Emulation and detection of physical faults and cyber-attacks on building energy systems through real-time hardware-in-the-loop experiments

The increasing use of remote or mobile access, integrated wearable technologies, data exchange, and cloud-based data analytics in modern smart buildings is steering the building industry towards open communication technologies. The increased connectivity and accessibility could lead to more cyber-attacks in smart buildings. On the other hand, physical faults (e.g., HVAC -heating, ventilation, and air-conditioning faults) may have similar adverse impacts as those from the cyber-attacks on building energy systems, such as occupant discomfort, energy wastage, and equipment downtime. However, current physical behavior-based anomaly detection methods fail to differentiate between cyber-attacks and physical faults in building energy systems. Moreover, the challenge in collecting real-world threat data with ground truth has led researchers to rely on numerical models with user-defined assumptions, which may not accurately reflect real-world conditions due to the lack of in-situ experimental datasets. To address these challenges and gaps, this paper presents a flexible hardware-in-the-loop (HIL) testbed for generating cyber-attack and physical fault datasets and demonstrating threat detection algorithms in a real building automation system (BAS) environment. This testbed combines hardware (i.e., real BAS with local HVAC controllers and a physical network) with software (i.e., high-fidelity models to represent behaviors of building envelope and HVAC energy systems), enabling emulations of realistic threats. Five HIL experiments, including one baseline without any threats, two with physical faults, and two with cyber-attacks, were conducted to generate datasets containing detailed network traffic and system states. A joint classification framework, incorporating a network analyzer and a physical HVAC fault detector, was proposed to automatically detect cyber-physical abnormalities on BAS at both the network and the physical HVAC levels. The network analyzer comprises a conditional random fields (CRF) based command validator and a statistics-based detection strategy. The fault detector employs a weather and schedule-based pattern matching and feature-based principal component analysis (WPM-FPCA) method. Evaluation of the classification using four metrics from the multi-class confusion matrix revealed an average accuracy of 90.2%, recall of 89.7%, precision of 88.5% and F1-score of 89.2%. Finally, these results demonstrate that the proposed joint classification framework can effectively differentiate between specific types of cyber-attacks (e.g., device reinitialization attack, network Denial-of-Service attack) and physical faults (e.g., air handling unit operational fault, cooling coil valve stuck) in real time for improved building energy management.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A hardware-in-the-loop (HIL) testbed for cyber-physical energy systems in smart commercial buildings

In recent years, there has been a growing trend toward the development of smart buildings that rely on cyber-physical systems (CPS) to optimize occupant comfort, safety, and energy efficiency. To ensure the reliable and efficient operation of CPS with designed control strategies, it is important to evaluate their performance under various scenarios before deploying them in the real world. This is where a Hardware-in-the-loop (HIL) testbed designed for studying sensor and control-related studies in smart buildings can be highly valuable. With the growing threat of cyber-attacks and physical faults targeting smart buildings, it is essential to ensure the security of building operations. A HIL testbed can emulate cyber-attack and physical fault scenarios, allowing researchers to develop and test threat detection and mitigation algorithms. This enables researchers to identify potential issues and optimize the algorithms in a safe and controlled environment before they are deployed in real-world settings, reducing the risk of failures that can negatively impact occupant comfort, safety, and energy efficiency. Therefore, this paper developed a HIL testbed designed for cyber-physical energy systems (e.g. buildings automation system (BAS)) in smart commercial buildings. The HIL testbed is comprised of a real-time building and Heating, Ventilation, and Air-Conditioning (HVAC) emulator using Modelica-based dynamic models, a set of BAS controllers, and a BAS computer server. The data generation capability of the HIL testbed is demonstrated by tracking normal and faulty operating data in the BAS, as well as monitoring detailed network traffic in the local BAS network. Here, this study further demonstrates the HIL testbed’s capability by conducting case studies on real-time physical fault and cyber-attack experiments using a Department of Energy (DOE) prototype commercial building. It is anticipated that the fully functional HIL testbed will be utilized for a variety of sensor and control-related studies, including but not limited to testing, developing, validating of different HVAC control strategies, fault detection & diagnosis, energy monitoring and analysis, cyber security study, etc.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Securing Grid-interactive Efficient Buildings (GEB) through Cyber Defense and Resilient System (CYDRES)

The DOE CYDRES project is driven by the urgent need to address critical research gaps in the domain of cyber-physical security of smart buildings, including Grid-interactive Efficient Buildings (GEBs). CYDRES, a real-time advanced building resilient platform, aims to enhance the cyber-attack-immune capabilities of buildings through multi-layered prevention, detection, and adaptation mechanisms. CYDRES consists of five key modules: a multi-layer network analyzer, an Automatic Fault Detection, Diagnosis, and Prognosis (AFDDP) framework, an intelligent mode selector, a cyber-resilient control framework, and a situation awareness platform. The Network Analyzer employs a data-driven framework that includes a protocol state learning tool and a CRF (Conditional Random Field) command validator. In Hardware-In-the-Loop (HIL) testbeds, it achieved 100% detection accuracy with a false alarm rate of 3%, validating its efficacy in identifying selected cyber-attacks. The AFDDP framework leverages pattern matching, PCA (Principal Component Analysis)-based strategies, and a DBN (Dynamic Bayesian Network)-based fault diagnosis approach to pinpoint the causes of physical system abnormalities using Building Automation System (BAS) data. In HIL experiments, the AFDDP module attained a detection accuracy of over 95% with a false alarm rate below 7%. Additionally, the fault detector utilized machine learning (Random Forest) and deep learning (Multi-Layer Perceptron) methods with acoustic sensor data to achieve a 100% fault detection accuracy in Heating, Ventilation, and Air-Conditioning (HVAC) equipment. The Mode Selector offered real-time impact analysis, allowing immediate actions to protect BASs in the face of emerging threats. The cyber-resilient control framework included an adaptive Model Predictive Control (MPC) and a measurement compensator, reducing temperature violations by up to 94% and improving the total demand flexibility by up to 70% in HIL experiments. Such HIL experiments covered a cyber-attack case and a physical fault case, showcasing CYDRES’ efficiency in maintaining operational continuity during threats. The situation awareness platform in Grafana enhanced real-time threat detection and response visualization, augmenting the operational awareness for building operators. CYDRES demonstrated high technical effectiveness in various test scenarios, particularly in HIL environments. The project's phased development approach ensured efficient use of resources, highlighting its practical feasibility and readiness for commercialization. By enhancing the security and resilience of building operations, CYDRES represents a significant advance in mitigating risks associated with cyber-physical systems, thereby enhancing public confidence in the safety of modern building infrastructure. Future directions for the project include expanding testing protocols, refining AFDDP methodologies, exploring more comprehensive resilient control strategies, and testing in real commercial buildings.

42 ENGINEERING↗

Dynamic Bayesian Networks for Fault Prognosis

A dynamic Bayesian Network (DBN)-based fault prognosis framework is proposed in this study to predict the future fault probabilities of gradual faults. The proposed framework utilizes the trend in prediction error generated from data driven forecasting models to estimate the future fault beliefs. The accuracy and scalability of the proposed method is evaluated using the data from a Modelica-based virtual testbed. Overall, the developed framework demonstrates good potential in estimating future fault probabilities of gradual faults.

Pradhan, Ojas↗

CYDRES: CYber Defense and REsilient System for securing grid-interactive efficient buildings

Smart buildings, especially Grid-interactive Efficient Buildings (GEBs), suffer from cyber-attacks and physical faults due to the integration of a large number of sensors and controls, connected devices, and associated communication networks. This study demonstrated a real-time advanced building resilient platform, called CYber Defense and REsilient System (CYDRES), which is deployable for existing and emerging Building Automation Systems (BASs). CYDRES aims to empower GEBs with cyber-attack-immune capabilities through multi-layer prevention and adaptation mechanisms to monitor, detect, and respond to cyber-attacks and physical operational faults. CYDRES is demonstrated through real-time experiments in a Hardware-in-the-Loop (HIL) testbed.

Building automation system, Cyber-attacks, Physica↗