger prototypes, standards validation and site energy management system (SEMS) controllers at rated power. This paper details the development of the charging infrastructure platform, implementation of communication system, validation of different SEMS algorithms, and understanding improvements required for future expansion. Using the developed testbed, interoperability gaps for SEMS implementation with multi-vehicle concurrent charging via a multi-port charger are experimentally observed. Aimed at supporting the transition to large-scale EV charging infrastructure deployment and DER integration, this testbed plays a crucial role in conformity testing of COTS device interoperability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A New Multi-Scale State Estimation Framework for the Next Generation of Power Grid EMS

Accurate system state information under various operation conditions is a prerequisite for power grid monitoring and efficient control. To achieve that goal, a new multi-scale state estimation framework is proposed, paving the way for the development of next generation of energy management system (EMS). The developed framework consists of three key components, namely the static state estimation (SSE) module, the dynamic state estimation (DSE) module, the interfaces and switching logics between the two modules. Specifically, the singular spectrum analysis (SSA)-based change point detection approach is developed to monitor the system continuously. If no event is detected by the SSA, the robust SSE using both SCADA and PMU measurements is executed. Otherwise, the event is declared and the results from SSE are used to derive the initial condition for DSE. During the transient process, only PMU-based DSE is executed for system monitoring and it will be terminated when SSA does not detect any change point of the system. After that, the DSE results are forwarded for SSE initialization and bus voltage magnitude and angle estimations. Simulation results carried out on the IEEE 39-bus system demonstrate the effectiveness and benefits of the proposed framework.

Power system state estimation, energy management s↗

foresee™ (SWR-17-15)

foresee™ is a home energy management system (HEMS) that provides a user centric energy automation solution for residential building occupants. Built upon advanced control and machine learning algorithms, foresee™ intelligently manages the home appliances and distributed energy resources (DERs) such as photovoltaics and battery storage in a home. Unlike existing HEMS in the market, foresee™ provides a tailored home automation solution for individual occupants by learning and adapting to their preferences on cost, comfort, convenience and carbon. foresee™ improves not only the energy efficiency of the home but also its capability to provide grid services such as demand response. Highly reliable demand response services are likely to be incentivized by utility companies, making foresee™ economically viable for most homes.

Source record↗

Probabilistic Look-ahead Contingency Analysis Integration with Commercial Tool and Practical Data

This paper presents an initial effort of integrating a smart sampling-based probabilistic look-ahead contingency analysis algorithm with General Electric (GE) Grid Solutions’ commercial energy management system (EMS) tool as a proof-of-concept for a seamless research tool integration using real world large-scale grid data. With the increasing impact of random forces such as variable generation and load, their stochastic behaviors cannot be ignored. However, the current practices are still dominated by deterministic tools. They are becoming increasingly inadequate for the future grid. The developed look-ahead contingency analysis algorithm incorporates forecast errors of variable energy and load to address the challenges brought by the increasing uncertainty of power system. The algorithm can reveal the potential violations caused by the variance of variable energy and load that are not normally detected by traditional deterministic approaches. To test its performance under practical environments ( real data with real commercial tool), significant efforts have been made to prepare test cases, modify GE EMS tool, and adapt an extreme value distribution algorithm to analyze the GE EMS’s violation-only outputs. The test results clearly demonstrate the effectiveness of the developed algorithm as new transformer violations that were not previously detected have been identified. This performance provides better situational awareness to engineers for their decision-making process under uncertainty. Moreover, with the discussion of computational performance and future work, this paper has shown a clear path for integrating the probabilistic algorithm with commercial tools to make us better equipped for the changing power system.

Modeling and simulation of power systems, constrai↗

Adaptive Cyber-Physical Resilience for Building Control Systems

The main goal of the project is to develop an AI-based process layer cybersecurity suite for detection, isolation and mitigation of cyber-attack effects on operation of building energy management systems (BEMS). The following constituent key technologies were developed under the program towards fulfilling the program objectives: (1) developed a high fidelity BEMS testbed for generation of training data and validation of developed technologies; (2) developed a physics informed ML based attack detection and localization module (ADL) capable of detecting high impact stealthy attacks (HISA - attacks causing 30% energy utilization but no immediate visible impact otherwise) with 98% accuracy; (3) developed a methodology to determine ’representative days’ to limit the data required for training; (4) developed a virtual sensing system that can reconstruct affected sensors with 10% error for the same HISA set; (5) developed a resilient model predictive control system that can continue operation of the BEMS without jeopardizing stability for the HISA set; and (6) integrated and deployed all the constituent modules and demonstrated the efficacy of the technology in real-time in a hardware in loop simulation.

42 ENGINEERING↗

PRIME: a real-time cyber-physical systems testbed: from wide-area monitoring, protection, and control prototyping to operator training and beyond

As the power grid continues to evolve with advanced wide-area monitoring, protection, and control (WAMPAC) algorithms, there is an increasing need for realistic testbed environments with industry-grade software and hardware-in-the-loop (HIL) to perform verification and validation studies. Such testbed environments serve as ideal platforms to perform WAMPAC prototyping, operator training, and also to study the impacts of different types of cyberattack scenarios on the operation of the grid. In this paper, we introduce PRIME (PNNL cybeR physIcal systeMs tEstbed): the testbed that integrates real-time transmission system simulator with commercial industry grade energy management system (EMS) software and remote hardware-in-the-loop (RHIL). PRIME is an end-to-end, modular testbed that allows high-fidelity RHIL experimentation of a power system. We present two detailed case studies (fault location and clearing in transmission system, and operator training) to showcase the capabilities of our PRIME testbed. Finally, we briefly discuss some of the potential limitations of our testbed in terms of scalability and flexibility to setup larger test systems and identify directions for future work to address those limitations.

42 ENGINEERING↗

A Novel Architecture for Attack-Resilient Wide-Area Protection and Control System in Smart Grid

Wide-area protection and control (WAPAC) systems are widely applied in the energy management system (EMS) that rely on a wide-area communication network to maintain system stability, security, and reliability. As technology and grid infrastructure evolve to develop more advanced WAPAC applications, however, so do the attack surfaces in the grid infrastructure. This paper presents an attack-resilient system (ARS) for the WAPAC cybersecurity by seamlessly integrating the network intrusion detection system (NIDS) with intrusion mitigation and prevention system (IMPS). In particular, the proposed NIDS utilizes signature and behavior-based rules to detect attack reconnaissance, communication failure, and data integrity attacks. Further, the proposed IMPS applies state transition-based mitigation and prevention strategies to quickly restore the normal grid operation after cyberattacks. As a proof of concept, we validate the proposed generic architecture of ARS by performing experimental case study for wide-area protection scheme (WAPS), one of the critical WAPAC applications, and evaluate the proposed NIDS and IMPS components of ARS in a cyber-physical testbed environment. Our experimental results reveal a promising performance in detecting and mitigating different classes of cyberattacks while supporting an alert visualization dashboard to provide an accurate situational awareness in real-time.

24 POWER TRANSMISSION AND DISTRIBUTION↗

The Business Value of Superior Energy Performance

Industrial facilities participating in the U.S. Department of Energy’s (US DOE) Superior Energy Performance (SEP) program are finding that it provides them with significant business value. This value starts with the implementation of ISO 50001-Energy management system standard, which provides an internationally-relevant framework for integration of energy management into an organization’s business processes. The resulting structure emphasizes effective use of available data and supports continual improvement of energy performance. International relevance is particularly important for companies with a global presence or trading interests, providing them with access to supporting ISO standards and a growing body of certified companies representing the collective knowledge of communities of practice. This paper examines the business value of SEP, a voluntary program that builds on ISO 50001, inviting industry to demonstrate an even greater commitment through third-party verification of energy performance improvement to a specified level of achievement. Information from 28 facilities that have already achieved SEP certification will illustrate key findings concerning both the value and the challenges from SEP/ISO 50001 implementation. These include the facilities’ experience with implementation, internal and external value of third-party verification of energy performance improvement; attractive payback periods and the importance of SEP tools and guidance. US DOE is working to bring the program to scale, including the Enterprise-Wide Accelerator (SEP for multiple facilities in a company), the Ratepayer-Funded Program Accelerator (supporting tools for utilities and program administrators to include SEP in their program offerings), and expansion of the program to other sectors and industry supply chains.

McKane, Aimee↗

Management of Risk and Uncertainty Through Optimized Co-Operation of Transmission Systems and Microgrids With Responsive Loads (Final Report)

The evolution of the power system to the reliable, efficient and sustainable system of the future will involve development of both demand- and supply-side technology and operations. Ambitious national and state-level goals around the decarbonization of electricity relies on the integration of very high levels of renewable resources, most of which are variable and intermittent. The use of demand response is an ideal approach to counterbalance the intermittency of renewable generation and brings the consumer into the spotlight. Though individual consumers are interconnected at the low-voltage distribution system, these resources are typically modeled as variables at the transmission network level. Demand-side participation cannot be leveraged effectively without explicitly including the distribution system dynamics in the optimization-based wholesale market operations. This project grew from a vision for co-optimized interaction of distribution systems, or microgrids, with the high-voltage transmission system. In this framework, microgrids encompass consumers, distributed renewables and storage. The energy management system of the lower voltage system (distribution or microgrid) can also sell (buy) excess (necessary) energy from the transmission system. Until recently, very little research had been conducted on the co-optimization of these two systems due to computational limitations. However, advances in computational capabilities, and the judicious use of decomposition methods and innovative approximation methods for high-dimension dynamic programming made this goal a viable objective for this project, leading to a fundamental shift in the ability to integrate and fully utilize demand-side resources. To this end, the modeling framework developed introduces a novel co-optimization framework, to include the operations of both the transmission and distribution systems (or microgrids) in operational decision making. This framework was used to analyze renewable and distributed generation along with responsive demand and to compare the capability of co-optimized systems to perform with higher levels of variable renewables. An ideal microgrid is defined as an electric entity capable of operating in both interconnected (with the high-voltage grid) and islanded mode. As such, the microgrid should incorporate generating units (traditional units and intermittent) and if needed, exchange power with the high-voltage grid. The interplay between the microgrid and high-voltage grid motivated the development of the co-optimization approach to ensure efficient performance of the interconnected network. Results show that the use of a bi-level optimization approach is an appropriate structure, capable of co-optimizing a transmission system with multiple distribution systems and microgrids. While increasing the number of connected systems provides increasing flexibility for renewables integration this can also the economic benefits to the low-voltage subsystems with each additional system connected. Comparison of a traditional single-level decision structure with the co-optimization approach illustrates a reduction in overall system cost under co-optimization, while specific cost allocations to transmission and distribution systems are changed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Performance Evaluation of Next-Generation Grid Automation and Controls with High PV Penetration

This paper presents a hardware-in-the-loop (BIL) simulation to evaluate the performance of an advanced grid automation architecture, referred to as data-enhanced hierarchical control (DEHC), in achieving voltage regulation and conservation voltage reduction (CVR) in distribution networks with very high photovoltaic (PV) generation. This architecture comprises an advanced distribution management system (ADMS), a distributed energy resource management system (DERMS), and grid-edge devices working synergistically to provide the grid benefits. The HIL setup used for the evaluation includes ADMS, DERMS, and grid-edge devices. The DEHC performance is evaluated in two representative scenarios considering loose and tight constraints of the power factor at the substation. The results show that the DEHC architecture is effective in achieving voltage regulation and CVR and thus enables the grid integration of high levels of PV generation.

ADMS↗

Energy Systems Integration Facility Stewardship Summary: Fiscal Year 2024

A summary of NREL's good stewardship of the nationally unique Energy Systems Integration Facility (ESIF) highlighting performance metrics, infrastructure upgrades, and examples of R&D impact. In fiscal year 2024, we developed advanced energy security and resilience capabilities as we built a new test bed for power electronics and completed a 1-megawatt platform for studying energy systems with grid-forming inverters. Researchers collaborated with utilities, manufacturers, and communities to solve their pressing questions, such as a control architecture that heralds a new direction for distributed energy management systems. With support from the U.S Department of Energy (DOE), the work in the ESIF laboratories continues to advance national goals for resilient and affordable energy.

annual report↗

Chapter 24: Strategic Energy Management (SEM) Evaluation Protocol. The Uniform Methods Project: Methods for Determining Energy Efficiency Savings for Specific Measures

Strategic energy management (SEM) focuses on achieving energy-efficiency improvements through systematic and planned changes in facility operations, maintenance, and behaviors (OM&B) and capital equipment upgrades in large energy-using facilities, including industrial buildings, commercial buildings, and multi-facility organizations such as campuses or communities. Facilities can institute a spectrum of SEM actions, ranging from a simple process for regularly identifying energy-savings actions, to establishing a formal, third-party recognized or certified SEM framework for continuous improvement of energy performance. In general, SEM programs that would be considered part of a utility program will contain a set of energy-reducing goals, principles, and practices emphasizing continuous improvements in energy performance or savings through energy management and an energy management system (EnMS).

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Improved Air-Conditioning Demand Response of Connected Communities over Individually Optimized Buildings

Connected communities potentially offer much greater demand response capabilities over singular building energy management systems (BEMS) through an increase of connectivity. The potential increase in benefits from this next step in connectivity is still under investigation, especially when applied to existing buildings. This work utilizes EnergyPlus simulation results on eight different commercial prototype buildings to estimate the potential savings on peak demand and energy costs using a mixed-integer linear programming model. This model is used in two cases: a fully connected community and eight separate buildings with BEMS. The connected community is optimized using all zones as variables, while the individual buildings are optimized separately and then aggregated. These optimization problems are run for a range of individual zone flexibility values. The results indicate that a connected community offered 60.0% and 24.8% more peak demand savings for low and high flexibility scenarios, relative to individually optimized buildings. Energy cost optimization results show only marginally better savings of 2.9% and 6.1% for low and high flexibility, respectively.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

AI-Driven Smart Community Control for Accelerating PV Adoption and Enhancing Grid Resilience

The U.S. Department of Energy (DOE) has launched a Connected Communities program that supports projects that expand DOE's network of grid-interactive, efficient building communities nationwide. As an early pilot of Connected Communities, the National Renewable Energy Laboratory (NREL) and its partners have developed and demonstrated a community-scale, hierarchical control solution to address the potential grid issues arising from high penetration of solar photovoltaics (PV) as well as to improve grid reliability and resilience in this residential community. A field pilot study has been performed at an affordable housing development called the Basalt Vista Community, which was built for school teachers and other professionals in the local workforce and represents an autonomous energy grid with all-electric, energy-efficient homes. With no natural gas line in the community, this is the first all-electric net-zero community in rural Colorado. In the field pilot study, NREL has validated the performance of the hierarchical control solution, which consists of NREL's foresee home energy management systems (HEMS) and community aggregators, in increasing demand flexibility and self-consuming PV, reducing potential over-voltages, and supporting critical loads during emergency events. In this presentation, we will present the methodology, simulation and field pilot results, and lessons learned from the project.

all-electric community↗

Massive Contingency Analysis with High Performance Computing

Contingency analysis is a key function in the Energy Management System (EMS) to assess the impact of various combinations of power system component failures based on state estimates. Contingency analysis is also extensively used in power market operation for feasibility test of market solutions. Faster analysis of more cases is required to safely and reliably operate today’s power grids with less marginal and more intermittent renewable energy sources. Enabled by the latest development in the computer industry, high performance computing holds the promise of meet the need in the power industry. This paper investigates the potential of high performance computing for massive contingency analysis. The framework of "N-x" contingency analysis is established and computational load balancing schemes are studied and implemented with high performance computers. Case studies of massive 300,000-contingency-case analysis using the Western Electricity Coordinating Council power grid model are presented to illustrate the application of high performance computing and demonstrate the performance of the framework and computational load balancing schemes.

Computational Load Balancing↗

Overheating in Hot Water- and Steam-Heated Multifamily Buildings

In this project, the ARIES Building America team collected apartment temperature data from the archives of companies that provide energy management systems (EMS) to multifamily buildings in the Northeast U.S. Data was analyzed from more than 100 apartments in eighteen buildings where EMS systems were already installed to quantify the degree of overheating in an effort to answer the question, "What is the magnitude of apartment overheating in multifamily buildings with central hot water or steam heat?" This report provides valuable information to researchers, utility program managers and building owners interested in controlling heating energy waste and improving resident comfort.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗