The rapid growth of future energy demand increases the need to economically store electrical energy over durations up to several days in long-duration energy storage (LDES) applications. LDES can reduce the grid stress for improving the resilience of the grid. The integration of renewable power and storage has several significant and positive impacts including expanding the renewable energy portion of electricity generation, meeting peak-load demand, and coordinating supply and demand. Several energy storage approaches including mechanical, chemical and electrochemical methods are currently deployed or under development. However, LDES requirements pose unique challenges for scalability, energy capacity, and cost. Thermal energy storage (TES) has the ability to store a large capacity of energy with improved site flexibility compared to incumbent LDES technologies (i.e., pumped hydro) and has attracted significant interest. Our development in TES technology using solid particles as the storage medium has shown feasibility and potential in serving LDES purposes. Particle TES has various advantages over commercialized molten nitrate salt TES and has emerged as a promising storage technology originating from Generation 3 concentrating solar power (CSP) development. Stable, inexpensive silica sand produced in the Midwestern U.S. was identified as a suitable storage medium and has been validated through lab heating and cycling tests. We have successfully developed particle TES for bidirectional electric energy storage to broaden the applications for TES beyond CSP technologies and into standalone electric-thermal energy storage (ETES) systems. Key component designs and performance were verified with prototype testing and model simulations. The ETES system uses high-temperature, low-cost particle thermal energy storage coupled with a unique pressurized fluidized bed heat exchanger that supports a high-efficiency, air-Brayton combined power cycle. At times of low energy demand or high renewable production, an electric particle heater heats large quantities of solid particles to high temperatures in excess of 1100 degrees C. The particles are stored in internally insulated silos. At times of high electricity demand, the hot particles are gravity-fed through the heat exchanger where stored thermal energy is transferred to the power cycle working fluid to drive the gas turbine power generation system, thereby converting the thermal energy back into electricity for the grid. The cold particles leaving the heat exchanger are returned to the storage silos by a well-insulated particle conveyor. This ETES technology using particle TES can be sited anywhere and is predicted to be economic and efficient. Moreover, this ETES technology could be co-located with a retired coal or gas plant to leverage existing power generation and grid infrastructure. Our work has focused on the development of each of the key components (e.g., the electric particle heater, particle storage silos, and the particle-to-gas pressurized fluidized bed heat exchanger) through conceptual designs, prototype testing, and computational modeling. These developments demonstrate technological feasibility and are an important step towards the next phase of development of this promising LDES technology. This presentation will show the progress in developing a pilot demonstration of the ETES system on a commercially relevant scale.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Ma, Zhiwen [National Laboratory of the Rockies, Golden, CO (United States)] (ORCID:0000000337188038), Jeong, Shin Young [National Laboratory of the Rockies, Golden, CO (United States)], Shah, Munjal [National Laboratory of the Rockies, Golden, CO (United States)] (ORCID:0000000261206016), Hirschey, Jason [National Laboratory of the Rockies, Golden, CO (United States)], Patel, Umang [National Laboratory of the Rockies, Golden, CO (United States)], Ustuner, Emre [National Laboratory of the Rockies, Golden, CO (United States)], Kayal, Rashad [National Laboratory of the Rockies, Golden, CO (United States)], Fergerson, Nicholas [National Laboratory of the Rockies, Golden, CO (United States)]. 2026-01-23. Pilot Development Progress to Demonstrate Electric Thermal Energy Storage (ETES) Using Low-Cost Particles. https://doi.org/10.2172/3015388

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

An immersed interface method for microstructure-scale electrochemical battery models: numerical formulation and performance portable implementation

We present the numerical formulation, verification, and performance portable implementation of an immersed interface method for microstructure scale electrochemical modeling of batteries. The innovation in this approach is the resolution of chemical species and electrostatic potential discontinuities at active interfaces without the use of interface conforming unstructured grids. A unified formulation on Cartesian grids for all domains (electrodes and electrolyte) is used with interfacial flux conditions applied using volume fraction or “color” function gradients. We have developed one dimensional and two dimensional test cases with analytic solutions for electrochemical modeling using which we verified the consistency and accuracy of our scheme. Our solver is also validated against solutions from a macroscale model and an unstructured multi-subdomain solver for a full lithium ion cell. We then demonstrated the utility of our solver on an image-based complex battery electrode microstructure at high charging rate. Our technique also exhibits good scalability on distributed memory architectures using central processing units (CPU), with problem sizes up to 1.8 billion degrees of freedom and with 5400 ranks. Initial performance studies of our open-source performance portable solver showed about 70 times speed up using a graphics processing unit (GPU) compared to single compute core for a problem with 4 million cells.

25 ENERGY STORAGE

Solvation-guided inhibition of manganese dissolution of lithium- and manganese- rich cathode via cyclic carbonate molecular engineering

Lithium and manganese-rich (LMR) layered oxides represent a leading class of high-energy cathode materials, but their practical realization is fundamentally limited by severe manganese (Mn) dissolution, a process that triggers structural degradation and rapid capacity fade. While mitigation efforts have predominantly focused on interfacial engineering, the intrinsic contribution of bulk electrolyte solvation to this degradation pathway remains largely unexplored, primarily due to the difficulty of deconvolving its effects from concurrent cathode-electrolyte interphase (CEI) formation. Here, we report an experimental design to isolate the role of solvation. We systematically varied the electrolyte solvent solvation power by substituting the strongly coordinating ethylene carbonate (EC) with its weaker coordinating fluorinated derivatives, fluoroethylene carbonate (FEC) and trans-4,5-Difluoro-1,3-dioxolan-2-one (DFEC), while maintaining a consistent interfacial chemistry. Remarkably, the electrolyte formulated with the weakest solvent, DFEC, exhibits superior cycling stability, suppressing Mn dissolution by up to 63% relative to the conventional EC-based system. Post-mortem analysis unequivocally attributes this performance enhancement to the preservation of the LMR cathode's structural integrity, a direct consequence of mitigated Mn dissolution. This work provides conclusive evidence that modulating bulk electrolyte solvation is a potent and direct strategy for stabilizing LMR cathodes, establishing a vital design principle for next-generation battery systems.

25 ENERGY STORAGE

Geothermal district energy systems coupled with seasonal underground thermal energy storage: a U.S. techno-economic screening by climate and geology

In the United States, cooling-dominated commercial building loads can cause geothermal heat pump-based district energy systems to accumulate a long-term subsurface thermal imbalance, motivating the incorporation of seasonal underground thermal energy storage. We developed a transferable workflow to evaluate geothermal district systems that pair ground heat exchangers with seasonal underground thermal energy storage. Using standardized hourly loads for seven commercial buildings and a uniform cost framework, we simulated ten U.S. cities with a physics-based ground heat exchanger model, subsurface storage simulations, and economic assessment to isolate the roles of climate and hydrogeology. In cooling-dominated cities, underground thermal energy storage supplied the majority of annual cooling, cutting electricity use and summer peaks substantially while achieving levelized costs comparable to or below conventional chiller-boiler plants. In cooler climates, the storage share shrunk, required borefield size and costs rose, and levelized cost of energy increased nearly linearly with declining underground thermal energy storage fraction, indicating storage fraction as the primary economic lever. Sensitivity analysis showed capital risk dominated by borefield drilling and surface heating, ventilation, and air-conditioning and piping, with underground thermal energy storage costs secondary. This workflow provides a transparent foundation for site-specific design and screening of next-generation geothermal district energy systems.

25 ENERGY STORAGE