Engineering Papers⌕ Search

SEARCH · Engineering Papers

Results for “building cooling system”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 235 records · Page 13

Human-in-the-loop Sensing and Control for Commercial Building Energy Efficiency and Occupant Comfort

Most of the existing heating, ventilation and air conditioning (HVAC) systems in commercial buildings operate in a conservative manner by assuming maximum occupancy in each room during pre-specified periods of the week, leading to significant energy being wasted as rooms are over-conditioned compared to the actual requirements of the occupants. Though critical, our understanding of occupancy patterns and thermal comfort needs of the occupants in commercial buildings is lacking and it is well known that both of these quantities are stochastic and time-varying, thus requiring sensing solutions to estimate them. This project had the goal of designing, implementing and evaluating a hardware and software solution to ameliorate this challenge. In particular, a depth camera (one whose pixels reveal distance from the camera as opposed to color values) placed on doorways is used to detect entrance and exit events from thermal zones in the building, and thereby estimate their occupancy levels. This information is then fed to a novel control algorithm that can, through interactions with the HVAC system, learn how to provide control inputs that maximize comfort and minimize energy waste. The resulting system represents a significant improvement over existing controllers for commercial HVAC systems and allowed us to improve our understanding of the design of future human-in-the-loop control solutions. For this solution to be feasible, the project had target metrics for its performance and cost. In particular, entrance and exit events for occupants moving about the building would need to be detected with an accuracy higher than 97%; and the resulting control inputs derived from this information would need to lead to approximately 10% energy savings compared to a schedule-based controller. Furthermore, regarding the final hardware design, the project had a target bill of materials (BOM) cost for the sensing solution of less than US$200 per unit while using less than 25W of power on average. All of these target metrics were met or exceeded by our final proposed solution. We performed evaluations by deploying the system in over 20 rooms of different types across 6 commercial buildings in Pittsburgh, PA over the course of three years, and performing targeted controlled experiments to test its performance along the different metrics. The human-in-the-loop control solutions (both hardware and software) developed through this project are expected to lead to significant improvements in the comfort and energy efficiency of HVAC systems used in commercial buildings. The insights we developed through the project pave the way to HVAC systems that can condition interior spaces according to their real-time utilization and the thermal comfort needs of the occupants, thereby reducing energy use. They also open up a new learning-based way of configuring HVAC controllers without having to manually fine-tune them for each building. These innovations can significantly increase the adoption of novel control solutions by the industry and thereby save resources and reduce costs of operation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

The Cost of Comfort in Your Home: Peak-Time Energy and Cost Savings from Setpoint Adjustment of Space Heating and Cooling

This poster presents the tradeoff between energy costs and thermal comfort in homes. Residential heating and cooling systems use a thermostat control to maintain a comfortable temperature range, but tighter temperature control leads to higher annual energy costs. We estimate the impact of temperature setpoint adjustment on annual energy costs using a residential building model developed at NREL. We show that increasing the allowable temperature range reduces energy costs in all five of the climate zones in the U.S. Annual costs reduced by about $100, with larger savings in areas with more heating and/or cooling loads.

30 DIRECT ENERGY CONVERSION↗

A dimensionless number for high-throughput design of multi-principal element alloys in directed energy deposition

The present study demonstrates the development of a dimensionless number to predict the build height in the additive manufacturing technique of directed energy deposition (DED). The build height can also be used to estimate the dendrite arm spacing and, thus, the cooling rate in the fabrication of samples. A baseline sample, 316L stainless steel, was used to fit the build height to the dimensionless number. A range of process parameters, including laser power, laser feed rate, powder flow rate, layer thickness, and hatch spacing, were varied. Based upon dendrite arm spacing, the estimated cooling rate varied between 102 and 104 K/s. Using the fitted relationship for the stainless steel, high-throughput (HT) processing of multi-principal element alloys (MPEAs) was performed. For this study, HT is the ability to fabricate a batch of 25 bulk samples (∼1 cm3) with different compositions within a 5-h period with ±10 at. % accuracy. A range of compositions using in situ alloying of elemental powders in the Fe–Ni–Cr–Mo system were made. The MPEAs' build height followed the same relationship to the dimensionless number as the 316L alloy. The dimensionless number predicts both macro and meso-scale features in HT processing, thus offering a design tool for choosing process parameters in DED additive manufacturing. Also, the ability to control or increase cooling rates can enhance the ability to promote metastability as well as control meso-scale chemical distributions of alloy samples.

Islam, Zahabul (ORCID:0000000169613209)↗

Geographic Information System Mapping Tool for Rainwater Harvesting in the United States

The Rainwater Harvesting Tool is a publicly available web-based geographic information system tool developed using geospatial analysis in combination with historic ZIP Code level monthly average precipitation and evapotranspiration data across the United States to help select potential locations for harvesting rainwater. Rainwater harvesting can provide a key source of alternative water for a variety of uses including landscape irrigation, vehicle wash, cooling tower makeup, dust suppression, and toilet flushing. Rainwater harvesting can help support institutional, commercial, and residential buildings in diversifying water sources and offset the use of freshwater. This tool aims to help organizations strategically target locations to implement rainwater harvesting systems. The metric used in the tool is called the rainwater harvesting potential, which is a normalized metric, measured in inches per year. The rainwater harvesting potential describes the amount of rainwater that can be reasonably collected and stored at a specific location. This metric was used to rank areas delineated by ZIP Codes across the US, from lowest to highest to show the relative availability of rainwater for harvesting. Two mapping layers are included in the tool that show the general rainwater harvesting potential for all applications and a layer that specifically shows the potential for harvesting rainwater to supply irrigation The Rainwater Harvesting Tool allows users to view overall trends across the United States, while also allowing the user to zoom in to a scale where ZIP Code boundaries are clearly delineated. The tool can be used to help organizations with buildings located in multiple regions to strategically identify where to install rainwater harvesting systems and prioritize locations that may be optimal for rainwater harvesting.

47 OTHER INSTRUMENTATION↗

Performance study of a novel dew point evaporative cooler in the climate of central Europe using building simulation tools

This paper presents the performance research of a hybrid air conditioning system (System II) equipped with novel dew point evaporative cooler (DPIEC) for a retail building located in temperate climatic conditions. The new cooler has a dedicated, adaptable structure that maximizes its performance in the climate conditions of central Europe. The unit can operate as a typical regenerative air cooler when outdoor air is drier than indoor air, it can operate as a counter-flow heat recovery unit when indoor conditions are more dry than outdoor and it can operate as a combination of both arrangements. The year-round, hourly-stepped building energy simulations were carried-out using a prognostic tool of energy consumption. The novel dew point evaporative cooler application potential was established using the black-box model based on regression equations was established based on experimental tests on a prototype of novel DPIEC. The hybrid system operation was compared to the typical air handling unit equipped with a standard energy wheel for heat recovery (System I). Presented research shows that DPIEC can cover about 95% of total cooling loads while the energy wheel covers only 9% of total cooling load. System II allows us to save 65% of seasonal electricity consumption comparing to System I. It comes from the fact that during most of the cooling season DPIEC is in operation and it covers most of the cooling loads without the need to switch the chilled water system.

Air conditioning↗

Review of the potential and challenges of MOF-based adsorption heat pumps for sustainable cooling and heating in the buildings

Heat pumps are regarded as the most suitable means to meet the future demand of heating and cooling in the building, as they require small input of electrical energy and output high thermal energy. Vapor compression heat pump (VCHP) and transcritical-CO 2 heat pump are the two major heat pump technologies currently dominating the market. However, VCHP system suffers from its fugitive emission of hydrofluorocarbon (HFC) refrigerants, and transcritical-CO 2 system requires high operating pressure (typically 9–13 MPa). For low-to-medium temperature heating and cooling applications thermally driven adsorption heat pump (AHP) provides a better alternative to VCHP and transcritical-CO 2 system as AHP uses natural refrigerants and operates at a much lower pressure. But currently available AHP technology has the limitation of low coefficient of performance (COP). Advances in synthesizing metal-organic frameworks (MOF) with high gas adsorption capacity have created an opportunity to address the problem of low COP of current AHP technology. Here, this article reviews the progress made in the past decade in utilizing MOF and conventional adsorbents with different working fluids in AHP technology and compares their performance. The article also summarizes the key challenges for the MOF-based AHP technology and provides the authors’ perspective to address these challenges.

30 DIRECT ENERGY CONVERSION↗

Decarbonizing the U.S. Economy by 2050: A National Blueprint for the Buildings Sector

Residential and commercial buildings are among the largest sources of carbon dioxide and other greenhouse gas (GHG) emissions in the United States, responsible for more than one-third of total U.S. GHG emissions. There are nearly 130 million existing buildings in the United States, with 40 million new homes and 60 billion square feet of commercial floorspace expected to be constructed between now and 2050. Today, most buildings consume large amounts of energy and cause significant climate pollution to meet our basic needs. Buildings account for 74% of U.S. electricity use and building heating and cooling drives peak electricity demand. Moreover, buildings are where electric vehicles (EVs), solar, storage, heat pumps, water heaters, and other distributed energy resources integrate with the electricity system. Consequently, the buildings sector will play a key role in achieving economywide net-zero emissions by 2050.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Draft Environmental Impact Statement for Proposed Energy Conservation Standards for Manufactured Housing

This draft environmental impact statement (EIS) analyzes the impacts related to DOE’s proposed energy conservation standards for manufactured homes. DOE’s proposed energy conservation standards are based on the 2021 International Energy Conservation Code (IECC) and relate to the building thermal envelope; air sealing; installation of insulation; duct sealing; heating, ventilation and air conditioning (HVAC); service hot water systems; mechanical ventilation fan efficacy; and heating and cooling equipment sizing. The draft EIS evaluates DOE’s proposed action (energy conservation standards tiered based the manufacturers retail list price), alternatives to the proposed action (including energy conservation standards tiered based on size of the manufactured home and untiered standards), and a no action alternative. The draft EIS presents analysis of impacts related to (1) energy resources; (2) air resources (including greenhouse gases, climate change, ambient air quality and indoor air quality); (3) health and safety; (4) socioeconomics; and (5) environmental justice.

MacDonell, Margaret↗

Dynamic Facade Dashboard v0.1.0

The dashboard is a useful tool for early-stage building design decision-making and communication, as it can help users quickly compare the energy and non-energy related performance of various automated, integrated facade systems using a library of pre-computed data. Users can explore the impacts of various design choices by selecting different facade glazing and shading systems, facade control strategies, and lighting control strategies across multiple climate zones. The dashboard instantly visualizes key metrics, including energy usage in HVAC and lighting, peak cooling and heating load, and daylight availability, allowing immediate trade-off analysis to optimize building efficiency and comfort.

Yu, Tammie [Lawrence Berkeley National Laboratory ↗

High Temperature, Isothermal Growth Promotes Close Packing and Thermal Stability in DNA-Engineered Colloidal Crystals

Here, we report a strategy to accelerate the synthesis and increase the crystallinity of colloidal crystals engineered with DNA. Specifically, by holding the DNA-modified Au particle building blocks above the T m of the individual nanoparticle building blocks, but slightly below the T m of the anticipated colloidal crystal during the assembly process, crystallinity is increased, and enthalpically-favored phases with high degrees of facet registration are observed. We studied the utility of this approach with systems for which the commonly adopted slow-cooling approach yielded primarily amorphous aggregates. In particular, we used it to synthesize high-volume fraction colloidal crystals from large (80 nm) anisotropic nanoparticles (cubes and rhombic dodecahedra) with short (<14 nm) DNA designed to restrict the degrees of freedom for the DNA bonds and maintain the anisotropy of the particle building block. Small-angle X-ray scattering and electron microscopy studies show that the crystalline phases synthesized via this method are more thermally stable than their corresponding aggregate phases, likely due to an increased number of DNA-DNA bonds between particles. Crystal size tunability (between 0.5 and 15 µm edge lengths) and epitaxial growth were demonstrated using this strategy by modulating the NaCl concentration in tandem with previously synthesized colloidal crystal nuclei. Taken together, this isothermal strategy provides a route to deliberately crystallize a wide variety of anisotropic colloidal materials and expands the phase space accessible to nanoparticles modified with DNA.

37 INORGANIC, ORGANIC, PHYSICAL, AND ANALYTICAL CH↗

MPC solution for optimal load shifting for buildings with ON/OFF staged packaged units: Experimental demonstration, and lessons learned

Small and medium-sized commercial buildings (SMCB) are significant demand response resources, and it is important to develop grid-responsive control algorithms that exploit those resources and create financial benefits for building owners and HVAC service providers. Furthermore, unlike large-sized commercial buildings, there is an opportunity to have universally applicable control solutions for many SMCBs since those buildings have a consistent HVAC system configuration: SMCBs are commonly served by multiple-staged air conditioning units controlled by their own thermostats. Despite the demand response potential and scalability, however, very few control solutions are available for SMCBs. Typical model predictive control (MPC) and heuristic control approaches for cooling load shifting that lower thermostat setpoints before an electric price jump are suitable mainly for large-sized commercial buildings where a continuous capacity modulation is possible, e.g., via dampers in variable air volume terminal units. However, those approaches can cause undesired, high peaks for SMCBs due to the nature of ON/OFF unit staging and narrow thermostat deadbands. This could discourage the use of advanced grid-responsive controls for SMCBs due to the concern of high demand charges, and has to be resolved. This paper presents a MPC solution that overcomes this challenge. It has a hierarchical MPC structure where an upper level MPC is responsible for electrical load shifting in response to an electric price signal while a lower level MPC is responsible for coordinating compressor stages to eliminate unnecessary peaks and follows the setpoints determined by the upper level MPC. In this work, two one-month, comprehensive laboratory tests have been carried out to demonstrate load shifting and cost savings for the algorithm. Interesting trade-offs between energy efficiency and load flexibility were observed and are discussed, and lessons learned for applying MPCs for SMCBs are also presented.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Machine learning based simultaneous control of air handling unit discharge air and condenser water temperatures set-point for minimized cooling energy in an office building

In this study, an artificial intelligence based real-time prediction and control model to optimize condenser water temperature and discharge air temperature (DAT) set-points in water-cooled air handling unit (AHU) system has been developed. EnergyPlus-MATLAB co-simulation has been conducted to analyze the developed model's effectiveness. Here, to develop artificial neural networks (ANN) model, embedded neural network objects in MATLAB was utilized. The developed model could decide an optimal temperature set-points based on outdoor air wet-bulb temperature to reflect the Korean climate context. As a result, the developed ANN prediction model showed the predictive performance of Cv(RMSE) of approximately 21%. Compared to the conventional fixed temperature algorithm, which fixes AHU DAT at 14°C and condenser water temperature at 32°C, the ANN based optimized control showed a 22% total cooling energy reduction. These results show that significant energy savings can be achieved by simultaneously controlling condenser water temperature and AHU DAT set-points considering Korean climatic characteristics using AI technologies such as ANN models.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impact of refrigerant undercharge faults on building indoor conditions and HVAC system operation in residential Buildings: A simulation study

This study investigates the impact of refrigerant undercharge on indoor temperature and HVAC system performance in residential buildings. Simulation models for typical residential buildings in Orlando, FL and Indianapolis, IN were developed using the ResStock database. A refrigerant undercharge fault model was then applied to the simulations with varying levels of fault intensity. The paper offers an extensive analysis, revealing that variations in supply air temperature, equipment runtime, and cooling energy consumption due to the level of refrigerant undercharge faults are notably significant on a summer representative day. Similarly, on a winter representative day, changes in supply air temperature and runtime are significant as well as changes in supplemental heat energy consumption. We find that occupants may remain oblivious to these faults during the cooling season, particularly when the HVAC system is oversized; in that case, supply air temperature data could help detect a fault. Another challenge is that during the heating season, when the supplemental heater operates, it is difficult to identify a refrigerant undercharge fault using only indoor and supply air temperature data. Finally, this study finds that supply air temperature, equipment runtime, and supplemental heater energy consumption data can help in detecting refrigerant undercharge faults.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

End-Use Savings Shapes Measure Documentation: Thermostat Control for Load Shedding in Large Offices

This documentation focuses on a single End-Use Savings Shape measure - thermostat control for load shedding. The thermostat control for load shedding measure applies heating and cooling temperature setpoint offsets for reducing the heating and cooling load during peak window. The measure takes daily peak load schedule inputs generated by the method "Dispatch Schedule Generation" described in the "Supplemental Documentation: Dispatch Schedule Generation for Demand Flexibility Measures" to determine the start and end times of the peak window, and then adjusts the thermostat cooling and/or heating setpoints by an offset value from original schedules during the peak window to reduce the HVAC or whole building daily peak load. The measure is flexible and allows users to adjust the heating and cooling offset values respectively, but for this study, the adjustment for heating and cooling setpoints are set to -2 degrees Celsius and +2 degrees Celsius by default. The measure provides options of adding rebound control period (default 2 hours) after peak windows for the setpoints to be ramped back to default values, to prevent the system from generating higher peak demand with step changes of setpoints in post-peak periods . This measure is applicable t o large offices equipped with electric HVAC system (either electric cooling only or both electric heating and cooling), which account for approximately 8.72% of the ComStock floor area. The thermostat control for load shedding measure demonstrates 2-5% daily peak demand reduction and 0.068% total site energy savings (3 trillion British thermal units [TBtu]) for the U.S. commercial building stock modeled in ComStock.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A prototype cooling blanket for mitigating occupant overheating risk in a hot indoor environment: Modeling and assessments

Conventional ways of cooling a room or an entire house for occupant thermal comfort during summer consume a significant amount of energy and are vulnerable to overheating risk during power outages that lead to loss of cooling system operations. This study investigates a low-power cooling blanket, as a Personal Cooling System (PCS), that covers the upper human body for direct cooling during a five-day heat wave in a single-family house. A modeling framework is developed for evaluating the thermal and energy performance of the cooling blanket, which builds upon the co-simulation of three models: a house energy model, a personal thermal comfort model, and a cooling blanket model. Simulation results show that under the power outage scenario, the cooling blanket can greatly reduce the occupant heat stress with a reduction of daily hours of exceedance (discomfort hours defined as TSV>2) by up to 17.2 h (a 95.3 % improvement from the baseline power outage without the blanket). The cooling blanket, equipped with an innovative electrocaloric heat pump (COP as high as 10.1) consumes 6.31 W and can be operated by a portable battery for several days. The cooling blanket consumes only 0.28 % of the electricity of a central air-conditioning system running to provide cooling for the whole house during the five-day heatwave period. The findings justify further research of electrocaloric wearable PCS as low-power effective cooling to ensure thermal survivability of occupants during extreme indoor environments.

Electrocaloric heat pump↗

A Scalable Hardware-and-Human-in-the-Loop Grid-interactive Efficient Building Equipment Performance Dataset

This project developed a publicly available, high-fidelity dataset about the interactions among humans, homes, and heat pumps supporting grid interactive efficient buildings to balance demand on the grid with comfort for occupants. Laboratory measurements and simulations of the hardware capture the second-scale electric power dynamics of heat pumps providing grid services like load shifting and load shedding. Field measurements, behavior tracking, and qualitative surveys of people in their homes over multiple years—including experimentally adjusting the heating and cooling system to provide grid services—to capture the reciprocal effect of human behavior on grid services, and grid services on human comfort. Taken together, these data capture the complete Hardware and Human in the loop system for residential heat pumps, reducing large uncertainties in simulation for design, and models for control of heat pumps, and grid-interactive buildings.

24 POWER TRANSMISSION AND DISTRIBUTION↗

PHASE CHANGE MATERIAL FOR THERMAL ENERGY STORAGE IN BUILDINGS BASED ON SODIUM SULFATE DECAHYDRATE AND DISODIUM HYDROGEN PHOSPHATE DODECAHYDRATE

The worldwide increasing energy demand and 2050 net zero carbon target urge the globe to solve the energy challenge. Thermal Energy Storage (TES) has received significant attention in recent years as TES can be integrated into heating, ventilation, and air-conditioning systems where the energy would be stored during low-demand times and dispatched during high-demand times, resulting in controlling the peak load and improving energy savings. Material development is an integral part of TES. Salt hydrates are appealing due to cost-effectiveness, low- to no toxicity, and their high melting enthalpy, where energy is stored as latent heat. However, most salt hydrates are prone to incongruent melting (i.e., phase separation upon melting), which results in poor stability and large supercooling. In this study, we produced a highly stable novel energy storage material at a composition of 32 wt% sodium sulfate decahydrate, 52 wt% sodium phosphate dibasic dodecahydrate, 12 wt% milled expanded graphite, and 4 wt% borax. The material has a melting temperature of 28°C and an energy storage capacity of 167 kJ/kg with a supercooling of less than 3°C. The system showed no loss in energy storage performance after 150 cycles. The findings suggest that the novel energy storage material developed in this might be utilized in building heating and cooling applications.

Turnaoglu, Tugba↗

Energy Demand Management in Buildings Using PCM-Integrated Wall

The buildings in the United States annually consume nearly 40% of total U.S. energy consumption and approximately 75% of U.S. electricity consumption. Almost half of the total U.S. energy consumption in buildings is attributed to the space conditioning through Heating, Ventilation, and Air Conditioning (HVAC) systems. Utilizing thermal energy storage in buildings, particularly integrating phase change material (PCM) in the walls, has been reported to be an effective method of managing the space heating and cooling loads. This presentation covers an in-depth discussion on the integration of a PCM to building walls, the key conditions required for effective utilization of the PCM, and effect of the PCM transition temperature and the PCM location on energy-saving potential of the PCM-integrated wall.

building↗