Reconfigurable Real-Time Power Grid Emulator for Systems With High Penetration of Renewables

Novel power system control and new utility devices need to be tested before their actual deployment to the power grid. To assist with such a testing need, real-time digital emulators such as RTDS and Opal-RT can be used to connect to the physical world and form a hardware in the loop (HIL) emulation. However, due to the limitations of today's computational resources, the accuracy and fidelity suffer from different levels of model reductions in purely digital simulations. CURENT has developed a reconfigurable electric grid hardware testbed (HTB) to overcome the limitations of digital emulators. The HTB has been used to develop measurement, control, modeling, and actuation techniques for a national grid with a high penetration of renewables. The power electronic-based system includes emulators for synchronous generators; photovoltaics with grid-interfacing inverter; wind turbines; induction motor loads, ZIP loads, power electronic loads; batteries; ac and dc transmission lines; short circuit faults and grid relay protection; and a multiterminal HVDC overlay including power electronics interfaces. The system contains real elements of power flow, measurement, communication, protection, and control that mimic what would be seen in an actual electric grid. This paper presents an overview of the HTB and several scenarios that have been run to determine control and actions needed for the future power grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Multi-Site Networked Hardware-in-Loop Platform for Evaluation of Interoperability and Distributed Intelligence at Grid-Edge

Electric power systems have experienced large increases in the number of intelligent, connected and controllable devices being deployed, leading to a high degree of distributed intelligence at the grid-edge. These devices, both utility-owned and consumer-owned, include but are not limited to: renewable generation sources, energy storage, remote switches, voltage regulators, and smart controllable loads such as electric vehicles. These new devices provide significant potential for increased operational flexibility that can be leveraged to achieve system reconfiguration, resiliency improvements, power quality improvements, and distribution system automation. However, there are two significant challenges that must be addressed before these assets can be leveraged for operations: interoperability and system level validation prior to deployment. Because of the complexity of distributed control systems, and their interactions with legacy centralized controls, a purely simulations-based approach for pre-deployment validation is not sufficient. It requires hardware-in-loop testing to emulate the operational hardware devices and evaluate their performance. Additionally, securely integrating multiple test facilities at utility operators and vendors might enable rapid scale-up of evaluation platforms, and remove the need for multiple expensive standalone installations. Presented in this paper, is the development of a multi-site evaluation platform that employs Advanced Distribution Management Systems (ADMS), distributed control devices, real-time hardware-in-loop assets, secure communication links, and protocol adapters. This platform uses standards-based approaches and open-source tools, and hence can serve as a template for other researchers and institutions to implement their multi-site evaluation frameworks for pre-deployment testing.

Essakiappan, Somasundaram↗

PV Inverter Testing for Momentary Cessation and Rate-of-Change-of-Frequency Events: Preprint

To understand the power system stability and develop better electromagnetic transient (EMT) models of field deployed photovoltaic (PV) inverters, it is important to characterize inverters' response to abnormal voltage and frequency scenarios. Because EMT models are not typically available for small distribution-connected PV inverters, and because inerterconnection standards historically did not specify desired ride-through behaviors, we tested two such inverters in the lab to characterize their responses to severe undervoltage events and high rate-of-change-of-frequency (ROCOF) conditions. The inverters tested were pre-IEEE 1547-2018 residential PV inverters widely used in the Hawaiian Electric territory and many other areas. The testing results for undervoltage scenarios showed that the inverter from one vendor exhibited momentary cessation while the inverter from the other vendor did not exhibit momentary cessation behavior or tripping for most of the events below the 120 ms undervoltage trip threshold duration set by IEEE 1547-2003. The testing results for ROCOF scenarios showed that the inverter from one vendor temporarily lost synchronization during ROCOF conditions while the inverter from the other vendor did not lose synchronization or cease generation for any ROCOF conditions. Both the inverters were also tested for EMT-simulated grid events with severe changes in frequency and voltage. The observed responses of the inverters were different from the simulated response of PV inverters represented the best available assumptions from pre-existing information. The results from these experiments can be used to update the inverter models used in bulk power system studies.

IEEE 1547 2018↗

PV Inverter Testing for Momentary Cessation and Rate-of-Change-of-Frequency Events

To understand the power system stability and develop better electromagnetic transient (EMT) models of field deployed photovoltaic (PV) inverters, it is important to characterize inverters' response to abnormal voltage and frequency scenarios. Because EMT models are not typically available for small distribution-connected PV inverters, and because inerterconnection standards historically did not specify desired ride-through behaviors, we tested two such inverters in the lab to characterize their responses to severe undervoltage events and high rate-of-change-of-frequency (ROCOF) conditions. The inverters tested were pre-IEEE 1547-2018 residential PV inverters widely used in the Hawaiian Electric territory and many other areas. The testing results for undervoltage scenarios showed that the inverter from one vendor exhibited momentary cessation while the inverter from the other vendor did not exhibit momentary cessation behavior or tripping for most of the events below the 120 ms undervoltage trip threshold duration set by IEEE 1547-2003. The testing results for ROCOF scenarios showed that the inverter from one vendor temporarily lost synchronization during ROCOF conditions while the inverter from the other vendor did not lose synchronization or cease generation for any ROCOF conditions. Both the inverters were also tested for EMT-simulated grid events with severe changes in frequency and voltage. The observed responses of the inverters were different from the simulated response of PV inverters represented the best available assumptions from pre-existing information. The results from these experiments can be used to update the inverter models used in bulk power system studies.

aggregates↗

Recent Improvements in the Beam Capture at Fermilab Booster for High Intensity Operation

The Fermilab Booster uses multi-turn beam injection with all its cavities phased such that beam sees a net zero RF voltage even when each station is at the same maxi-mum voltage. During beam capture the RF voltage is increased slowly by using its paraphase system. At the end of the capture the feedback is turned on for beam acceleration. It is vital for present operations as well as during the PIP-II era that both the HLRF and LLRF systems provide the proper intended phase and RF voltage to preserve the longitudinal emittance from injection to extraction. In this paper, we describe the original architecture of the cavity phase distribution, our recent beam-based RF phase measurements, observed significant deviation in the relative phases between cavities and correction effort. Results from the improved capture for high intensity beam are also presented.

43 PARTICLE ACCELERATORS↗

Three-Dimensional Grid Visualization for Planning Activities: A Dubai Case Study

National Laboratory of the Rockies (NLR), in collaboration with the Dubai Electricity and Water Authority (DEWA) and Infra-X, has undertaken the Energy Visualization Analysis Project. The aim of this project is to enhance analytical and 3D visualization capabilities for distribution network planning and renewable energy integration. As modern grid continues to evolve with large-scale solar PV deployment and emerging distributed energy resources (DERs), the ability to effectively analyze, visualize, and communicate complex grid behaviors has become increasingly critical. The project focuses on developing empirical use cases based on real distribution feeder data and engineering workflows, ensuring the outcomes are directly aligned with operational environment. Through time-series power flow simulations and nodal hosting capacity analysis, the study quantifies the impacts of high PV penetration on voltage and thermal limits within representative 11 kV feeders. These analyses identify specific nodes and conditions where DER integration challenges arise. Furthermore, a Battery Energy Storage System (BESS) optimization algorithm was applied to determine the optimal size and placement of storage systems that can mitigate network constraints and enhance hosting capacity. The comparative results between base-case and BESS-augmented scenarios clearly demonstrate improvements in network stability and load management efficiency. In parallel, the NLR team developed an immersive 3D visualization framework, enabling interactive exploration of grid simulations using commodity head-mounted display (HMD) systems. This framework transforms conventional 2D simulation data into spatially intuitive visual environments - allowing engineers to analyze feeder conditions, PV hosting potential, and BESS effects in real time. This report represents the first foundational phase in establishing a visualization-driven analytical ecosystem. It provides a methodological foundation for data integration, visualization architecture, and simulation-based decision support, paving the way for large-scale adoption of immersive visualization across DEWA's Smart Grid Initiative, R&D activities, and future network resilience studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Megawatt-Class, High-Voltage SiC Power Electronics Converters for Advanced Manufacturing with Grid Support Services

DE-EE0009135 aimed to push the 10kV SiC MOSFET based power electronics to 3-phase 13.8kV 10MW to be used as a Megawatt Class Medium-Voltage Power Conditioning Systems – PCS – to enable “Resilient Distribution through Grid-dispatching and Uninterrupted Quality Power to Manufacturing Facilities” during transitory grid disturbances. As a stretch to those goals, Eaton added the load power peak shaving opportunity.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Molecular-Level Control over Ionic Conduction and Ionic Current Direction by Designing Macrocycle-Based Ionomers

Poor ionic conductivity of the catalyst-binding, submicrometer- thick ionomer layers in energy conversion and storage devices is a huge challenge. However, ionomers are rarely designed keeping in mind the specific issues associated with nanoconfinement. Here, we designed nature-inspired ionomers (calix-2) having hollow, macrocyclic, calix[4]arene-based repeat units with precise, sub-nanometer diameter. In ≤100 nm-thick films, the in-plane proton conductivity of calix-2 was up to 8 times higher than the current benchmark ionomer Nafion at 85% relative humidity (RH), while it was 1-2 orders of magnitude higher than Nafion at 20-25% RH. Confocal laser scanning microscopy and other synthetic techniques allowed us to demonstrate the role of macrocyclic cavities in boosting the proton conductivity. The systematic self-assembly of calix-2 chains into ellipsoids in thin films was evidenced from atomic force microscopy and grazing incidence small-angle X-ray scattering measurements. Moreover, the likelihood of alignment and stacking of macrocyclic units, the presence of one-dimensional water wires across this macrocycle stacks, and thus the formation of long-range proton conduction pathways were suggested by atomistic simulations. We not only did see an unprecedented improvement in thin-film proton conductivity but also saw an improvement in proton conductivity of bulk membranes when calix-2 was added to the Nafion matrices. Nafion-calix-2 composite membranes also took advantage of the asymmetric charge distribution across calix[4]arene repeat units collectively and exhibited voltage-gating behavior. The inclusion of molecular macrocyclic cavities into the ionomer chemical structure can thus emerge as a promising design concept for highly efficient ion-conducting and ion-permselective materials for sustainable energy applications.

37 INORGANIC, ORGANIC, PHYSICAL, AND ANALYTICAL CH↗

Seismic Resilience of Large Power Transformer Bushings & Non-SF6 Industrial Base Scan Review

Large (high voltage) power transformers (LPT), and more specifically, their bushings, are known to be susceptible to seismic failure. With bushing failure, a transformer will have to be replaced, which has a considerable lead time, adding to the power outage duration. Cost-efficient, proven solutions are not currently available to mitigate this risk, which can persist for the more than 30-year life of a particular transformer. This work will focus on developing and demonstrating a hardware solution to address seismic vulnerabilities and reduce outage risks from LPT failure. Sulfur Hexafluoride (SF6) is a specialty gas with excellent electrical insulation properties which has been used extensively in the power industry. This gas is unfortunately also one of the most potent greenhouse gases known to humanity. A 2014 report by the Intergovernmental Panel on Climate Change found that SF6 has a global warming potential (GWP) 23,000 times higher than Carbon Dioxide, and has the highest GWP of all gases assessed (Myhre 2013). SF6 is almost exclusively man-made and is produced for use as an insulator in high voltage electrical equipment. This makes the production and use of SF6 one of the leading sources of anthropogenic climate change. To fully eliminate the environmental impacts of SF6, alternative technology is needed. The ideal replacement would be a technology that can fulfil the same role as SF6, at the same cost or cheaper, but without adverse environmental effects. Currently, no technology fits this description, however several promising technologies have begun to enter the market. An industry scan was performed to assess the state of industry adoption and manufacturing capability for SF6-free alternative technologies for use at the high-voltage level, and the primary barriers to broader adoption.

10 SYNTHETIC FUELS↗

Reese Housing Power Project (Final Technical Report)

The Reese Housing Power Project is located on Tribal trust land in Colusa, CA and expands existing medium-voltage distribution to seven new households with the addition of medium-voltage cabling, step down transformers, smart meters, and street lighting for the new development. The Tribe utilized their existing Co-Generation power plant and micro grid to supply the new homes with highly reliable power with fewer interruptions and at a reduced rate compared with the local utility. The project gives the Tribe greater independence from traditional power sources and provides jobs for the community. The project reduces electric energy costs, increases Tribe self-reliance, and provides highly reliable electric power to seven tribal members’ homes. Construction of the project also provided jobs for the community.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Moderate active Fe 3+ doping enables improved cationic and anionic redox reactions for wide-voltage-range sodium storage

Layered metal oxides are promising cathode materials for sodium-ion batteries (SIBs) due to their high theoretical specific capacity and wide Na + diffusion channels. However, the irreversible phase transitions and cationic/anionic redoxes cause fast capacity decay. Herein, P2-type Na 0.67 Mg 0.1 Mn 0.8 Fe 0.1 O 2 (NMMF-1) cathode material with moderate active Fe 3+ doping has been designed for sodium storage. Uneven Mn 3+ /Mn 4+ distribution is observed in NMMF-1 and the introduction of Fe 3+ is beneficial for reducing the Mn 3+ contents both at the surface and in the bulk to alleviate the Jahn–Teller effect. The moderate Fe 3+ /Fe 4+ redox can realize the best tradeoff between capacity and cyclability. Therefore, the NMMF-1 demonstrates a high capacity (174.7 mAh g -1 at 20 mA g -1 ) and improved cyclability (78.5% over 100 cycles) in a wide-voltage range of 1.5–4.5 V (vs. Na + /Na). In-situ X-ray diffraction reveals a complete solid-solution reaction with a small volume change of 1.7% during charge/discharge processes and the charge compensation is disclosed in detail. This study will provide new insights into designing high-capacity and stable layered oxide cathode materials for SIBs.

25 ENERGY STORAGE↗

Simplified calculation of the area specific impedance for solid-state battery design

Simplified algebraic area specific impedance (ASI) correlations have been developed for solid-state composite battery electrodes made of a single ion conducting electrolyte, conductive additive, and intercalation active material. Two ASI expressions were developed, one for short times ( i.e. , pulsed power operation) and another for the pseudo steady state operation (i.e., sustained discharge for energy estimation). A full electrochemical model based on porous electrode theory was developed to examine the accuracy of the simplified ASI expressions. The simplified expressions agree favorably with full model results over a wide range of parameters (i.e. , electrode thicknesses, electrolyte conductivities, solid-state diffusion coefficients, specific surface areas, etc.) and conditions (i.e. , C-rates, states of charge, and pulse times). Under most conditions, the error between the full model and the correlations is well below 7 %. Higher errors were observed for the pseudo steady state expression at high/ low states of charge where the assumption of uniform reaction distributions loses validity. Here, the short time ASI has higher error at low states of charge due to the nonlinearity of the open circuit voltage equation, which is assumed linear in the formulation of the simplified algebraic expression.

25 ENERGY STORAGE↗

Hierarchical Control and Stability Analysis for a Nonisolated Grid-Tied DC Energy Router Integrating Energy Storage and Partial Distributed Generation

This article proposes a nonisolated dc converter-based energy router (dc-ER) and its operating strategy. Here, the intent is to integrate energy storage (ES), distributed generation (DG), local load, and dc power grid in an autonomous and more efficient way. The ES/DG power ports are coupled with each other in partial-type connections, which obtains higher voltage supply gain and direct input–output power transmission. High-voltage supply gain allows a wide solar power tracking range and the possibility of optimal battery charging/discharging. Direct input–output power transmission improves the energy conversion efficiency. In this article, the operating modes of dc-ER are first analyzed, followed by the optimal hardware design counting the DG current ripple minimization and the limitation caused by the power flow direction. Second, the mathematical model of dc-ER is deduced. The hierarchical control is then proposed to manage port energy in a flexible manner. The stability is analyzed by using impedance modeling. Finally, experimental and simulation results verify the superiorities of the proposed topology in terms of flexible operating mode transition and high-power conversion efficiency.

25 ENERGY STORAGE↗

Dynamically robust coordinated set point tracking of distributed DERs at point of common coupling

Low-inertia operation of small-scale power systems, such as a microgrid or a portion of a long feeder, requires careful coordination of the controller performance of the constituting devices. This challenge is exacerbated in microgrids serving the functionalities of a conventional synchronous-based generation unit while comprised of smaller DERs operating mainly interfaced through power electronics converters. This paper builds on the idea of set point modulation and proposes a two-level control strategy that aims to achieve superior performance at the point of common coupling (PCC) of microgrids by combining a local control level with a distributed and coordinated level. Several case studies on both AC and DC systems, the CIGRE low-voltage benchmark system as the AC system and a test DC microgrid, validate the performance of the proposed approach. The real-world applicability of the approach is established via a high-fidelity power hardware-in-the-loop (PHIL) experimental setup and an application case study on grid frequency regulation. The proposed approach enables a microgrid to participate in ancillary service provisions where speed and quality of regulation are critical.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Dynamic Building Load Control to Facilitate High Penetration of Solar Photovoltaic Generation (Final Technical Report)

Solar photovoltaic (PV) resources are the most common form of distributed generation in residential and commercial customer premises within electric distribution networks. A higher penetration of PV generation in distribution circuits will impose challenges on maintaining service voltages within the range of industry standards, power quality, and power flow. Buildings consume 74% of the electricity produced in the United States, and a significant portion of the building load is dispatchable, making them responsive to electrical grid needs. Oak Ridge National Laboratory—in collaboration with Southern Company; the University of Tennessee, Knoxville; and the Georgia Institute of Technology—is examining the PV integration issues in distribution-level electrical grids and developing integrated demand-side control and communication systems to enable responsive loads. The proposed responsive loads mechanism performs renewable generation following to increase the penetration of solar PV within each feeder. The specific objectives of this project are to (1) examine distribution-level PV integration scenarios to understand requirements, (2) undertake an end-to-end simulation-based design of a distributed control strategy of loads geographically near the PV generation asset to minimize the effect on the distribution feeder, (3) deploy and demonstrate the control technology developed in partnership with utilities, and (4) perform a scalability analysis at the utility scale. This 3-year integrated project aims to develop, demonstrate, and validate demand-side control technology to enable increased the penetration of renewables while mitigating challenges that arise due to their intermittency. Activities in Budget Period (BP) 1 focused on a literature review and the formal design of a control system for integrating local distribution with generation and loads. The team used modeling and simulation to evaluate the impact of varying buildings loads, variable PV generation, and power flow dynamics on the distribution circuit. The dynamic models developed in BP 1 were used in BP 2 to develop a model-based control design and a test bed. The test bed has enabled the simulation-based testing and comparison of different control designs and formulations applied to different configurations of the distribution grid, PVs, and building loads. The control approaches developed in BP 2 were implemented in BP 3 in the form of hardware deployed at the Central Baptist Church (CBC) in Knoxville, Tennessee, for testing and evaluation. The outcome of this project was the development and demonstration of open-source, low-cost, low-touch sensing and control retrofits to distributed PV generation and building loads that, in a coordinated fashion, provide the load-shaping response needed to integrate high levels of renewable penetration. This research addresses the target metrics by dynamically controlling a load with solar generation variability to minimize the extent of two-way power flow, enhance reliability, facilitate high PV penetration (>100% of peak load in a line segment), and generate scalable software and hardware solutions adaptable to any penetration levels. The research and development activities are focused and designed to be impactful within the relevant 2020 targets time frame.An accurate open-source integration simulation framework for end-to-end control design was developed and deployed at the CBC facility for testing and evaluation. This final report provides a detailed review of the technical results achieved during this 3-year integrated project. A novel spectral analysis of PV data is demonstrated to derive the requirements of the control design. A detailed simulation-based analysis of PV integration at increasing penetration levels is presented using 1 year of PV data to demonstrate the impact on the distribution circuits. Two different control strategies were developed and demonstrated via simulation to track variable PV generation with adaptive load dispatch. The report concludes with a summary of accomplishments and recommendations for a path forward.

14 SOLAR ENERGY↗

Stacked Low-Inertia Converter or Solid-State Transformer: Modeling and Model Predictive Priority-Shifting Control for Voltage Balance

This paper presents control challenges of stacked low-inertia converter (SLIC) or cascaded reduced dc-link solid-state transformer (SST) and proposes a novel model predictive priority-shifting (MPPS) control with implicit modulator and a discrete-time large-signal model for voltage balancing and dc-link regulation. Low-inertia converters, featuring small electrolytic capacitor-less dc links, dramatically reduce cost, size, and weight compared to conventional solutions. However, without a large dc-link buffer, the input and output are tightly coupled, leading to significant control challenges. The control becomes even more challenging with these converters stacked input-series output-parallel (ISOP) for medium-voltage (MV) grid, which causes coupling between the modules besides the coupling within each module. This paper analyzes the multi-objective, multi-degree of freedom control problem, using the modular soft-switching solid-state transformer (M-S4T) as an example of the SLIC. First, distribution of control efforts under controller saturation is critical because multiple control objectives can be conflicting, especially when the module voltages are unbalanced and are being restored. The MPPS can shift the priorities to address this issue. Second, due to the low inertia and high dc-link ripple, classic space vector pulse-width modulation (SVPWM), average model with small-ripple assumption, and control design based on small-signal model cannot accurately modulate, model, and control the nonlinear reduced dc link. Therefore, a discrete-time large-signal model of the M-S4T is established to derive the predictive control in the MPPS. The MPPS and the PI control are compared in MV simulations to show the issue of applying the PI to the SLIC and the effectiveness of the MPPS for voltage balancing and dc-link regulation in a deadbeat manner. Finally, the proposed control is tested on a 5 kV ISOP SiC SST prototype to verify priority shifting to address controller saturation issue and fast and robust voltage balancing.

14 SOLAR ENERGY↗

Selecting Critical Scenarios of DER Adoption in Distribution Grids Using Bayesian Optimization

We develop a new methodology to select scenarios of DER adoption most critical for distribution grids. Anticipating risks of future voltage and line flow violations due to additional PV adopters is central for utility investment planning but continues to rely on deterministic or ad hoc scenario selection. We propose a highly efficient search framework based on multi-objective Bayesian Optimization. We treat underlying grid stress metrics as computationally expensive black-box functions, approximated via Gaussian Process surrogates and design an acquisition function based on probability of scenarios being Pareto-critical across a collection of line- and bus-based violation objectives. Our approach provides a statistical guarantee and offers an order of magnitude speed-up relative to a conservative exhaustive search. Case studies on realistic feeders with 200-400 buses demonstrate the effectiveness and accuracy of our approach.

Mulkin, Olivier↗