Bias Correcting NOAA's High-Resolution Rapid Refresh (HRRR) Wind Resource Data for Grid Integration Applications [Slides]

Many weather years of high-quality wind data are widely accepted in the grid integration community to be important for studying wind energy technical potential, energy system operations, and grid resilience. NREL makes high-quality wind and solar resource data available. NREL's Grid-Atmosphere workshop (March 2024) identified NREL National Solar Radiation Database as widely used in grid integration modeling, but there is less agreement on commonly used wind datasets. One important factor identified by ESIG's 2023 report 'Weather Dataset Needs for Planning and Analyzing Modern Power Systems' for gold standard wind data is regular updates. To address the need for regular updates, NREL's team can now process all currently available and regularly updated High-Resolution Rapid Refresh (HRRR) outputs. HRRR is an hourly-updated operational forecast product produced by the National Oceanic and Atmospheric Administration (NOAA) (Dowell et al., 2022). One barrier to NREL using HRRR is systematic bias and consistency with NREL's existing wind datasets (e.g. WIND Toolkit, 'WTK') across weather years. To address this barrier, we show that the HRRR can be interpolated and bias-corrected to be consistent with NRE's existing datasets. We call the new dataset BC-HRRR (bias-corrected HRRR). As with historical datasets like the WTK, BC-HRRR is intended for use in grid integration modeling (e.g., capacity expansion, production cost, and resource adequacy modeling). BC-HRRR's (2015-present) consistency with WTK (2007-2013) allows NREL to extend internal grid integration tooling with 15+ weather years of wind data with low-overhead extensibility to future years as they are made available by NOAA. The rest of this slide deck documents the BC-HRRR processing methods, validation, and its implications for intended use.

17 WIND ENERGY↗

Bridging Control and Deployment: A Cross-Layer Analysis of Scalable Building Cluster Control

Building cluster control has emerged as a promising approach for enabling flexible and coordinated operation of distributed building systems, yet its transition from pilot demonstrations to routine grid-interactive operation remains limited. This paper argues that this gap cannot be explained by control algorithms alone. Instead, it arises from interacting barriers in communication infrastructure, data and semantic interoperability, uncertainty management, stakeholder participation, market design, and policy support. Accordingly, the paper reviews both technical and non-technical barriers to building cluster control. Technical challenges include heterogeneous devices and protocols, communication latency and reliability, distributed decision-making, and uncertainty propagation across aggregated loads. Non-technical barriers include user participation, stakeholder coordination, incentive allocation, and data governance. Existing solution approaches are synthesized, including semantic interoperability frameworks, edge and hierarchical communication architectures, distributed and transactive control strategies, uncertainty-aware optimization, policy mechanisms, and market reforms. Based on this analysis, two research directions are identified: testing infrastructures that can evaluate control performance under realistic multi-building conditions, and abstraction methods that allow building clusters to interact with other energy sectors through standardized flexibility representations. Overall, the paper provides a structured review of how building cluster control can move from isolated demonstrations toward reproducible, market-compatible, and grid-relevant implementation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Design and Prototyping of Advanced Control Systems for Advanced Reactors Operating in the Future Electric Grid (Final Report)

Despite its significant advantages as a baseload, low-carbon energy source, the U.S. nuclear power industry has faced increasing difficulties in maintaining economic competitiveness in a rapidly evolving energy market. The economic conditions faced by the current fleet of nuclear power plants (NPPs) in the U.S. deregulated electricity market require a concerted effort to mitigate specific cost factors. Many units are struggling to stay competitive, and some premature shutdowns have occurred. Besides, in response to the large penetration of renewable energy sources, the role of nuclear power plants as pure baseload units needs to be reconsidered. Based on these experiences, operational flexibility is considered a fundamental requirement for the next generation of nuclear reactors to be competitive in the future energy market. The deployment of advanced reactors capable of operating within a new power grid paradigm, known as the Integrated Energy System (IES) was investigated. This approach combines new reactor designs with Thermal Energy Storage (TES) technologies, allowing the nuclear reactor to maintain a steady power output without the need for constant adjustments in response to load demand fluctuations. With this configuration, the reactor operates as a baseload unit, experiencing only very gradual power transients, while the energy storage facility within the power conversion cycle acts as a peaking unit.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Rewarding Grid-Friendly Behavior: Estimating the Potential Bill Reduction and Load Shifting Benefits of Dynamic Prices

Shifting electric load from times of peak demand can be a key strategy to slow price growth as reducing peak demand avoids the cost of upgrading generation, transmission and distribution infrastructure. Utilities are releasing time-varying prices, such as time of use rates or dynamic prices, to incentivize grid-friendly load shifting. New dynamic price programs provide insight into the true cost of operating electricity grids and the potential economic benefits of load shifting. Program developers and device manufacturers need to understand the economic opportunities in terms of 1) the variation in prices across hours, days, and seasons; 2) the change in utility bills for customers who don’t shift load; and 3) the potential load shifted and economic value of different technologies if manufacturers or aggregators deploy price-responsive controls. This paper estimates possible impacts of dynamic price adoption and load shifting controls if customers paid the dynamic rate from one pilot program. Statistical analysis of historical prices identified annual and seasonal metrics as well as representative price curves for each circuit in the pilot. Simulations for residential technologies with price-responsive controls including unitary heat pump water heaters, central multifamily heat pump water heaters, heating & cooling + storage systems, and pool pumps estimated the potential impacts of highly dynamic prices both with and without load shifting controls. Results showed the potential to reduce electricity costs on representative days by 42-94% and reduce consumption during times of high electricity prices by 63-100% compared to baseline operation for those flex-friendly devices.

Grant, Peter↗

Modeling Grid Data Flows for Transmission and Distribution Operations: Review, Design, Next Steps

Operational scenarios of the power grids grow multifold to accommodate the diverse needs of both the utilities and end consumers, and the various other stakeholders in-between. To comprehensively model and apply analytics to support objectives and business functions of grid sectors, a reliable approach to characterize and design data flows is crucial. The flows bridge business functions with communications protocols, stakeholders such as the grid actors, and data interfaces comprising different data objects. Additionally, constraints applied to the flow such as cybersecurity, trust, privacy, and ownership among others intersect these entities, requiring the delineation of their interactions under different scenarios. This paper aims to not only highlight relevant research in the space of grid data flows, but also proposes, for the transmission-distribution sector, a novel modeling approach that marries the aforementioned entities: objectives, business functions, data interfaces, communication protocols, data stakeholders, and flow constraints. It elaborates on the design philosophy and the significance of each entity within the model and applies it to an example function of fault location, isolation and service restoration (FLISR). Finally, the next steps to extend the application of this data flow model for other practical operational scenarios are discussed.

Sundararajan, Aditya [ORNL] (ORCID:000000033577854↗

GridSTIX

SF-25-112 Grid-STIX is a comprehensive extension of the STIX (Structured Threat Information Expression) 2.1 ontology specifically designed for electrical grid cybersecurity applications. This ontology provides a standardized, machine-readable framework for modeling grid assets, operational technology devices, threats, vulnerabilities, supply chain risks, and security relationships in electrical power systems. ## Key Features - **Comprehensive Grid Coverage**: Physical assets, OT devices, grid components, sensors, and energy storage systems - **Zero Trust Architecture**: Policy decision points, enforcement points, trust brokers, and continuous monitoring - **AMI Infrastructure**: Advanced metering networks, head-end systems, mesh gateways, and MDM systems - **Advanced Security Modeling**: Attack patterns, vulnerabilities, mitigations, and supply chain risks - **Critical Grid Relationships**: Power flow, protection, control, and synchronization relationships - **Supply Chain Security**: Supplier modeling, country of origin tracking, and risk assessment - **Protocol Support**: DNP3, Modbus, IEC 61850, IEC 60870-5-104, OPC-UA, and IEEE standards - **Python Code Generation**: Automated STIX-compliant Python class generation from ontologies - **Interactive Visualization**: Enhanced HTML network graphs with grid-specific categorization - **STIX 2.1 Compliance**: Full compatibility with STIX threat intelligence ecosystem

Blakely, Benjamin [Argonne National Laboratory (AN↗

Proposed Critical Thinking Metrics for Power Grid Trainees

The TRS Intro to Critical Thinking for Operational Decision-Making course for power grid operators seeks to help trainees improve their use of critical thinking skills in operation environments. To determine the effectiveness of this training, we have identified 3 categories of evaluation measures: critical thinking metrics, situation awareness (SA) evaluations, and behavioral observations. Critical thinking metrics seek to directly measure trainee’s ability to use critical thinking skills through their verbalized responses to different questions or scenarios. SA will be evaluated during various points throughout simulated exercises completed during the training. SA evaluations aim to determine the level of a trainee’s ability to perceive, comprehend and anticipate events in the operational environment. This construct will be assessed through verbalized responses to questions informed by the Situation Awareness Global Assessment Technique (SAGAT). Behavioral observations capture how trainees use the system, including which simulator displays or windows they use or actions they perform and in what order. These observations help us understand how the critical thinking training may inform operator action. We hypothesize that while these measures are correlated with each other, they provide different perspectives on each trainee’s ability to gain SA and use critical thinking skills in operation environments. By comparing these measures in a pre-assessment and a post-assessment, we can determine how much improvement a trainee gains through the training. These measures may also be used during the training as appropriate. This document specifies these 3 categories of measures, which components of these measures currently seem to be the best candidates to use in the training course, and which parts of the training course is related to each component.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Intelligently Partitioned Phasor-EMT Hybrid Simulations of Large-Scale, High-IBR Power Systems

As the penetration level of power electronics-interfaced renewables such as photovoltaics (PV) and wind has surged in modern electric grids, new operational risks caused by the dynamics of those inverter-based resources (IBRs) are emerging in parallel. Lessons learned from various grid events include that the impact of IBRs on system-level grid stability will become prominent along with the increase of renewables and that the short-timescale dynamic impacts of IBRs on grid stability are not fully captured by current commercial dynamic simulation tools [1] [2]. For example, IBRs can be controlled to mitigate those destabilizing interactions, but conventional phasor-domain tools (e.g. PSS/E, PSLF) often cannot capture that; likewise, the existing electromagnetic transient (EMT) simulation tools (e.g. PSCAD, EMTP) can simulate detailed IBR controls, but for large power systems with many IBRs, slow simulation speeds severely impede the ability to study dynamic events [3] [4]. Massively paralleling simulations using high-performance computing (HPC) can help address this, especially now that cloud-based HPC capability is widely available, but today s EMT tools are not HPC-compatible, and parallelization of dynamic simulation solvers is not trivial because each region can dynamically affect the others. Thus, dynamic simulation of grids with very large numbers of IBRs potentially poses a barrier to the ongoing energy transition.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Optimal Control for Fast Frequency Response and Black-Start using Embedded Storages with Grid-Forming Control

The grid-forming inverter is regarded as the solution for integrating high levels of renewable resources into future power systems. Ensuring the stable operation of grids necessitates that grid-forming inverters offer fast frequency response. This report introduces an optimal control method that coordinates the embedded storage within the grid-forming control model with conventional synchronous generators. The optimized active power reference for the embedded storage is generated using receding horizon optimization control, aiming to keep the center of inertia frequency within acceptable limits. The effectiveness of the proposed control is verified through testing in the IEEE 39-bus system. In addition, with grid-forming capability, we will also investigate the application of using mobile embedded storages as black-start units to provide cranking power to energize non-blackstart generators in a black-start process.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Feedback Optimization of Incentives for Distribution Grid Services

Energy prices and net power injection limitations regulate the operations in distribution grids and typically ensure that operational constraints are met. Nevertheless, unexpected or prolonged abnormal events could undermine the grid's functioning. During contingencies, customers could contribute effectively to sustaining the network by providing services. Herein this paper proposes an incentive mechanism that promotes users' active participation by essentially altering the energy pricing rule. The incentives are modeled via a linear function whose parameters can be computed by the system operator (SO) by solving an optimization problem. Feedback-based optimization algorithms are then proposed to seek optimal incentives by leveraging measurements from the grid, even in the case when the SO does not have a full grid and customer information. Numerical simulations on a standard testbed validate the proposed approach.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Demonstrating the data center as a flexible grid asset using a C-HIL setup

Increasing data center demand is outpacing grid infrastructure development. Artificial intelligence workloads and hyperscale cloud growth are creating unprecedented demand for power, while traditional grid expansion faces multiyear development timelines. Verrus is developing an innovative datacenter solution for this challenge, data centers that act as active grid-supportive assets rather than passive loads. Our approach integrates a novel grid-aware power flow management system with battery energy storage systems(BESS) into a microgrid-controlled, medium-voltage power distribution architecture that delivers critical capabilities, such as: * Fast response to grid disturbances such over/ under voltage or over/ under frequency * Demand flexibility that can service requests from the utility within 10 s * Uninterrupted transition to islanded operation during grid outages * Continuous uptime assurance for compute loads while maintaining all customer service level agreements. Through Verrus' strategic partnership with the National Renewable Energy Laboratory (NREL), these capabilities were validated using NREL's Advanced Research on Integrated Energy Systems (ARIES) virtual emulation environment to model a 70-MW grid-interactive data center. This paper outlines the design, methodology, and results of this emulated deployment, demonstrating that data centers can provide both critical load resilience and ancillary grid support without compromising uptime requirements. Specifically, we present a digital real time simulation of a 70 MW data center integrated with a physical microgrid controller, and demonstrate the data center response in the event of a grid voltage and frequency event, utility demand response request and utility outage.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Novel Protection Scheme for Unbalanced Faults in Inverter Dominated Networks: A Computationally Efficient Algorithm for Entry-Level Relays

Microgrids are now a common practice in distribution systems to increase resilience and reliability. However, microgrid protection remains a critical challenge, considering its requirement to operate in both grid connected and islanded, and the variability in fault characteristics under each mode of operation. This paper presents unbalanced power (S unb ) based fault detection algorithm, which considers local voltage and current unbalances to determine faults in the system. S unb is a computationally efficient fault detection algorithm that is suitable for implementation in the programmable logic of entry level protective relays. In addition, the difference in current and voltage unbalance (D n ) is used to determine the fault type. The proposed method demonstrates high sensitivity and selectivity for line-to-ground (LG), line-to-line (LL), and double line-to-ground (LLG) faults, representing the most common faults in distribution systems. It also allows relay coordination with upstream and downstream protection devices in both island and grid connected operation, while preserving grading margins. The same pickup and time multiplier settings of a particular relay for both modes of operation eliminates the need for adaptive settings, which rely on communication networks. Validation was performed with a hardware-in-the-loop (HIL) setup using Typhoon HIL real time simulator interfaced with three entry-level, SEL 751 relays. Results confirmed the algorithm’s ability to discriminate fault conditions, and determine the fault type under both operating modes, maintain fast detection times, and ensure proper protection coordination.

fault classification↗

Digital Twin + AI: Control Room of the Future

A digital twin enhances power grid control room operations by providing real-time monitoring, predictive insights, simulation capabilities, remote control, training opportunities, data integration, and decision support. This technology empowers control room operators to effectively manage the grid, optimize performance, and ensure reliable and efficient energy distribution.

control room of the future↗

High-Fidelity Analysis of EV Integration on Real Utility Feeders in Colorado

Residential electric vehicle (EV) charging has the potential to alter long-held assumptions on load characteristics impacting distribution grid planning, operations, and design standards. This study identifies analysis and control methods to increase the affordability of residential EV charging both for Xcel Energy and their customers. The project also provides solutions for more reliable grid interconnection that can support a reliable utility business model prepared for increasing EV charging load in the coming years. For this project, we referenced Level 2 alternating current (AC) onboard charging profiles for various vehicle models and high-fidelity charging data collected at the experimental setup established at the EV Research Infrastructure Laboratory at the National Renewable Energy Laboratory (NREL). Next, we developed EV adoption models for 2030 and 2040 for the Boulder and Aurora regions in Colorado. Moreover, we evaluated different smart charging control algorithms and compared their performance. We developed time-of-use (TOU)-based and grid-aware active EV charging control methods and integrated them within the study region to understand field impacts. Diving deeper, we selected 10 feeders in Boulder and Aurora for high-fidelity grid modeling down to the house level. We executed detailed grid analysis comparing the smart charge management (SCM) algorithms we developed. Finally, we created a novel tool, Electric Vehicle Infrastructure--Distribution System Integration Tool (EVI-DiST), to integrate all the approaches in a single software environment to provide easy integration, fast simulation, and detailed evaluation capability for utility engineers and other stakeholders.

33 ADVANCED PROPULSION SYSTEMS↗

Vulcan Test Platform: Demonstrating the Data Center as a Flexible Grid Asset

Explosive data center demand is outpacing grid infrastructure development. AI workloads and hyperscale cloud growth are creating unprecedented power requirements, while traditional grid expansion faces multi-year development timelines, regulatory hurdles, and decarbonization challenges. Sidewalk Infrastructure Partners recognized this impending crisis years ago and founded Verrus to develop an innovative solution: data centers that function as grid assets rather than passive loads. The Verrus approach integrates proprietary grid-aware controls with battery energy storage systems (BESS) in a medium-voltage architecture that delivers three critical capabilities: Fast-responding demand flexibility that can service requests from the utility within 10 seconds, Uninterrupted transition to islanded operation during grid disturbances, Continuous uptime assurance while maintaining all customer service level commitments Through Verrus' strategic partnership with the National Renewable Energy Laboratory (NREL), we validated these capabilities on Vulcan, a 70 MW utility-scale test platform powered by NREL's ARIES Virtual Emulation Environment. This deployment-ready technology has successfully demonstrated that Verrus data centers can deliver meaningful grid services while maintaining mission-critical reliability. This technical report outlines the design, methodology, and results of this emulated deployment, demonstrating that data centers can play a pivotal role in enhancing grid flexibility and reliability, without sacrificing service level guarantees.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Multiple Beam Triode Driven RF Sources for Accelerator Applications Phase I Final Report

Calabazas Creek Research, Inc, (CCR), in collaboration with Microwave Power Products, Inc. (MPP), formerly Communications & Power Industries, LLC (CPI,) and JP Accelerator Works, Inc. (JPAW), embarked on a program to develop multiple beam triodes to produce RF power from 350 – 800 MHz with an average power exceeding 200 kW. The effort was motivated by the performance of a triode-based RF source which produces 25 kW of UHF power at 90% efficiency. The CCR effort focused on implementing this technology into a multiple beam device to increase the output power while retaining the low cost, compact size, and high efficiency. The program performed extensive simulations indicating that the goals could be achieved, and a prototype multiple beam triode was built, baked, and tested. Unfortunately, a grid to cathode short terminated the testing before the tube could generate RF power. Nevertheless, the effort demonstrated that a multiple beam triode could be designed, built, baked, and energized to high voltage. The multiple beam triode used oxide cathodes, which are only capable of pulsed operation. The multiple beam triode will be rebuilt using dispenser cathodes, which will allow high duty or continuous operation. The grids were also modified to be more robust to avoid previous issues. The MB triode will provide the beam power for RF generation. The RF is generated by surrounding the triode with input and output cavities to convert beam power to RF power. RF cavities to generate 200 kW CW at 350-450 MHz using the MB triode with dispenser cathodes was assembled during the program. The next Phase of this effort is to assemble the multiple beam triode using the subassemblies built in the Phase I program and test with the RF cavities. The Phase I program also initiated design of a higher frequency, higher power multiple beam triode. That design is forecast to produce approximately 500 kW CW from 350 - 500 MHz.

43 PARTICLE ACCELERATORS↗

Transmission Operator Workflows for Real-Time Reliability Studies: A Review of Control Room Practices and Naturalistic Decision Making

This report provides an overview of real-time reliability study tools and their use by power system operators in the control room environment. After introducing some of the nuances of the control room environment and the differences in perspectives between power system engineers and operators, the roles and responsibilities of key entities involved in RTCA workflows are introduced. These are specifically the transmission system operator (TOP) and reliability coordinator (RC), which are required to run tools such as real-time contingency analysis (RTCA) as part of a real-time reliability assessment every 30 minutes, as dictated by a series of standards issued by the North American Electric Reliability Corporation (NERC). The process by which power systems operators operate the grid is discussed in terms of naturalistic decision making (NDM) and the recognition-primed decision-making (RPD) model. This cognitive model describe how experts working in high-risk, high-stress environments make safety-critical decisions under uncertainty and time pressure. For power system operators, the mental simulations involved in the traditional RPD model are supplemented by physics-based simulations using numerical tools, such as RTCA, to improve situational awareness and effectiveness of control actions. Next, a generic workflow is introduced to describe operator decision making for running RTCA tools and responding to system violations on a pre-contingent basis. The types of analysis performed and control actions chosen by power system operators are described in detail. The overall high-level workflow is then expanded in subsequent sections, with special attention given to high-voltage violations, low-voltage violations, and thermal overloads. Each type of violation is described in detail, with explanations of common causes, impacts on equipment and customers, and mitigation strategies. An additional workflow diagram is provided for each type of violation.