Solar-heated ranger station--Glendo, Wyoming

Report evaluates solar-energy system in residential ranger station. Installation provided 22 percent of space-heating and 58 percent of hot-water energy requirements. Annual net energy savings were 30 million Btu. Report describes system and its subsystems: collector array, storage, hot-water, and space-heating. Average weather conditions of test site, performance values, and energy savings are listed.

Source record↗

Solar-Heated Water at a Motel--Mobile, Alabama

Solar-assisted hot-water system for a new 122-unit motor inn in Mobile, Alabama, generates more than half the energy needed for hot-water heating at motel each year. System consists of 93 flat-plate collectors, 2,500 gallon (9,500 1) insulated storage tank located outdoors, heat exchangers and controls. Electronic thermometers, measuring the temperatures at 22 locations monitor system performance.

Source record↗

Solar heating and cooling systems design and development

The development of twelve prototype solar heating/cooling systems, six heating and six heating and cooling systems, two each for single family, multi-family, and commercial applications, is reported. Schedules and technical discussions, along with illustrations on the progress made from April 1, 1977 through June 30, 1977 are detailed.

Source record↗

Solar heating for an observatory--Lincoln, Nebraska

Report describes solar-energy system for 50 seat observatory that provides 60 percent of space heating needs. System includes 9 flat-plate collectors, rock storage bin, blowers, controls, ducting, and auxiliary natural-gas furnace; it has five operation modes. Net energy savings were 11.31 million Btu for 12 months, or equivalent of 1.9 barrels of oil. Report appendixes list performance factor definitions, performance equations, and average area weather conditions.

Source record↗

Heliostat Sizing Methodology for Solar Heat for Industrial Processes

This study presents a method to obtain a heliostat size that minimizes the levelized cost of a heliostat-based concentrating solar thermal system for industrial process heat (IPH) applications at operating temperatures from 565 to 1550 degrees Celsius. The method extends prior work by embedding a routine for system design that obtains near-optimal subsystem sizes, increasing the fidelity of drive cost functions, and adding an optical performance model. An illustrative business case is developed for Daggett, California, targeting specified annual thermal energy outputs of 50 to 400 GWhth. Optical performance is modeled using verified estimates from the literature. A surrogate heliostat cost model, derived from commercial heliostat designs and scaled for production volume, installation, and operations and maintenance costs, is used to develop cost functions. Results show that heliostat size strongly affects the levelized cost of heat (LCOH), producing a characteristic U-shaped trend with a robust near-optimal window of 8 - 12 m2; the heliostat size producing the lowest project cost in our study grows slightly as the project size increases, and is reduced as the operating temperature increases. The findings in this study are consistent with the general trend of smaller heliostats under deployment at existing projects for high-temperature industrial process heat and reflect the significant reduction in power electronics and other per-heliostat costs. The methodology we propose is general and can be tailored to revised cost curves as the technology continues to evolve.

14 SOLAR ENERGY↗

Prototype solar heating and hot water systems

Progress made in the development of a solar hot water and space heating system is described in four quarterly reports. The program schedules, technical status and other program activities from 6 October 1976 through 30 September 1977 are provided.

Source record↗

Solar Heating System installed at Belz Investment Company, Memphis, Tennessee

A hot air solar system which utilizes flat plate air collectors is discussed. Collector areas for each of four buildings cover 780 sq ft, with storage capacity of 390 cu ft per building. The air system has a special air handling unit to move air through the collectors and into and out of the rock storage, with connection to the air duct distribution system. The heat of the motor is added to the heat delivered to the system. The solar system also includes four motorized special low leakage dampers and two gravity fabric dampers. The system is automatically controlled by a solid state controller with three thermistors: one located in the collectors, one in the rock box to plenum, one in the return air duct from the heated space. A three stage heating thermostat, located in the conditioned space, controls the operation.

Source record↗

Solar heating and cooling technical data and systems analysis

The acquisition and processing of selected parametric data for inclusion in a computerized Data Base using the Marshall Information Retrieval and Data System (MIRADS) developed by NASA-MSFC is discussed. This data base provides extensive technical and socioeconomic information related to solar energy heating and cooling on a national scale. A broadly based research approach was used to assist in the support of program management and the application of a cost-effective program for solar energy development and demonstration.

Christensen, D. L.↗

Solar-heating system-performance tests

Report describes comprehensive performance tests of complete solar powered space and hot water heating system to verify its suitability for field installation in small single family dwellings.

Source record↗

Solar heating and domestic hot water system installed at North Dallas High School

The solar energy system located at the North Dallas High School, Dallas, Texas is discussed. The system is designed as a retrofit in a three story with basement, concrete frame high school building. Extracts from the site files, specification references for solar modification to existing building heating and domestic hot water systems, drawings, installation, operation and maintenance instructions are included.

Source record↗

Solar heating and cooling system installed at Columbus, Ohio

The Solar Energy System was installed as a part of a new construction of a college building. The building will house classrooms and laboratories, administrative offices and three lecture halls. The Solar Energy System consists of 4,096 square feet (128 panels) Owens/Illinois Evacuated Glass Tube Collector Subsystem, and a 5,000 gallon steel tank below ground storage system. Hot water is circulated between the collectors and storage tank, passing through a water/lithium bromide absorption chiller to cool the building.

Source record↗

Solar-Heated and Cooled Office Building--Columbus, Ohio

Final report documents solar-energy system installed in office building to provide space heating, space cooling and domestic hot water. Collectors mounted on roof track Sun and concentrate rays on fluid-circulating tubes. Collected energy is distributed to hot-water-fired absorption chiller and space-heating and domestic-hot-water preheating systems.

Source record↗

Solar heating and domestic hot water system installed at Kansas City, Fire Stations, Kansas City, Missouri

The solar system was designed to provide 47 percent of the space heating, 8,800 square feet area and 75 percent of the domestic hot water (DHW) load. The solar system consists of 2,808 square feet of Solaron, model 2001, air, flat plate collector subsystem, a concrete box storage subsystem which contains 1,428 cubic feet of 0.5 inch diameter pebbles weighing 71.5 tons, a DHW preheat tank, blowers, pumps, heat exchangers, air ducting, controls and associated plumbing. Two 120 gallon electric DHW heaters supply domestic hot water which is preheated by the solar system. Auxiliary space heating is provided by three electric heat pumps with electric resistance heaters and four 30 kilowatt electric unit heaters. There are six modes of system operation.

Source record↗

Solar heating, cooling and domestic hot water system installed at Columbia Gas System Service Corporation, Columbus, Ohio

The solar energy system installed in the building has 2,978 sq ft of single axis tracking, concentrating collectors and provides solar energy for space heating, space cooling and domestic hot water. A 1,200,000 Btu/hour water tube gas boiler provides hot water for space heating. Space cooling is provided by a 100 ton hot water fired absorption chiller. Domestic hot water heating is provided by a 50 gallon natural gas domestic storage water heater. Extracts from the site files, specification references, drawings, installation, operation and maintenance instructions are included.

Source record↗

Solar heating and cooling system for an office building at Reedy Creek Utilities

The solar energy system installed in a two story office building at a utilities company, which provides utility service to Walt Disney World, is described. The solar energy system application is 100 percent heating, 80 percent cooling, and 100 percent hot water. The storage medium is water with a capacity of 10,000 gallons hot and 10,000 gallons chilled water. Performance to date has equaled or exceeded design criteria.

Source record↗

Solar-heating system performance tests

Report contains results of performance tests on complete system for solar space and hot-water heating system that uses commercially available components. Results were used to determine system suitability for field installation and to generate performance data base for comparison with future tests on field installed systems.

Source record↗

Solar heating for an electronics manufacturing plant--Blue Earth, Minnesota

Partial space heating for 97,000 square foot plant is supplied by 360 flat plate solar collectors; energy is sorted as heat in indoor 20,000 gallon water tank. System includes all necessary control electronics for year round operation. During December 1978, solar energy supplied 24.4 percent of building's space heating load.

Source record↗