DOE OSTI · 1810550
Resiliency-Driven Proactive Distribution System Reconfiguration With Synchrophasor Data
Also available from
Abstract
Measuring and enabling resiliency of electric distribution systems with increasing weather and cyber events are important. Some of the extreme events (e.g. Earthquakes, Hurricanes) and associated paths are predicted and monitored closely in advance and allow to take pre-event proactive control actions. The Distribution Phasor Measurement Units (D-PMUs) provide new opportunities and supporting such proactive actions. Here, a synchrophasor based resiliency driven pre-event reconfiguration can ensure minimizing impact of the expected event on the power distribution system and associated performance. However, the D-PMUs will also face challenges in terms of data quality similar to the transmission PMUs. The focus of this paper is to provide data mining approaches for anomaly detection in D-PMUs and proposing resiliency-driven pre-event reconfiguration with islanding as a proactive mechanisms to minimize the impact of adverse events on system using processed synchrophasors data. Results are validated for real industrial feeders and test cases with satisfactory response
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Pandey, Shikhar, Chanda, Sayonsom, Srivastava, Anurag K., Hovsapian, Rob O.. 2020-01-22. Resiliency-Driven Proactive Distribution System Reconfiguration With Synchrophasor Data. https://doi.org/10.1109/tpwrs.2020.2968611. https://engineeringpapers.com/record/osti%3A1810550/resiliency-driven-proactive-distribution-system-reconfiguration-with-synchrophasor-data
Citations retain the original authors and DOI and include this site’s record URL. If this discovery service contributed to your research, you can also cite Engineering Papers by Indiciae: BibTeX · RIS.