NASA NTRS · 19800008316
Cooling tower water conditioning study
Abstract
Successful elimination of cooling tower treatment chemicals was demonstrated. Three towers functioned for long periods of time with ozone as the only treatment for the water. The water in the systems was reused as much as 30 times (cycles of concentration) without deleterious effects to the heat exchangers. Actual system blow-down was eliminated and the only makeup water added was that required to replace the evaporation and mist entrainment losses. Minimum water savings alone are approximately 75.1 1/kg/year. Cost estimates indicate that a savings of 55 percent was obtained on the systems using ozone. A major problem experienced in the use of ozone for cooling tower applications was the difficulty of accurate concentration measurements. The ability to control the operational characteristics relies on easily and accurately determined concentration levels. Present methods of detection are subject to inaccuracies because of interfering materials and the rapid destruction of the ozone.
Keep this discovery
Explore connections, maps & timelines
Humphrey, M. F., French, K. R.. 1979-12-15. Cooling tower water conditioning study. https://ntrs.nasa.gov/citations/19800008316
Cite the original work for its findings. Save a collection to share your selection of sources.