A Measurement-Based Adaptive Voltage Regulation Method Considering Topology Changes

This paper proposes an online adaptive data-driven distributed energy resource (DER) dispatch optimization method for voltage control considering topology changes. By using a local sensitivity factor (LSF)-enabled voltage control, traditional DER control can be reformulated into a linear programming (LP) problem, leading to faster computation speeds. Power injection alteration and topology changes are two common operational changes in the distribution network that can affect the LSF and voltage control performance. To address this issue, a robust estimation method is developed to adjust the sensitivity matrix at each time step for the time-varying power injection changes. When topology changes occur, only the allocated predominant LSF submatrices are updated based on measurement data, allowing for a fast adaptation to the system reconfiguration. Results obtained from a real distribution feeder in Southern California demonstrate its robustness as compared to traditional volt-var control and constant LSF matrix dispatch control methods.

DERs↗

Experimental Test Bed to Enable Realistic Evaluations for Direct Transfer Trip Relaying via Private Wireless LTE Communications

Increasing penetration levels of inverter-based distributed energy resources (DERs) in distribution systems are creating challenges in system operation. Currently, wired or proprietary wireless communications are used by advanced distribution management systems (ADMS) to detect the state of the system and control the DERs for optimal operation. Wireless communications are an alternative solution that can enable connectivity between the dispersed assets used in distribution system applications. This paper demonstrates an experimental test bed to enable the realistic evaluation of communications system characteristics for direct transfer trip (DTT) relaying of a photovoltaic inverter system using a private 900-MHz spectrum wireless LTE network. Private LTE network communications can be deployed to many remote DERs and other grid-edge devices to prevent costly infrastructure upgrades across distribution systems. In addition, this paper provides a framework for evaluating the impact of signal strength and network traffic in communications systems. The results shown develop a better understanding of the best practices for using LTE communications systems across multiple utility applications, such as protective relaying, voltage regulation, and supervisory control and data acquisition system messages.

900-MHz LTE network↗

Time Sequence Machine Learning-Based Data Intrusion Detection for Smart Voltage Source Converter-Enabled Power Grid

Smart inverters of distributed energy resources can enable cloud computing, condition monitoring, result visualization, remote control, and peer-to-peer energy trading in advanced power systems. However, the advent of data injection attacks in the communication architecture can alter measurement characteristics of power grids and have devastating consequences. In this article, we propose a time sequence machine learning-based anomaly detection methodology for detecting cyber intrusion into control signal setpoints and dc voltage signal measurement bias of the voltage source converter (VSC) in wind generators. We first investigated the effects of four types of denial of service, tampering signal, and stealthy-type data intrusion attacks on smart VSCs and overall wind farms. We then proposed a novel time sequence machine learning-based intrusion detection framework that can be implemented to detect different cyberattacks in the VSCs. The performance of the proposed framework has been compared with that of autoencoder and clustering-based intrusion detection framework. The proposed framework was validated by using the IEEE 39 bus power system in the presence of four wind farms in different locations. Using several metrics for intrusion detection performance, we validated the effectiveness of the proposed framework.

42 ENGINEERING↗

Integration of Utility Distributed Energy Resource Management System and Aggregators for Evolving Distribution System Operators

With the rapid integration of distributed energy resources (DERs), distribution utilities are faced with new and unprecedented issues. New challenges introduced by high penetration of DERs range from poor observability to overload and reverse power flow problems, under-over-voltages, maloperation of legacy protection systems, and requirements for new planning procedures. Distribution utility personnel are not adequately trained, and legacy control centers are not properly equipped to cope with these issues. Fortunately, distribution energy resource management systems (DERMSs) are emerging software technologies aimed to provide distribution system operators (DSOs) with a specialized set of tools to enable them to overcome the issues caused by DERs and to maximize the benefits of the presence of high penetration of these novel resources. However, as DERMS technology is still emerging, its definition is vague and can refer to very different levels of software hierarchies, spanning from decentralized virtual power plants to DER aggregators and fully centralized enterprise systems (called utility DERMS). Although they are all frequently simply called DERMS, these software technologies have different sets of tools and aim to provide different services to different stakeholders. This paper explores how these different software technologies can complement each other, and how they can provide significant benefits to DSOs in enabling them to successfully manage evolving distribution networks with high penetration of DERs when they are integrated together into the control centers of distribution utilities.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Improvements in and test results for the 2 to 15 kilowatt Brayton cycle electrical subsystem

The electrical subsystem of the 2- to 15-kW Brayton power conversion system consists of the auxiliary electrical equipment required for an integrated, self-contained system. For the last 2 years the electrical subsystem has been undergoing extensive tests. The first year of testing resulted in determining the performance characteristics of the electrical subsystem. During the second year several significant changes and improvements were investigated. An inverter designed for motor starting the alternator performed successfully. Some of the changes that have been made are a new alternator speed pickup, which is independent of the alternator output voltage; new, more efficient power supplies for the control system; and a volts-per-hertz reference for the alternator voltage regulator. Test data were taken on the temperature distribution of the electrical subsystem at startup conditions over a cold-plate temperature range of 25 to -50 C.

Vrancik, J. E.↗

A 25-kW Series-Resonant Power Converter

Prototype exhibited efficiency of 93.9 percent. 25-kW resonant dc/dc power converter designed, developed, fabricated, and tested, using Westinghouse D7ST transistors as high-power switches. D7ST transistor characterized for use as switch in series-resonant converters, and refined base-drive circuit developed. Technical base includes advanced switching magnetic, and filter components, mathematical circuit models, control philosophies, and switch-drive strategies. Power-system benefits such as lower losses when used for high-voltage distribution, and reduced magnetics and filter mass realized.

Frye, R. J.↗

Resilient Inverter-Driven Black Start with Collective Parallel Grid-Forming Operation: Preprint

As the modern power systems are experiencing exceptional changes with increasing penetration of inverter-based resources (IBRs), system restoration using IBRs has received attention. Using local grid-forming (GFM) assets near consumers, engineered to establish grid voltages in the absence of a stiff grid, i.e., bottom-up restoration, a distribution system would obtain high system resilience, by not relying on the bulk power system restoration requiring significant human intervention and procedure to restore. This paper studies the technical feasibility of the novel approach with detailed electromagnetic transient (EMT) simulations. To thoroughly evaluate the potential of GFM inverters and technical challenges in IBR-driven black start, a detailed three-phase inverter model is developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter to sustain momentary overloading during the black start. To examine dynamic aspects of the black start process, the EMT simulation also models transformer and motor dynamics to emulate their inrush and start-up behaviors as well as network dynamics. In addition, active involvement of grid-following distributed energy resources (DER) is also studied to facilitate the black start process. It is shown that, by allowing multiple GFM inverters to collectively black start without master-slave coordination, a system can achieve high resilience even with a fraction of assets lost. Two test cases of inverter-driven black start using two and one GFM inverters, respectively, for a heavily unbalanced 2-MVA distribution feeder are demonstrated. Takeaways for further study and field deployment are provided.

grid-forming inverter↗

An Innovative Energy Management System for Microgrids with Multiple Grid-Forming Inverters

As increasingly more grid-forming (GFM) inverter-based resources replace traditional fossil-fueled synchronous generators as the GFM sources in microgrids, the existing microgrid energy management systems (EMS) need to be updated to control and coordinate multiple GFM inverters that consider system control objectives under different microgrid connection states. For each state, we formulate an optimization problem and apply a real-time feedback-based control algorithm; altogether, the control algorithms seamlessly connect the states into a generic microgrid EMS that controls the nodal voltages and frequencies, becomes a virtual power plant (VPP) when connected to the main grid, and coordinates power sharing responsibility among GFM sources when islanded. We showcase the EMS on a real-world simulation of a microgrid under the different states to demonstrate its operational effectiveness.

energy management systems↗

Electric power processing, distribution and control for advanced aerospace vehicles.

The results of a current study program to develop a rational basis for selection of power processing, distribution, and control configurations for future aerospace vehicles including the Space Station, Space Shuttle, and high-performance aircraft are presented. Within the constraints imposed by the characteristics of power generation subsystems and the load utilization equipment requirements, the power processing, distribution and control subsystem can be optimized by selection of the proper distribution voltage, frequency, and overload/fault protection method. It is shown that, for large space vehicles which rely on static energy conversion to provide electric power, high-voltage dc distribution (above 100 V dc) is preferable to conventional 28 V dc and 115 V ac distribution per MIL-STD-704A. High-voltage dc also has advantages over conventional constant frequency ac systems in many aircraft applications due to the elimination of speed control, wave shaping, and synchronization equipment.

Krausz, A.↗

Peer-to-peer communication control for resilient operations of networked cyberphysical systems

This report includes two main accomplishments of the peer-to-peer communication control for resilient operation of networked microgrids project in FY24, which include a scheme for cyberattack-aware coordination of networked microgrids for supporting voltages of bulk power systems and a scheme for price signal-based operations of EV-rich networked microgrids with mixed ownership. First, the cyberattack-aware scheme enables networked microgrids to distributedly determine the amount of reactive power injection to support the voltage of bulk power system (BPS) in a fair manner. In this scheme, a risk-informed algorithm is presented to generate the peer-to- peer (P2P) communication graph with minimal risk of attack on communication links. To deal with cyberattacks on MG controllers, the resilient consensus algorithm (CA) is utilized for MG controllers to robustly estimate the total reactive power headroom, from which the MGs can accurately provide the needed amount of reactive power injection for supporting the voltage of BPS. The CA implementation and performance within the P2P communication framework are demonstrated on the IEEE 39-bus system with 6 microgrids contained in the distribution feeder under different cyberattack scenarios. Second, the price-based scheme enables the usage of the real-time price signal for the operations of electric vehicle (EV)-rich networked-microgrids with mixed ownership, in which not all the microgrids can communicate with the distribution system operator (DSO). In this scheme, a max consensus is introduced to enable the real-time price signal to be propagated from the DSO to all the microgrids, from which each microgrid controller will manage the DERs to balance the load demand and the power injection from the EV charging stations within its microgrid. Numerical results over one day with 288 slots of 5-minute intervals on the modified 123-node test feeder including 3 microgrids with high penetration of EV are presented to evaluate how the price signal affects the operations of networked microgrids under different charging strategies of the EV charging stations. The result indicates that our proposed EVCS (dis)charging strategy, which leverages the flexibility of EVs to support the grid through discharging during peak demand, proves to be a cost-effective solution that reduces operational costs while improving the social welfare of EV charging.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Generic and Multifunctional Electromagnetic Transient Model for Grid-Following Inverters

This paper presents a generic and multifunctional electromagnetic transient (EMT) dynamic model of grid-following (GFL) inverter-based resources (IBRs) using the PSCAD software platform. The features of the model include flexibility in selecting various types and combinations of DC sources covering photovoltaic modules, battery modules, and ideal DC-source modules as well as flexibility in selecting either switching or averaged models of the inverter. This model also covers exhaustive lists of controller algorithm, including open-loop/closed-loop PQ dispatch control, DC voltage and AC terminal voltage control, and conventional current control designed in the dq-domain, the ..alpha....beta.. -domain, and the positive-/negative-sequence domain. Moreover, this model is equipped with flexibility in selecting various types of current-limiting schemes, including saturation-based and latching-based current limiters, and anti-windup protection. Also, the EMT model is agnostic to the MVA rating and is suitable for interfacing transmission systems by complying with IEEE Std. 2800. The generality in the power circuits and the multifunctional options in the operation and control of the developed EMT model make it suitable for both academia and industry to study various power system aspects, including, but not limited to, the fault behavior of GFL IBRs, the impacts on the protection system, and the transient stability of a system interfaced with large numbers of GFL IBRs.

integrated circuit modeling↗

Large-Scale Adoption of Self-Synchronized Universal Droop Controller-Based Inverters to Enable Ancillary Services for Different Modes of Distribution System Operations

This work proposes the large-scale adoption of self-synchronized universal droop controller (SUDC)-based inverters to enable ancillary services for different modes of distribution system operations. The IEEE 123 bus system was modeled on a real-time simulator to study the performance of large-scale adoption of SUDC inverters in a distribution system. The resulting data collected shows that the voltage and the frequency were regulated within ranges, such as less than 5% for voltage and less than 0.5% for frequency, under different load variations and grid operations. Also, the black start was achieved within 0.4 s without any voltage overshoot. Through the simulation and validation on a small microgrid and the IEEE 123 bus distribution system, it can be concluded that the SUDC was successfully adopted to regulate the voltage and the frequency within the given ranges, and black start achieved within 1 s without voltage overshoot for different modes of distribution system operations.

14 SOLAR ENERGY↗

Trust-Based Detection and Mitigation of Cyber Attacks in Distributed Cooperative Control of Islanded AC Microgrids

In this study, we address the challenge of detecting and mitigating cyber attacks in the distributed cooperative control of islanded AC microgrids, with a particular focus on detecting False Data Injection Attacks (FDIAs), a significant threat to the Smart Grid (SG). The SG integrates traditional power systems with communication networks, creating a complex system with numerous vulnerable links, making it a prime target for cyber attacks. These attacks can lead to the disclosure of private data, control network failures, and even blackouts. Unlike machine learning-based approaches that require extensive datasets and mathematical models dependent on accurate system modeling, our method is free from such dependencies. To enhance the microgrid’s resilience against these threats, we propose a resilient control algorithm by introducing a novel trustworthiness parameter into the traditional cooperative control algorithm. Our method evaluates the trustworthiness of distributed energy resources (DERs) based on their voltage measurements and exchanged information, using Kullback-Leibler (KL) divergence to dynamically adjust control actions. We validated our approach through simulations on both the IEEE-34 bus feeder system with eight DERs and a larger microgrid with twenty-two DERs. The results demonstrated a detection accuracy of around 100%, with millisecond range mitigation time, ensuring rapid system recovery. Additionally, our method improved system stability by up to almost 100% under attack scenarios, showcasing its effectiveness in promptly detecting attacks and maintaining system resilience. These findings highlight the potential of our approach to enhance the security and stability of microgrid systems in the face of cyber threats.

Computer Science↗

LLM-Based Adaptive Distribution Voltage Regulation Under Frequent Topology Changes: An In-Context MPC Framework

This paper proposes a large language model (LLM) based adaptive inverter control for distribution voltage regulation under frequent topology changes. We leverage the ability of the LLM to perform in-context learning and create a topology-adaptive surrogate model for power flow calculation. The surrogate model is then integrated with a long short-term memory-based load forecaster and a model predictive control (MPC) scheme to achieve the optimal inverter control that adapts to frequent topology changes. Unlike many existing works that assume fixed-topology grids or require the knowledge of all possible topologies when training a model, the proposed in-context MPC method tackles the distribution voltage control problem under various topologies and adapts to unknown topologies with limited data requirement for fine-tuning. The effectiveness of our method is demonstrated on a modified IEEE 123-bus test system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Experimental Test Bed to Enable Realistic Evaluations for Direct Transfer Trip Relaying via Private Wireless LTE Communications: Preprint

Increasing penetration levels of inverter-based distributed energy resources (DERs) in distribution systems are creating challenges in system operation. Currently, wired or proprietary wireless communications are used by advanced distribution management systems (ADMS) to detect the state of the system and control the DERs for optimal operation. Wireless communications are an alternative solution that can enable connectivity between the dispersed assets used in distribution system applications. This paper demonstrates an experimental test bed to enable the realistic evaluation of communications system characteristics for direct transfer trip (DTT) relaying of a photovoltaic inverter system using a private 900-MHz spectrum wireless LTE network. Private LTE network communications can be deployed to many remote DERs and other grid-edge devices to prevent costly infrastructure upgrades across distribution systems. In addition, this paper provides a framework for evaluating the impact of signal strength and network traffic in communications systems. The results shown develop a better understanding of the best practices for using LTE communications systems across multiple utility applications, such as protective relaying, voltage regulation, and supervisory control and data acquisition system messages.

900 MHz LTE network↗

A High Voltage Distribution System for the Mu2e Electron Tracker

This paper describes the design and development of a High Voltage distribution system (Smart Switch - SS) which distributes one input high voltage (HV) into six High Voltage channels (HVDS) of a straw detector plane. The SS independently sets, controls, and monitors the HV to each individual channel of a straw-detector plane in the Mu2E Electron Tracking Detector. Each straw plane is composed of three 120 deg crescent-shaped panels, and each panel is composed of 96 straw-tube detectors. Each output channel of the SS has independent, ON-OFF, current and HV monitoring, as well as filtration, isolation, and a crowbar to provide overcurrent protection for in that channel. The inter-communication system is based on TCP/IP protocol using a Raspberry Pi. The HVDS meets all required specifications including long term stability, accurate monitoring of the HV and current, and overcurrent trip. The performance of the HVDS was found to be comparable to, if not better than, commercial HV power supplies.

42 ENGINEERING↗

Anomaly Detection and Mitigation in FACTS-based Wide-Area Voltage Control Systems using Machine Learning

With the increasing deployment of Flexible AC Transmission System (FACTS) devices in wide-area voltage control systems (WAVCS) for achieving improved voltage stability of bulk power systems, the possibility for cyber attacks on these systems is also increasing. Successful stealthy cyber attacks that are difficult to detect by traditional informational technology (IT)-based cybersecurity solutions or threshold-based bad data detectors can lead to a voltage collapse in power grid. This paper presents the testbed-based attacks implementation and real-time evaluation of machine learning (ML) algorithm for detecting and mitigating stealthy cyber attacks on FACTS-based WAVCS on a hardware-in-the-loop (HIL) testbed. Initially, we discuss the implementation of a fuzzy logic controller (FLC) that controls a Static VAR Compensator (SVC) device deployed in a two-area four-machine Kundur power system for improving transient voltage stability. Later, the ML-based Anomaly Detection and Mitigation (ADM) system is implemented on the cyber-physical HIL testbed to detect and mitigate various stealthy cyber attacks, which are injected in real-time over the wide-area network (WAN). The experimental results show accurate and effective performance of ADM system in detecting and mitigating anomalies while keeping the grid stable and within the system operating limits, as defined by the North America Electric Reliability Corporation (NERC).

24 POWER TRANSMISSION AND DISTRIBUTION↗

System Modeling and Robust Stability Region Analysis for Multi-inverters Based on VSG

As the number of inverter-interfaced distributed generators (IIDGs) increases, the decrease in the inertia of the microgrid affects the stability of microgrid voltage and current. The virtual synchronous generator (VSG) control method simulates the output characteristics of the synchronous machine to improve the inertia and damping of the microgrid. However, low-frequency oscillations can occur in systems with multi-VSGs connected in parallel, primarily when operating in island mode. Therefore, this article develops the small-signal state-space model for multi-inverters based on VSG and analyses the robust stability region (RSR) of the control parameters. Firstly, an extensible small-signal state-space model is established and simplified in the dq axis, which is a necessary preprocessing for the subsequent stability analysis. Secondly, the guardian map method based on bialternate product operation is constructed, and the RSR is established through translation mapping and rotation mapping. Therefore, the solution of RSR is transformed into the problem of identifying the Hurwitz matrix. Finally, the simulations and experiments verify that the calculated region can ensure stable operation during startup and meet the requirement to suppress low-frequency oscillations. In conclusion, the method of solving RSR proposed in this paper provides a basis for selecting controller parameters in practical engineering.

24 POWER TRANSMISSION AND DISTRIBUTION↗