How Microgrids Will Shape the Future (Presentation)
Presented at the Small Wind Conference, 16-19 June 2014, Stevens Point, Wisconsin
SEARCH · Engineering Papers
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Presented at the Small Wind Conference, 16-19 June 2014, Stevens Point, Wisconsin
Before rotating, fossil fuel-based, synchronous generators (SGs) are phased out, in line with renewable generation goals, grid-forming (GFM) inverters are expected to parallel SGs. Primary droop control allows GFM inverters to share power without communication; however, it is necessary to dispatch GFM inverters and/or SGs with the desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to a low state of charge). Therefore, this paper develops an analytic approach to dispatching GFM inverters and SGs with the desired output power by shifting the droop intercept up/down while maintaining the same frequency operating point for improved transient stability. This concept is demonstrated through a pure hardware setup with two off-the-shelf inverters and one diesel generator under an islanded microgrid, and we provide insight on the real-world implementation of the proposed concept.
The Ernest Orlando Lawrence Berkeley National Laboratory (LBNL) is working with the California Energy Commission (CEC) to determine the potential role of commercial-sector distributed energy resources (DER) with combined heat and power (CHP) in greenhouse gas emissions (GHG) reductions. Historically, relatively little attention has been paid to the potential of medium-sized commercial buildings with peak electric loads ranging from 100 kW to 5 MW. In our research, we examine how these medium-sized commercial buildings might implement DER and CHP. The buildings are able to adopt and operate various technologies, e.g., photovoltaics (PV), on-site thermal generation, heat exchangers, solar thermal collectors, absorption chillers, batteries and thermal storage systems. We apply the Distributed Energy Resources Customer Adoption Model (DER-CAM), which is a mixed-integer linear program (MILP) that minimizes a site?s annual energy costs and/or CO2 emissions. Using 138 representative mid-sized commercial sites in California, existing tariffs of major utilities, and expected performance data of available technologies in 2020, we find the GHG reduction potential for these buildings. We compare different policy instruments, e.g., a CO2 pricing scheme or a feed-in tariff (FiT), and show their contributions to the California Air Resources Board (CARB) goals of additional 4 GW CHP capacities and 6.7 Mt/a GHG reduction in California by 2020. By applying different price levels for CO2, we find that there is competition between fuel cells and PV/solar thermal. It is found that the PV/solar thermal adoption increases rapidly, but shows a saturation at high CO2 prices, partly due to limited space for PV and solar thermal. Additionally, we find that large office buildings are good hosts for CHP in general. However, most interesting is the fact that fossil-based CHP adoption also increases with increasing CO2 prices. We will show service territory specific results since the attractiveness of DER varies widely by climate zone and service territory.
This presentation provides an overview of site-specific evaluation of microgrid controller using controller- and power-hardware-in-the-loop.
The article presents a control and communication architecture for interconnecting multiple microgrids by leveraging IEC 61850 data models with distributed energy resources (DER) extensions, IEC Common Information Model (CIM) and Open Field Message Bus (OpenFMB) frameworks. An example use case for planned islanding in the nested microgrid scenario is also provided.
With the increase in penetration of inverter-based resources (IBRs) in the electrical power system, the ability of these devices to provide grid support to the system has become a necessity. With standards previously developed for the interconnection requirements of grid-following inverters (GFLI) (most commonly photovoltaic inverters), it has been well documented how these inverters “should” respond to changes in voltage and frequency. However, with other IBRs such as grid-forming inverters (GFMIs) (used for energy storage systems, standalone systems, and as uninterruptable power supplies) these requirements are either: not yet documented, or require a more in deep analysis. With the increased interest in microgrids, GFMIs that can be paralleled onto a distribution system have become desired. With the proper control schemes, a GFMI can help maintain grid stability through fast response compared to rotating machines. This paper will present an experimental comparison of commercially available GFMI and GFLI ' responses to voltage and frequency deviation, as well as the GFMI operating as a standalone system and subjected to various changes in loads.
San Diego Gas & Electric's Borrego Springs Microgrid is one of the largest microgrids in the USA, serving 2500 residential customers, 300 commercial and industrial customers, and has a peak demand of approximately 14 MW. This microgrid is located at the end of a long transmission line, and is subjected to extreme weather events like storms, wildfires, and flooding, which frequently cause grid outages. The microgrid currently relies on 3.65 MW of diesel-powered generators to provide grid-forming services during these outages, which results in greenhouse gas and criteria pollutant emissions. However, the microgrid has access to approximately 37 MW of installed solar generation and struggles with overgeneration and curtailment. 1.5 MW/4.5 MWh of grid-scale batteries have been installed to capture some the overgeneration and provide resiliency, but a longer-duration low-greenhouse gas emission energy storage solution is needed. In our project, the team will evaluate in the lab and demonstrate in the field a grid-forming fuel cell inverter that can provide grid-forming services while utilizing hydrogen's energy storage scalability. We will first utilize NREL's Renewable Energy Integration and Optimization (REopt) platform to perform analyses on future microgrid scenarios that use hydrogen assets to reduce or eliminate the need for diesel backup generators. We will then evaluate the grid-forming inverter through power hardware-in-the-loop and controller hardware-in-the-loop experiments at ARIES, and de-risk the field deployment and operation of hydrogen assets in the microgrid setting. Finally, this project will demonstrate the operation of the fuel cell inverter and updated microgrid controller by operating in grid-forming mode in the Borrego Springs microgrid.
Practical vendor-agnostic interoperability guidelines for the secondary control architecture of microgrids (MGs) with multiple grid-forming (GFM) inverter-based resources (IBRs) have not yet been developed. Therefore, this paper proposes a generic and vendor-agnostic secondary control architecture that works with all GFM IBRs and synchronous generators. This secondary control does not need to employ any additional measurement devices in the MG and uses the inherent communication systems of the GFM units, such as Modbus TCP/IP. The practical challenges of Modbus holding registers such as packet loss, quantization error, etc. and their deteriorating impacts on the secondary control action are investigated. The proposed three-stage modification of any secondary control architecture to eliminate these impacts includes 1) averaging the data read, 2) situational event-triggering of the controller, and 3) the finite iteration of the controlling action. The proposed method is validated using a laboratory hardware MG with commercial GFM units.
In this report, we propose a novel model predictive control(MPC)-based real-time conditional self-restoration energy management system (CSR-EMS) for interconnected microgrids (IMGs) integrated with renewable energy sources (RESs) and energy storage systems (ESSs). Superior to the existing IMG self-restoration methods, the “conditionality” of the proposed CSR-EMS can economically realize self-restoration and grid-assisted restoration during energy deficiency or faults, in both islanded and grid-connected modes. Cost minimization is implemented as the objective function to judge in real-time which restoration mode is economically preferred. The proposed CSR-EMS comprises two layers–the lower layer operates locally to eliminate electricity fluctuations created by RESs and ensure economic effectiveness within an MG, whereas the upper layer oversees the real-time operational status of the IMG system and determines power exchange among microgrids (MGs) during abnormalities. In detail, when a microgrid inside the IMG system experiences an energy deficiency, the CSR-EMS, on an MPC basis, intelligently optimizes power production from each dispatchable distributed generator (DG), ESS, power imported from the main grid, and power exchange among the IMGs to maintain the demand–supply balance, while considering system recovery cost, state of charge (SoC) of ESSs and operation modes of the IMGs (i.e., grid-connected or islanded mode). Simulation results and comparisons with existing IMG self-healing EMSs demonstrate the economic efficacy of the proposed CSR-EMS strategy during normal and abnormal operations, which can be used as an energy control framework for modern power systems with multiple interconnected microgrids.
This paper describes a systematic process of designing resilient electric distribution systems and microgrids using smart meters for surgical load management (SLM) as part of Advanced Metering Infrastructure (AMI). The work focuses on selection approach, integration, and interoperability aspects for AMI in microgrids. SLM is proposed as a granular control methodology for serving selective critical loads across different distribution feeders in the system during extreme events. The surgical load shedding as well as load pick-up provides a robust approach for maximizing critical load served in a resource-constrained electric distribution system or a microgrid. We present the case of a 20 MW islanded microgrid in Cordova, AK, USA, which is the demonstration site for field validation of resilience enhancement technologies for the DOE-funded Grid Modernization project RADIANCE. Cordova microgrid is an islanded distribution grid that provides an environment to prove the approach, and the techniques may also be applicable to other regional distribution systems.
This paper describes a systematic process of designing resilient electric distribution systems and microgrids using smart meters for surgical load management (SLM) as part of Advanced Metering Infrastructure (AMI). The work focuses on selection approach, integration, and interoperability aspects for AMI in microgrids. SLM is proposed as a granular control methodology for serving selective critical loads across different distribution feeders in the system during extreme events. The surgical load shedding as well as load pick-up provides a robust approach for maximizing critical load served in a resource-constrained electric distribution system or a microgrid. We present the case of a 20 MW islanded microgrid in Cordova, AK, USA, which is the demonstration site for field validation of resilience enhancement technologies for the DOE-funded Grid Modernization project RADIANCE. Cordova microgrid is an islanded distribution grid that provides an environment to prove the approach, and the techniques may also be applicable to other regional distribution systems.
Individual microgrids have proven their ability to provide uninterrupted power to critical end-use load during severe events. Building on the performance of individual microgrids during extreme events, there has been an increasing interest in the operations of network microgrids. By networking microgrids during extreme events, it is possible to share resources, increase the duration for which they can operate islanded, and increase the resiliency of critical end-use loads. While there are benefits to networking the operations of resiliency-based microgrids, the switching operations that they require introduce transients which can result in a loss of dynamic stability. The issue of dynamic stability is especially acute in microgrids with high penetrations of inverter-connected generation, and a correspondingly low system inertia. While the low-inertia of these microgrids can be increased by over-sizing the rotating generators, the increased capital and operating costs can become a barrier to deployment. This work will present a method of augmenting primary frequency controls to support the switching transients necessary for the operation of networked microgrids, without the need to over-size rotating machines.
We take the perspective of a microgrid that has installed distribution energy resources (DER) in the form of distributed generation with combined heat and power applications. Given uncertain electricity and fuel prices, the microgrid minimizes its expected annual energy bill for various capacity sizes. In almost all cases, there is an economic and environmental advantage to using DER in conjunction with demand response (DR): the expected annualized energy bill is reduced by 9percent while CO2 emissions decline by 25percent. Furthermore, the microgrid's risk is diminished as DER may be deployed depending on prevailing market conditions and local demand. In order to test a policy measure that would place a weight on CO2 emissions, we use a multi-criteria objective function that minimizes a weighted average of expected costs and emissions. We find that greater emphasis on CO2 emissions has a beneficial environmental impact only if DR is available and enough reserve generation capacity exists. Finally, greater uncertainty results in higher expected costs and risk exposure, the effects of which may be mitigated by selecting a larger capacity.
Increasing need for distribution circuit reliability and resilience prompt a clearer understanding of community microgrid interconnection and operational requirements. While customer-owned, behind-the-meter microgrid implementation is not always simple, increasing demand for reliability has commercialized many installation approaches. This rapid commercialization has broadened industry understanding of single-customer microgrid integration. Moreover, off-grid behaviors of such microgrids are not required to meet utility standard interconnection requirements. However, multi-customer community microgrids (utility- or third-party operated), are less well explored and introduce more complex design and operational challenges. The control of DER along with distribution automation devices, unmanned operation, protection coordination, and other aspects makes community microgrids challenging to implement and operate in both on-grid and off-grid modes. This whitepaper is a technical primer for understanding community microgrids. It provides a foundation for understanding the components, configurations, design, and operational considerations for community microgrids.
Efficient and effective management of the electric distribution system requires an integrated approach to allow various systems to work in harmony, including distribution management systems (DMS), distributed energy resources (DERs), distributed energy resources management systems, and microgrids. This study highlights some outcomes from a recent project sponsored by the US Department of Energy, Office of Electricity Delivery and Energy Reliability, including information about (i) the architecture of these integrated systems and (ii) expanded functions of two example DMS applications to accommodate DERs: volt-var optimisation and fault location, isolation, and service restoration. In addition, the relevant DER group functions necessary to support communications between the DMS and a microgrid controller in grid-tied mode are identified.
The Integrated Distribution Management System (IDMS) project was initiated to demonstrate the interactive operation of microgrid systems and the distribution systems with which they interconnect. The key technologies for this are the microgrid management system and the utility distribution management system. The IDMS project successfully demonstrated that a utility’s advanced distribution management system/distributed energy resources management system (ADMS/DERMS) could effectively manage microgrids to provide visibility and control functionalities as well as use the microgrid as a dispatchable resource to support the utility grid. The DERMS accomplishes this by determining active and reactive power needs at the point of common coupling (PCC) using advanced applications like volt/VAR watt optimization (VVWO) and load relief (LR) with the underlying core applications state estimation (SE) and load flow (LF). The ADMS/DERMS can use the microgrid as a resource to resolve and prevent violations in the grid and to optimize the operational working state of the grid. The IDMS project demonstrated that a utility-operated ADMS with embedded DERMS functionality can flexibly manage a variety of microgrids and other aggregated distributed energy resources (DER) in concert with the wider distribution grid. Microgrids can provide grid services in any number of different ways to meet the operational needs of the distribution utility. The manner of aggregation — microgrid or virtual power plant — is not necessarily relevant to the utility as long as the grid services from the aggregated DER are available and can be managed by its ADMS/DERMS for the stability and reliability of the grid. The IDMS project demonstrated this integrated ADMS concept by combining hardware/software-in-the-loop testing with commercial products from different vendors and a utility’s network model. The project integrated the Schneider Electric EcoStruxure™ ADMS with DERMS with the Schweitzer Engineering Laboratories (SEL) POWERMAX ® Microgrid Control System, and the simulated resources with energy company PECO’s model of a utility-owned microgrid, establishing an operational relationship in which the utility manages the operational functionality of a microgrid at the PCC and that provides the utility with the capability to control the comprehensive power system, inclusive of the macrogrid and microgrid.
This paper presents a parametric comparative analysis between the virtual synchronous generator (VSG) method and the droop control method to emulate inertia in the voltage-source inverter (VSI). Droop controllers are commonly used to regulate sharing power in microgrids and distribute power generation proportionally among VSI’s depending on their rated power. Additionally, VSG has been used to regulate the Rate-of-Change-of-Frequency (RoCoF) of the microgrid using virtual inertia. Although both methods can be used to regulate the frequency variation, the influence of each method on the closed loop eigenvalues is not the same. In this work, the transient response of the frequency is analyzed for each method to determine their advantages and disadvantages regarding frequency regulation in microgrid applications. The results were verified by conducting experimental trials using VSI’s. These experiments demonstrated that VSG is more suitable for regulating RoCoF and frequency nadir than droop controllers since it provides inertial support and improves frequency response.
Islanded microgrids may experience voltage and frequency instability due to uncontrolled state changes of voltage regulation devices and inaccurate demand forecasts. Uncontrolled state changes can occur if optimal microgrid restoration and dispatch algorithms, used for generating control commands for distributed energy resources, do not incorporate the behavior of automatic controllers of voltage regulation devices. Inaccurate demand forecasts may be encountered since post-outage demand of behind-the-meter net metered (NM) loads can vary significantly from their historical NM profiles. Here, this paper proposes an optimization formulation which allows optimal control of voltage regulators and capacitor banks without remote control and communication capabilities. A generalized demand model for NM loads is proposed which incorporates the cold load pickup phenomenon and their time varying post-outage demand in accordance with the IEEE 1547 standard. The time dependent optimal control formulation and the NM demand model are integrated in a sequential microgrid restoration algorithm by linearization of the involved logic propositions. A detailed case study on the unbalanced IEEE 123-node test system in OpenDSS validates the effectiveness of the proposed approach.