DOE OSTI · 3365795
Large Load Impacts to Distribution System Hosting Capacity
Abstract
This work examined the impact of large loads on utility distribution system models using the Sandia-developed open-source software DREAMS. It was shown that hosting capacity varies with location and changes after any asset is added to, or removed from, a system. Despite the tested models having similar rated voltages and other characteristics, their thermal and voltage constrained hosting capacity varied over 2 MW. The addition of a 3-phase balanced constant power large load with power factor of 1.0 exhibited non-linear reductions to all voltage constrained hosting capacities. The reductions to thermal constrained hosting capacity from a load with similar characteristics was more linear, related to the size of the added load, and did not impact all model buses. Co-located capacitors were shown to accommodate demand that was beyond the baseline voltage constrained hosting capacity limits, however, the costs and benefits from this approach were found to not be 1:1 and required additional available thermal capacity.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Haines, John Thaddeus [Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)] (ORCID:0000000165928115). 2026-05-01. Large Load Impacts to Distribution System Hosting Capacity. https://doi.org/10.2172/3365795