Real-Time Lifetime Prediction of Semiconductor Devices Using Hardware-in-the-Loop

This paper presents a unique approach to enable real-time lifespan prediction of semiconductor power modules using a Hardware-in-the-Loop (HIL) system. By integrating the module's overall loss characteristics-specifically switching and conduction losses-with a thermoelectric model of the thermal management system, this research demonstrates that the model can dynamically estimates the junction temperature profile of the semiconductor devices in response to a changing torque demand profile for the motor drive system. This capability enables continuous monitoring of the module's operational time and cumulative stress induced on the devices to compute accumulated remaining lifetime or time-to-failure (TTF). This study provides an architectural framework for the HIL system with high-fidelity component models of multiple physical domains, allowing simulation of dynamic behaviors of a closely-coupled motor drive system. The advanced real-time computation and measurement functionalities of the HIL system allow for both dynamic lifetime calculations based on simulated data and aggregate lifetime predictions utilizing historical data. Moreover, this paper details an algorithm that not only computes cumulative damage but also synthesizes these data into a comprehensive aggregated lifetime metric. This methodology can enhance the maintenance scheduling strategies and operational reliability of semiconductor devices in critical applications, ultimately extending their service life while optimizing performance.

hardware-in-the-loop (HIL)↗

Small-Signal Stability of Grid-Forming Inverters Using Current-Limiting and Frequency Stabilization

This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.

current limiting↗

Modified Andronov-Hopf Oscillator-Based Grid-Forming Converter with Emulated Virtual Cable for Enhanced Power Sharing Performance

Nonlinear oscillator-based grid-forming converters offer superior dynamic and steady-state performance, making them an attractive solution for interconnecting renewable resources. This paper proposes a novel modified Andronov-Hopf oscillator to enhance the operating spectrum and facilitate the integration of renewable energy sources. An inner loop controller based on the Lyapunov energy function is implemented to achieve robust stability and performance, while a virtual cable emulation strategy enables seamless parallel operation. Comprehensive modeling and simulation studies validate the effectiveness of the proposed system, demonstrating its capabilities in addressing diverse operating scenarios, including grid faults, renewable energy fluctuations, and parallel operation. The proposed solution exhibits fast transient response, robust stability, and flexible operation, making it a valuable contribution to the field of renewable energy integration. The results of this study can be used to inform the design and implementation of next-generation grid-forming converters, enabling a more sustainable and reliable energy future. Additionally, the proposed system's ability to operate in both grid-connected and islanded modes makes it an ideal candidate for remote and off-grid renewable energy applications. The proposed solution's scalability and modularity also make it suitable for large-scale renewable energy integration. The proposed system is verified through MATLAB/Simulink and PLECS simulations, demonstrating its effectiveness in ensuring robust and efficient operation.

Andronov-Hopf Oscillator (AHO)↗

Evaluation of Converter Performance Considering Static and Dynamic Device Part-to-Part Variability

This paper presents a methodology to incorporate and analyze the impact of semiconductor device part-to-part variation on power converter performance. By integrating extensive static and dynamic device characterization data with an automated compact model generation process that reflects manufacturing variability, device models with inherent variability features are utilized in converter simulations for a comprehensive assessment of performance impacts. The traditional converter performance evaluation process typically yields fixed efficiency values, often dismissing the inherent part-to-part variability caused by the manufacturing process of semiconductor devices. To address this limitation, a large population of devices was characterized to capture variations in static parameters-such as transfer, output, and capacitance characteristics-as well as dynamic behaviors, including switching losses. This data-driven approach enables the development of individual compact models, which were then integrated into converter simulations to evaluate efficiency ranges rather than single point estimated values. The converter simulation results show that part-to-part component variation can lead to significant efficiency deviations, exceeding several percentage points in high-power conversion applications. By offering a more accurate representation of converter behavior under real-world manufacturing conditions, this methodology enables designers to anticipate performance variability, improving the robustness of power converter designs.

device characterization↗

Equivalent-Circuit Models for Grid-Forming Inverters under Unbalanced Steady-State Operating Conditions: Preprint

Positive- and negative-sequence equivalent-circuit models are put forth to capture the operation of grid-forming (GFM) inverters in unbalanced steady-state operating conditions acknowledging the impact of current limiting. The particular control architecture examined adopts droop control (for primary control), nested inner-current and outer-voltage control (in the stationary reference frame), and it is adaptable to two different types of current limiting (current-reference saturation and virtual-impedance limiting). We anticipate the proposed models to be of interest in modeling, analysis, and simulation of GFM inverters in unbalanced settings that may arise, e.g., in the face of faults. Validation of the equivalent-circuit models is pursued via comparison with full-order electromagnetic-transient (EMT) simulations for representative balanced and unbalanced faults.

equivalent-circuit models↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: Droop, Virtual Synchronous Machine (VSM), and dispatchable Virtual Oscillator Control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy, and with no explicit tuning of the solver, lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

electromagnetic transient simulation↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations: Preprint

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: droop, virtual synchronous machine (VSM), and dispatchable virtual oscillator control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy with up to 150x lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

circuit-equivalent model↗

Multilevel Cybersecurity for Photovoltaic Systems

The motivation behind this project is to protect critical infrastructure in electric power generation pertaining to solar photovoltaic (PV) systems. This growing renewable energy resource is becoming a more vital part of the nation’s energy portfolio, particularly since it has achieved grid-parity to existing generation methods in terms of cost. It is thus vital that steps be taken to ensure the cybersecurity of these assets. The project goal was to devise a multilevel cybersecurity solution to address PV security gaps at the inverter and system levels, and field test the solution under the supervision and review of a US-based solar inverter manufacturer and PV installer/operator. A two-level cyberattack defense approach was formulated whereby the first level, the solar inverter level, hardens individual devices and achieves a deeply cyber-secure inverter. The inverter level security involves a multi-layer defense-in-depth approach for securing the inverter while also providing data for the system level algorithms. The second level, the system level, addresses intrusion detection and restoration involving an ensemble of inverters and relevant systems.

14 SOLAR ENERGY↗

Grid Integration of Offshore Wind Power: Standards, Control, Power Quality and Transmission

Offshore wind is expected to be a major player in the global efforts toward decarbonization, leading to exceptional changes in modern power systems. Understanding the impacts and capabilities of the relatively new and uniquely positioned assets in grids with high integration levels of inverter-based resources, however, is lacking, raising concerns about grid reliability, stability, power quality, and resilience, with the absence of updated grid codes to guide the massive deployment of offshore wind. To help fill the gap, this paper presents an overview of the state-of-the-art technologies of offshore wind power grid integration. First, the paper investigates the most current grid requirements for wind power plant integration, based on a harmonized European Network of Transmission System Operators (ENTSO-E) framework and notable international standards, and it illuminates future directions. The paper discusses the wind turbine and wind power plant control strategies, and new control approaches, such as grid-forming control, are presented in detail. The paper reviews recent research on the ancillary services that offshore wind power plants can potentially provide, which, when harmonized, will not only comply with regulations but also improve the value of the asset. The paper explores topics of wind power plant harmonics, reviewing the latest standards in detail and outlining mitigation methods. The paper also presents stability analysis methods for wind power plants, with discussions centered on validity and computational efficiency. Finally, the paper discusses wind power plant transmission solutions, with a focus on high-voltage direct-current topologies and controls.

17 WIND ENERGY↗

Parallel Grid-Forming Inverter-Driven Black Start: Power-Hardware-in-the-Loop Validation: Preprint

With power systems encountering increasing deployment levels of inverter-based resources (IBRs), system restoration using grid-forming (GFM) IBRs has gained attention. Engineered to establish grid voltages in the absence of a stiff grid, black-start-capable GFM IBRs are expected to enhance power system resilience by playing a critical role in bottom-up system restoration. This paper experimentally studies the feasibility of the novel approach through power-hardware-in-the-loop (PHIL) testing and validation with a commercial GFM inverter. The PHIL test setup demonstrates an inverter-driven black start of a 5-MW unbalanced distribution feeder where two GFM inverters collectively black start the feeder: one is a commercial hardware GFM inverter interacting through the PHIL interface, and the other is a software GFM emulated by a real-time simulation with full electromagnetic transient (EMT) models. Both GFM inverters are equipped with negative-sequence voltage control to suppress the voltage imbalance resulting from the unbalanced loading, allowing us to study the dynamic interactions between the GFMs with their control parameters unknown. To evaluate the dynamic behavior of the GFM inverters under the entire black-start process, the EMT model of the distribution system details the transformer and motor dynamics to emulate their inrush and startup behaviors. It abstracts conventional grid-connected inverter dynamics, i.e., grid-following inverters. Oscilloscope measurements of the hardware GFM inverter are also presented for critical steps. Takeaways for further study and field deployment are provided.

grid-forming inverter↗

Large-Signal Stability Improvement of Parallel Grid-Forming Inverter-Driven Black Start: Preprint

With the rapid increase of inverter-based resources in modern grids, advanced grid-forming (GFM) inverter capa- bilities, such as system restoration and operation under faults, are urgently needed to realize power electronics-dominant grids at scale. One such capability is inverter-driven black start using GFM inverters. This paper analyzes the ability of two recently proposed advanced GFM controls to help GFM inverters sustain system-wide, off-nominal conditions and remain synchronized until they can overcome the momentary overloading as more GFMs join the process without generator sequence coordination or communications and finally stabilize the grid. Through an extensive set of 1,200 full-order electromagnetic transient simu- lations, we evaluate the black-start process while employing the various GFM inverter controls. The results show that the GFM current limiter and primary control have a significant impact on the stability of the system during dynamic operating conditions and thus impact the success of inverter-driven system restoration.

current limit↗

Chapter 32 - Power Grid Resilience

The new energy paradigm is altering the current power grid trend from synchronous generator reliant system toward power-electronics-based distributed energy resources (DERs). The resilient operation of modern power grid is highly dependent upon cyber and physical reliable operation of DERs. Power grid resilience broadly refers to the ability of the grid to be robust to eventualities and singularities that may disrupt the continuity of reliable power flow. This could involve resilience related to the physical system but more recently, the focus on cyber resilience has been evolving rapidly especially given the burgeoning growth of distributed generation and power-electronics-based DERs under smart grid and given that such threats to reliable operation do not have to evolve localized to where the physical asset is. Commonly, in power grids dominated by DERS, control and energy management are structured at a multitime scale multilayer fashion: (i) primary control layer at microseconds time scale, (ii) secondary control layer at millisecond time scale, and (iii) tertiary control layer at seconds to minutes time scale. The cyber-related issues that may affect the power grid resilience can be introduced in through primary, secondary, and tertiary control layers. The failure of each of these control layers may impact the reliable and resilient operation of the overall network and cause widespread failures which leads to unintended blackouts. As such, this chapter focuses on cyber-related resilience issues in primary control layer, secondary control layer, tertiary control layer, wide area/utility control, and anomaly detection and resilient communication.

anomaly detection↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

Performance Specifications for Grid-Forming Technologies

Standards and specifications for inverter-based resources (IBRs) focus primarily on grid-following (GFL) technologies at present. Therefore, these may generally not be appropriate for application in power systems to ensure acceptable operation with grid-forming (GFM) technologies. In some cases, the direct application of prevailing standards and specifications may not be appropriate for - or may even inadvertently limit the potential of - GFM resources. The Universal Interoperability for Grid- Forming Inverters (UNIFI) Consortium is a U.S. Department of Energy funded effort to advance GFM technology. The UNIFI team brings together academic, industrial, and national-lab researchers as well as industry stakeholders (utilities, system operators, vendors) to collaboratively pursue advances in a broad range of GFM technologies. This paper introduces a set of system- and unit-level specifications driven by consensus across the UNIFI project team. These are intended to seamlessly integrate GFM technologies at any scale into power-systems operation and control in a vendor-agnostic manner. A suite of illustrative simulation results that demonstrate the application of and adherence to the proposed specifications are included.

grid-forming inverter↗