Evaluation of Data-Enhanced Hierarchical Control for Distribution Feeders With High PV Penetration
Not Available
SEARCH · Engineering Papers
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Not Available
With support from the U.S. Department of Energy Solar Energy Technologies Office, the National Renewable Energy Laboratory (NREL) partnered with Xcel Energy, Schneider Electric, Varentec, and Electric Power Research Institute (EPRI) to meet the goals of the Enabling Extreme Real-Time Grid Integration of Solar Energy (ENERGISE) program. This project developed and validated an innovative data-enhanced hierarchical control architecture that enables the efficient, reliable, resilient, and secure operation of future distribution systems with a high penetration of distributed energy resources like solar energy. The architecture enables a hybrid control approach where a centralized control layer is complemented by distributed control algorithms for solar inverters and autonomous control of grid edge devices. It is fully interoperable and includes all the cybersecurity aspects necessary for reliable and secure system operation. The hybrid approach can seamlessly integrate multiple voltage-regulation technologies, both at central and grid-edge levels, which enables reliable and efficient system operation in the face of unpredictable conditions. The overarching goal of the Eco-Idea project is to develop, validate, and deploy a unique and innovative Data-Enhanced Hierarchical Control (DEHC) architecture that comprehensively addresses the formidable challenges associated with proliferation of high penetration of distributed PV such as reverse power flows, transients from variability of PV systems, feeder load balancing, and voltage stability. These issues are exposing the weaknesses of existing grid operations and controls - including, but not limited to, lack of grid situational awareness, heuristic and slow-acting control actions, latency of control for emergency situations, and points of failure in communications. The proposed architecture will comprehensively resolve the deficiencies of current operational settings - where monitoring and control solutions proposed across industry and academia may not be interoperable and may not coexist in the same system - and will enable an efficient, reliable, resilient, and secure operation of future distribution systems with penetration of solar energy well beyond current limits. The DEHC architecture was developed and validated rigorously through hardware-in-loop simulations in the laboratory environment and deployed on the field.
This paper presents a cyber-physical algorithm for grid interactive DER control to enable two features of Virtual Power Plants (VPPs) dispatch and grid voltage regulation, considering the communication and security impacts. We first formulate the DER dispatch problem as a real-time, iterative, and grid-interactive DER control problem. Thereafter, we consider a probabilistic traffic model to characterize packet delays and loss in a communication network, and study how the delays enter the process of information exchange among the grid measurement units, local DER controllers and the grid control center that coordinately execute this dispatch algorithm. Finally, we propose a cyber-physical grid-interactive DER control algorithm using the previous message strategy. The tracking and regulation capabilities of this proposed algorithm can be made immune to the asynchrony resulting from the communications network traffic. We carry out simulations to show possible numerical instabilities and sensitivities of the tracking and regulation capabilities on the proposed strategy. Our results exhibit that the uncertainties of the underlying communications infrastructure must be considered in the control algorithm for the VPP tracking and regulation capabilities of any DER in a generic Cyber-Physical System (CPS).
This paper investigates the impacts of electric vehicles (EVs) on power system frequency regulation based on an open-source transmission-and-distribution (T&D) dynamic co-simulation framework. The development of a EV dynamic model based on appropriate WECC dynamic model is introduced first, then the T&D dynamic co-simulation platform is described. The advantage of the overall platform is that DERs such as distributed photovoltaic (DPV) and EV are modeled explicitly in both transmission and distribution simulators for frequency dynamics and voltage, respectively. In the case studies, EVs frequency responses (i.e., primary and/or secondary) are simulated after the system is exposed to N-1 contingency such as a generation trip. Various EV frequency regulation participation strategies are investigated as well to study their impacts on system frequency response. The studies shows that EVs have potential capability to provide effective frequency regulation services.
This paper proposes a novel model-free/data-driven centralized training and decentralized execution multi-agent deep reinforcement learning (MADRL) framework for distribution system voltage control with high penetration of PVs. The proposed MADRL can coordinate both the real and reactive power control of PVs with existing static var compensators and battery storage systems. Unlike the existing DRL-based voltage control methods, our proposed method does not rely on a system model during both the training and execution stages. This is achieved by developing a new interaction scheme between the surrogate modeling of the original system and the multi-agent soft actor critic (MASAC) MADRL algorithm. In particular, the sparse pseudo-Gaussian process with a few-shots of measurements is utilized to construct the surrogate model of the original environment, i.e., power flow model. This is a data-driven process and no model parameters are needed. Furthermore, the MASAC enabled MADRL allows to achieve better scalability by dividing the original system into different voltage control regions with the aid of real and reactive power sensitivities to voltage, where each region is treated as an agent. This also serves as the foundation for the centralized training and decentralized execution, thus significantly reducing the communication requirements as only local measurements are required for control. Comparative results with other alternatives on the IEEE 123-nodes and 342-nodes systems demonstrate the superiority of the proposed method.
The purpose of this project is to provide a software platform that gives utility companies the capability to seamlessly dispatch legacy devices (at both the distribution and subtransmission levels) and distributed energy resources (DERs) to achieve system-wide performance and reliability targets–such as minimizing loss, reducing voltage violation, and corresponding imbalance–for extreme solar futures with well over 100% (capacity) penetrations.
This presentation highlights the key developments of the ARAP-e NODES project, including the innovative real-time optimal power flow (RT-OPF) algorithm for distributed energy resource (DER) management, trip planning for T+D coordination, and extensive validation of the RT-OPF algorithm in NREL ESIF laboratory with 100+ physical hardware devices, controller-hardware-in-the-loop test at Southern California Edison (SCE), and two field demonstrations.
This paper investigates the impacts of electric vehicles (EVs) on power system frequency regulation based on an open-source transmission-and-distribution (T&D) dynamic co-simulation framework. The development of a EV dynamic model based on appropriate WECC dynamic model is introduced first, then the T&D dynamic co-simulation platform is described. The advantage of the overall platform is that DERs such as distributed photovoltaic (DPV) and EV are modeled explicitly in both transmission and distribution simulators for frequency dynamics and voltage, respectively. In the case studies, EVs frequency responses (i.e., primary and/or secondary) are simulated after the system is exposed to N-1 contingency such as a generation trip. Various EV frequency regulation participation strategies are investigated as well to study their impacts on system frequency response. The studies shows that EVs have potential capability to provide effective frequency regulation services.
Distributed photovoltaic (PV) systems equipped with advanced inverters can control real and reactive power output based on grid and atmospheric conditions. The Volt-Var control method allows inverters to regulate local grid voltages by producing or consuming reactive power. Based on their power ratings, the inverters may need to curtail real power to meet the reactive power requirements, which decreases their total energy production. To evaluate the expected curtailment associated with Volt-Var control, yearlong quasi-static time-series (QSTS) simulations were conducted on a realistic distribution feeder under a variety of PV system design considerations. Overall, this paper found that the amount of curtailed energy is low (<; 0.55%) compared to the total PV energy production in a year but is affected by several PV system design considerations.
Due to the increasing penetration of distributed energy resources (DERs) required for the sustainable distribution system, new voltage control strategy is needed by utilities. Traditional voltage control strategy can not support the increasing number of DERs in a coordinated and scalable manner to meet the operational voltage regulation requirement. Supported by the power electronics converter, the energy storage system can provide fast, smooth, and flexible voltage control services. In this paper, an effective and easy to implement sensitivity-based voltage control strategy is developed for the energy storage system. The developed control strategy is validated using an industrial feeder data in Northwest Washington. The proposed strategy can mitigate the voltage unbalance issue, improve the voltage profile, and correct power factors while supporting sustainable distribution system operation.
In this paper, a state-space nonlinear control previously designed for balanced operation of grid-forming (GFM) inverters is extended to unbalanced operations. Unbalanced voltages and currents are analyzed, and their time-varying direct, quadrature, and zero components are parameterized in terms of six constant parameters. These parameters provide primary control design choices for not only an inverter’s terminal voltage but also its injections of both real and oscillatory power. It is shown that the proposed GFM control can precisely achieve a desired balanced terminal voltage under unbalanced loads. It is also shown that, by allowing the terminal voltage to be slightly unbalanced, oscillatory power can be adaptively minimized. Lastly, it is illustrated that oscillatory power can also be shared among multiple GFM inverters. Case studies and their simulations demonstrate that the proposed GFM control is effective in meeting the aforementioned objectives.
As feeder-level microgrid controls begin to incorporate multiple GFM DER and voltage regulation equipment, island reactive power dispatch strategies can be improved. Although Volt-Var Optimization (VVO) control is typical in an Advanced Distribution Management System (ADMS), most microgrid controllers do not apply VVO during island operations. This report investigates reactive power control strategies for feeder-level microgrid operations. It also proposes evaluation metrics that can be applied to analyze the performance improvements of the new microgrid control strategy.
To facilitate the implementation of distributed energy resource management systems (DERMS), we propose to insert a grid-edge distributed energy resource (DER) chip hosting a DERMS algorithm into the next generation of smart meters. This will create a pathway for the wide adoption of DERMS technology because many utilities plan to invest in advanced metering infrastructure in the near future. This will also bridge the gap between an electrical power utility and DERs behind the meter. The DER chip is designed to follow power direction signals from the DERMS coordinator while balancing its local objectives. We tested the chip using a controller- and power-hardware-in-the-loop evaluation under three scenarios that a DERMS could face in the real world. The DER chip was capable of and effective at directing four heterogeneous DERs to respond to a DERMS coordinator for grid services (e.g., voltage regulation and a virtual power plant).
To facilitate the implementation of distributed energy resource management systems (DERMS), we propose to insert a grid-edge distributed energy resource (DER) chip hosting a DERMS algorithm into the next generation of smart meters. This will create a pathway for the wide adoption of DERMS technology because many utilities plan to invest in advanced metering infrastructure in the near future. This will also bridge the gap between an electrical power utility and DERs behind the meter. The DER chip is designed to follow power direction signals from the DERMS coordinator while balancing its local objectives. We tested the chip using a controller- and power-hardware-in-the-loop evaluation under three scenarios that a DERMS could face in the real world. The DER chip was capable of and effective at directing four heterogeneous DERs to respond to a DERMS coordinator for grid services (e.g., voltage regulation and a virtual power plant).
GE Research and its partner GE Renewables have proposed the use of an interface converter solution to increase the penetration of small to medium-sized CHP (1MWe to 20MWe) into distribution grids and improve their flexibility and grid support capability. Indeed, the proposed interface converter solution thanks to presence of the grid-ready inverter, allows to streamline the compliance to grid codes requirements, reduce the interconnection delays and costs and ultimately one of the main barriers for CHP adoption by commercial and industrial facilities. An additional benefit provided by the interface converter is the use of the grid-ready inverter for reactive power which eliminates the need of sizing the generator for that capability. These two benefits highly favor the economic feasibility of converter-interfaced CHP. Five user cases, each in one of the leading U.S states for CHP potential reported by the DOE in its estimation of the U.S Technical Potential of CHP, were selected to compare the economic performances of converter-interfaced CHP as compared with directly-coupled. They include a college campus in California, a hospital in New York, a water reclamation plant in Texas, a hotel in Minnesota, and a large office building in Pennsylvania. Results showed that, the presence of the interface converter allows to increase the return on investment (ROI) by 0.5 to 2 percentage points in most of the cases (4 of 5). Indeed, the interface converter by shortening the interconnection process allows to accelerate revenues while reducing interconnection costs. Added to the reduced cost of the required generator these savings trade favorably the capital cost of the converter. The analysis also showed that the profitability of the converter-interfaced CHP is highly sensitive to the energy price, interconnection delay, and converter cost. However, it appears that if the interface converter can shorten the interconnection process by at least 6 months, adopting this solution will be more economically viable than directly-coupled configuration in almost all the +23,000 sites of the U.S Technical Potential CHP. The evaluation of the benefits of a converter-interfaced CHP also showed that it enables higher ROI when coupled with other distributed energy resources (DER) such as battery energy systems (BESS) or solar photovoltaic (PV). Indeed, in those scenario, the grid-ready inverter included in the interface converter eliminates the need of separate inverters if DC-coupling is used. On the technical performance, it has been verified that the presence of the interface converter allows to reduce by 70% to 80% the CHP short-circuit contribution to grid faults. This not only reduces the mechanical and thermal stresses exposed to the CHP electrical components but also increases the grid hosting capacity which ultimately enables higher penetrations CHP. Another key benefit of the interface converter validated with hardware-in-the-loop simulations and testing is its superior capability for reactive power support. Indeed, using a power hardware testbed with two +700kW inverters configured in back-to-back, a microgrid controller and actual facilities loads it was demonstrated that the presence of the interface converter can help maintain a power factor near ~1 or regulate the voltage to ~1.0pu at the point of common coupling. This benefit can be highly valuable if in the future, due to higher penetration of renewable distributed energy resources (DER), utilities start billing demand charge based on kVA instead of kW as currently. It was also validated that converter-interfaced CHP can dispatch heat and power commands and seamlessly switch between the two modes while consistently controlling the power factor or voltage at PCC. Indeed, the power hardware testing showed that grid-connected converter-interfaced CHP can follow either the power or heat demand while maintaining a unity power factor at converter output. This research proved that the adoption of an interface converter as the solution for interconnection of CHP system into the distribution grid can greatly improve the economic feasibility of small to medium-sized CHP as well as the plant power quality, flexibility and resiliency. Additionally, it allows increased penetrations of CHP into the distribution grid, extends their grid support capability, and facilitates the integration of BESS and PV DER by streamlining their collocation within the same facilities. This ultimately provides an opportunity for commercial and small industrial facilities in the U.S to accelerate their energy transition thanks to the high energy efficiency of CHP systems and its reliable, flexible, and resilient microgrid operation when interconnected with an interface converter.
Increasing penetration levels of inverter-based distributed energy resources (DERs) in distribution systems are creating challenges in system operation. Currently, wired or proprietary wireless communications are used by advanced distribution management systems (ADMS) to detect the state of the system and control the DERs for optimal operation. Wireless communications are an alternative solution that can enable connectivity between the dispersed assets used in distribution system applications. This paper demonstrates an experimental test bed to enable the realistic evaluation of communications system characteristics for direct transfer trip (DTT) relaying of a photovoltaic inverter system using a private 900-MHz spectrum wireless LTE network. Private LTE network communications can be deployed to many remote DERs and other grid-edge devices to prevent costly infrastructure upgrades across distribution systems. In addition, this paper provides a framework for evaluating the impact of signal strength and network traffic in communications systems. The results shown develop a better understanding of the best practices for using LTE communications systems across multiple utility applications, such as protective relaying, voltage regulation, and supervisory control and data acquisition system messages.
In this paper, we propose a two-stage electricity market framework to explore the participation of distributed energy resources (DERs) in a day-ahead (DA) market and a real-time (RT) market. The objective is to determine the optimal bidding strategies of the aggregated DERs in the DA market and generate online incentive signals for DER-owners to optimize the social-welfare taking into account network operational constraints. Distributionally robust optimization is used to explicitly incorporate data-based statistical information of renewable forecasts into the supply/demand decisions in the DA market. We evaluate the conservativeness of bidding strategies distinguished by different risk aversion settings. In the RT market, a bi-level time-varying optimization problem is proposed to design the online incentive signals to tradeoff the RT imbalance penalty for distribution system operators (DSOs) and the costs of individual DER-owners. This enables tracking their optimal dispatch to provide fast balancing services, in the presence of time-varying network states while satisfying the voltage regulation requirement. Simulation results on both DA wholesale market and RT balancing market demonstrate the necessity of this two-stage design, and its robustness to uncertainties, the performance of convergence, the tracking ability and the feasibility of the resulting network operations.
This report summarizes the work performed under a project funded by U.S. DOE Solar Energy Technologies Office (SETO) to use grid edge measurements to calibrate distribution system models for improved planning and grid integration of solar PV. Several physics-based data-driven algorithms are developed to identify inaccuracies in models and to bring increased visibility into distribution system planning. This includes phase identification, secondary system topology and parameter estimation, meter-to-transformer pairing, medium-voltage reconfiguration detection, determination of regulator and capacitor settings, PV system detection, PV parameter and setting estimation, PV dynamic models, and improved load modeling. Each of the algorithms is tested using simulation data and demonstrated on real feeders with our utility partners. The final algorithms demonstrate the potential for future planning and operations of the electric power grid to be more automated and data-driven, with more granularity, higher accuracy, and more comprehensive visibility into the system.