Engineering PapersSearch

Engineering topics

Shamim, Jubair A. [Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)] (ORCID:0000000208162691)

Publications and source records attributed to Shamim, Jubair A. [Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)] (ORCID:0000000208162691).

Coupled heat and mass transfer in internally cooled silica gel-coated aluminum foam heat exchangers for dehumidification

Solid desiccant dehumidifiers offer significant potential to improve humidity control in buildings due to their ability to independently regulate latent (humidity) and sensible (temperature) loads. However, adsorption of water vapor by desiccants is an exothermic process; the resulting heat of adsorption increases both the desiccant bed temperature and the temperature of the air flowing over the bed, thereby limiting the performance of desiccant dehumidifiers. To address this problem, desiccant-coated heat exchanger prototypes were developed by coating silica gel onto aluminum foam substrates and integrated with chilled water circulation for effective removal of the heat of adsorption. Prototype heat exchangers with two different pore densities (10 and 20 pores per inch (PPI)) and two different desiccant loadings (∼10.36% and ∼17.80%) were fabricated. Experiments were conducted by varying the inlet air face velocity, chilled water inlet temperature, and chilled water flow rate to investigate the coupled heat and mass transfer characteristics of the prototype heat exchangers over a wide range of operating conditions. The underlying transport mechanisms were analyzed using transient desiccant bed temperature, outlet air temperature, and outlet humidity profiles. The results demonstrate that internal cooling significantly enhances dehumidification performance by maintaining more favorable thermodynamic conditions for water vapor adsorption. Under identical operating conditions, a 20 PPI heat exchanger coated with 25.05 g of silica gel achieved 98.98% higher cumulative water uptake and 97.75% higher moisture removal capacity than the corresponding non-cooled case after 5 min of adsorption. This substantial enhancement was further supported by a validated one-dimensional coupled heat and mass transfer model developed in the present study. To date, this is one of the first experimental studies to systematically investigate the combined effects of internal cooling, foam pore density, and desiccant loading on the performance of silica-gel-coated metal foam heat exchangers under HVAC-relevant operating conditions.

42 ENGINEERING

On the validity and limitations of 1D model for heat and mass transfer performance evaluation in a multilayer binder-free desiccant dehumidifier: isothermal dehumidification with internal cooling

Efficient humidity control is essential for maintaining indoor thermal comfort, yet conventional vapor-compression-based dehumidifiers are energy-intensive. Employing separate sensible and latent cooling through desiccant-coated heat exchangers (DCHEs) combined with evaporative coolers offers energy savings of up to 80 % compared to conventional systems. However, the dehumidification performance of DCHEs remains limited due to the use of polymer binders for coating desiccant materials onto heat exchange surfaces. In our previous study, we developed a multilayer fixed-bed binder-free desiccant dehumidifier (MFBDD) that demonstrated high dehumidification capacity and low pressure drop compared to rotary desiccant wheels. Nevertheless, its potential for further enhancement through internal cooling and the use of step-shaped adsorption isotherms has not been explored. In this study, a physics-based one-dimensional (1D) transient model is developed and validated to capture the coupled heat and mass transfer processes in the MFBDD and extended to simulate internal cooling using a high-capacity composite metal–organic framework, MIL-101/GO-6 (water uptake ≈1.6 g/g within 35–47 % RH). The model enables detailed analysis of local air and bed temperature dynamics and quantifies how internal cooling affects the dehumidification performance under a wide range of operating conditions. Results show that integrating internal cooling and using MIL-101/GO-6 enhance mass adsorbed, moisture removal capacity, and dehumidification effectiveness by 50 %–99 % compared with the M.S. Gel baseline. The study further reveals that achieving near-isothermal operation requires simultaneous enhancement of the convective heat transfer coefficient and heat exchange surface area. In conclusion, this work provides the first detailed physical insight into the interplay between internal cooling and step-shaped isotherms in a binder-free desiccant device and establishes a validated modeling framework for scaling up and system-level performance evaluation of next-generation energy-efficient dehumidification systems.

Heat and mass transfer

Review of the potential and challenges of MOF-based adsorption heat pumps for sustainable cooling and heating in the buildings

Heat pumps are regarded as the most suitable means to meet the future demand of heating and cooling in the building, as they require small input of electrical energy and output high thermal energy. Vapor compression heat pump (VCHP) and transcritical-CO 2 heat pump are the two major heat pump technologies currently dominating the market. However, VCHP system suffers from its fugitive emission of hydrofluorocarbon (HFC) refrigerants, and transcritical-CO 2 system requires high operating pressure (typically 9–13 MPa). For low-to-medium temperature heating and cooling applications thermally driven adsorption heat pump (AHP) provides a better alternative to VCHP and transcritical-CO 2 system as AHP uses natural refrigerants and operates at a much lower pressure. But currently available AHP technology has the limitation of low coefficient of performance (COP). Advances in synthesizing metal-organic frameworks (MOF) with high gas adsorption capacity have created an opportunity to address the problem of low COP of current AHP technology. Here, this article reviews the progress made in the past decade in utilizing MOF and conventional adsorbents with different working fluids in AHP technology and compares their performance. The article also summarizes the key challenges for the MOF-based AHP technology and provides the authors’ perspective to address these challenges.

30 DIRECT ENERGY CONVERSION

Advances in Desiccant Wheels for Dehumidification, VOC Mitigation, and CO 2 Removal for Energy-Efficient IAQ Management

Humidity control is pivotal to maintain occupant thermal comfort and suppress mold growth in indoor environments. Furthermore, poor indoor air quality (IAQ) due to the presence of volatile organic compounds (VOCs) and high concentrations (>1,000 ppm) of CO 2 can cause health issues and negatively affect cognitive performance. Therefore, providing high-quality indoor air has gained significant attention over the past decade. Conventional cooling coil and filter-based HVAC systems have limited capability to meet the augmented demand for occupant thermal comfort and high indoor air quality. Moreover, modern buildings are increasingly airtight to save energy, and increasing ventilation to mitigate VOC and CO 2 concentration is discouraged. Separate sensible and latent cooling technology using a rotary desiccant wheel presents a promising solution in this respect. Because of the development of desiccant materials with high water vapor, VOC, and CO 2 uptake, desiccant wheels can be used as an integrated technology option for IAQ management. Here, to promote desiccant wheel use for energy-efficient management of IAQ in buildings, this article reviews recent advancements in using desiccant wheels for dehumidification, VOC mitigation, and CO 2 capture from outdoor air. Finally, the article presents the authors’ perspective by summarizing the key research gaps in the field and discussing the future direction of research to address these gaps from two different aspects, namely, suitable adsorbent material development and desiccant wheel design.

CO2 capture