App Deconfliction: Orchestrating Distributed, Multi-Agent, Multi-Objective Operations for Power Systems
Not Available
Engineering topics
Publications and source records attributed to Poudel, Shiva.
Not Available
Not Available
Electric utilities are facing the need for better monitoring, analysis, and control of their distribution systems. An accurate mathematical model is a key to both the development of cutting-edge, scalable model-based algorithms and the assessment of emerging technologies such as distributed energy resources (DER) for grid planning and operation. However, the constantly evolving nature of power distribution systems poses challenges to maintaining accurate models. In this paper, we propose a novel load flow based approach to validate power distribution models. Networked equipment models described according to the Common Information Model (CIM) standard and a measurement model are used to formulate the distribution load flow problem. First, a system admittance matrix (Ybus) is derived from device-level CIM parameters. Next, the operational parameters (dynamic Ybus and nodal injections) are extracted from the measurement model using sensor configuration and equipment state. An iterative power flow method is then used to compute nodal voltages and branch flows that are compared against the measurement data to find any inconsistencies in the networked equipment model. This approach is implemented within GridAPPS-D, an open-source standards-based platform for advanced distribution management system (ADMS) application development, and demonstrated on the IEEE 13-bus, 123-bus, and 8500-node test feeders.
The 9500 Node Test System is a representative section of distribution power system model developed as a part of the GridAPPS-D™ project, an effort funded by DOE as a part of the Grid Modernization Lab Consortium (GMLC) program. The test system was developed to fulfill a growing need to represent the rapidly evolving state of electric distribution systems by combining elements of legacy infrastructure systems, modern feeder topologies, and an anticipated future with smart grid technologies. It also provides a network model capable of supporting the simulation of operational scenarios such as the ones in a utility distribution control center. This test system allows the evaluation of the performance of advanced power applications in real-time, such as one that simulates the operations of an Advanced Distribution Management Systems (ADMS), Distributed Energy Resource Management Systems (DERMS), etc. in a Distribution control center. This model is an extension of the widely used IEEE 8500 Node Test Feeder and is currently being validated to become an IEEE test case to help increase adoption and widespread usage among both academia and industry. It is a full-size model representative of a section of a utility’s distribution system with multiple feeders fed from different substations. The model includes multiple distribution circuits, a sub-transmission system, multiple substations, behind the meter customer rooftop photovoltaics (PV), and multiple utility-scale distributed energy resources. To enable accurate simulations of operational scenarios, the 9500 Node Test System is designed to support procedure-based operations, with the ability to realistically demonstrate switching operations, feeder reconfiguration, adjustment of volt-var control equipment, dispatch of distributed generation, and response to planned and unplanned outages. The 9500 Node Test System includes three radial distribution feeders with 12.3 MVA of average load, consisting of both medium voltage and low voltage equipment each supplied by a different distribution substation. The three distribution feeders are connected to each other through Normally-Open switches which can be closed when needed to simulate restoration scenarios due to a fault. One feeder represents today’s grid with low penetration of customer-side renewables. The second represents a potential future grid with microgrids and 100% renewable penetration. The third has no customer generation resources, a district steam plant, and a utility-scale solar farm. The three diverse circuits were created to allow the simulation of both today’s situation as well as potential future scenarios. All three feeders have customers connected by low-voltage secondary triplex lines. This test system meets all requirements outlined in the report for creating a simulation environment that would enable discussion between key technical stakeholders as well as having the potential to accelerate operational application development and their subsequent testing and integration. The new model is a possible representation of what we believe the distribution grid may look like in the future: a high penetration of renewables, reconfigurable radial and mesh topology, numerous DERs, islanded microgrids, and significantly increased data and measurement density. The system supports both the solution of existing and newer algorithms but also enables the evaluation of applications in a realistic operational environment defined by task oriented procedural steps that represent the interaction between the control center operator and field personnel.
It is of growing concern to ensure resilience in power distribution systems to extreme weather events. However, there are no clear methodologies or metrics available for resilience assessment that allows system planners to assess the impact of appropriate planning measures and new operational procedures for resilience enhancement. In this paper, we propose a resilience metric using parameters that define system attributes and performance. To represent extreme events (tail probability), the conditional value-at-risk of each of the parameters are combined using Choquet Integral to evaluate the overall resilience. The effectiveness of the proposed resilience metric is studied within the simulation-based framework under extreme weather scenarios with the help of a modified IEEE 123-bus system. With the proposed framework, system operators will have additional flexibility to prioritize one investment over the others to enhance the resilience of the grid.
Pacific Northwest National Laboratory's (PNNL) co-simulation platform (CSP) for the Microgrids, Infrastructure Resilience, and Advanced Controls Launchpad (MIRACL) project, also known as MIRACL-CSP, is a functional layer designed and developed to oversee the operational exchanges of data at the application level to and from different resources residing on the MIRACL Data Hub shared platform. MIRACL-CSP allows virtual interactions between various data hub resources during co-simulation runtime.
The current practices for restoring critical services in the distribution system during a disaster, align with the traditional centralized ideology of distribution systems operations. A central processor evaluates the distribution system after a disruption and attains a restoration plan. However, the centralized operational paradigm is susceptible to single-point failures, requires full situational awareness of the distribution system, and poses scalability challenges for large multifeeder distribution systems. This motivates a distributed decision-making paradigm where multiple agents solve smaller subproblems and jointly coordinate their individual decisions to achieve the global/network-level objective. Toward this goal, we propose a layered architecture for distributed algorithms for resilience and a two-stage distributed algorithm for distribution system restoration. The proposed distributed decision-making framework enables the bottom-up restoration of the distribution system using all available resources, including distributed generation, while only requiring local awareness and limited communications with neighboring connected regions. The proposed framework is robust to single-point failures, enables autonomy using distributed algorithms, and had reduced computational cost compared to centralized optimization solutions.
The rapid adoption of photovoltaic (PV) systems combined with falling prices of energy storage is paving the way for a future in which customers could locally supply their energy needs and export surplus power to the grid. However, reverse power flow from multiple sites in a network can cause overvoltage that decreases system reliability and the utilization level of PV system. In this paper, we present a two-stage approach to solve the energy coordination problem in distribution networks. In the first stage, a household with PV and energy storage is optimized to allow customers to adopt different control strategies such as load following and tariff arbitrage. We show that such customer-led control strategies can cause reverse power flows during peak PV generation periods, thus resulting in overvoltage. In such cases, the second stage of the proposed approach is called upon to solve a fairness-based energy coordination problem that can maintain voltages within limits while maximizing the PV generation while fairly distributing the actions among all the PV systems. As a result, each of the resources in the network has equal opportunity to export power and shares the responsibility of voltage regulation. Simulation studies have been carried out on the IEEE 13-bus test feeder to verify the effectiveness of the proposed approach.
Not Available
An accurate model of a power distribution system is the foundation for model-based applications that ensure efficient and reliable grid operation in an advanced distribution management system (ADMS) environment. However, these models are error-prone and comprehensive model validation is challenging due to lack of standards-based systems, data originating from disparate databases and other sources, and the constantly evolving nature of modern power distribution systems. In this paper, a novel framework for comprehensive model validation is described. The proposed application, the Model Validator, ensures that a model is both consistent and feasible by validating the derivative static and operational network model. A modular architecture for the application has been implemented and integrated with an open-source standards-based platform for ADMS application development, GridAPPS-D, allowing new validation capability to be added with minimal time and effort. The Model Validator application is demonstrated on the IEEE 13-bus, 123-bus, and 8500-node test cases over three validation scenarios.
Grid hardening is one of the most effective approaches that reduce the component failures and restoration efforts thus increasing the resilience of the power systems against extreme events. However, hardening and upgrading the entire system is prohibitively expensive and hence the optimal design of a distribution network is challenging. This paper adopted a reinforcement learning algorithm to identify the optimal hardening strategy to enhance the resilience of power distribution systems. Adopting the Q-learning algorithm as the reinforcement learning technique, we found the sequential optimal action for hardening measures to enhance the grid's resilience for the given budget. To identify the optimal strategy through Q-learning, Conditional Value at Risk (CVaR) is used as a rewarding metric. A study on the IEEE 123-bus test feeder validate the effectiveness of the proposed model and show how to effectively allocate budget limited resources to plan a resilient power distribution network.
Recent research in the literature proposed parameter-based functional forms to quantify the impact of disturbances on electric power grids. This modeling was based on a concept of generalized grid disturbances that harmonized reliability and resilience. Three main stages—avoid, react, and recover—were identified, and to support practicality, were intended to be independently planned. An objective of the grid disturbance model was to fairly analyze the potential impacts of novel mitigations like transactive energy systems (TES) on grid reliability and resilience. Quantitative evaluation of a common performance metric (e.g., area under the curve of percentage customers online before, during, and after an event) over time was shown as an effective tool for such analysis. Such quantification may also enable system planners to assess the impact of appropriate mitigative actions for improving grid performance against potential disturbances. This is the focus of this report, i.e., presenting an evaluation modeling framework that can be utilized to evaluate grid performance against disturbances, under a variety of existing and possible new mitigative actions.
Improving the reliability of power distribution systems is critically important for both utilities and customers. This calls for an efficient service restoration module within a distribution management system to support the implementation of self-healing smart grid networks. Although the emerging smart grid technologies, including distributed generators (DGs) and remote-controlled switches, enhance the self-healing capability and allow faster recovery, they still pose additional complexity to the service restoration problem, especially under cold load pickup (CLPU) conditions. Herein, a novel two-stage restoration framework is proposed to generate a restoration solutions with a sequence of control actions. The first stage generates a restoration plan that supports both the traditional service restoration using feeder reconfiguration and the grid-forming DG-assisted intentional islanding methods. The second stage generates an optimal sequence of switching operations to bring the outaged system quickly to the final restored configuration. The problem is formulated as a mixed-integer linear program that incorporates system connectivity, operating constraints, and the CLPU models. It is demonstrated that on using a multi-feeder test case, the proposed framework is effective in utilizing all available resources to quickly restore the service and generate an optimal sequence of switching actions to be used by the operator to reach the desired optimal configuration.
One of the major goals of new grid operation regimes, such as transactive energy systems (TESs), is to make the power grid more resilient to withstand natural or man-made disasters and potential reliability events, and to continue to serve the maximum number of its customers. But it is a well-known fact to system operators that not all customers are the same. This implies that any discussion of TESs’ impacts on the resilience of the power system should consider the needs of its critical customers (such as the power system operation centers, fire and police stations, and hospitals) over those of other customers. When evaluating the resilience of the system, bonus points must be awarded to any system that could maintain its power supply to critical customers during a disturbance that may cause an outage. This report discusses critical infrastructure (CI) as found in the literature and then categorizes it based on the field to which the operations belong (such as human life/safety-related, operations management, necessary city operation, industrial customers, etc.). Each of these CI categories is further divided into types of critical customers (e.g., the human life/safety-related category has different types of customers like hospitals, fire and police stations, etc.). The entire demand of each of the critical customer types is not categorized as critical load (CL); instead, only a portion of the total load of these critical customers is characterized as critical load. This is done based on the categories of equipment, the function of which is crucial in the operation of the overall facility. CL categorization is performed to provide the ratio of the critical load portion to the overall load , so that it can serve as a parameter in the resilience evaluation of the grid through a metrics-based approach. Such categorization is important as it helps to augment the existing quantifiable resilience metrics with CL categorization. The metrics for a power system need to not only consider how well a system performed during a disturbance event, but also how it reduced strain and supplied power to its CLs. The first step in this process is characterize CLs in the system. After CL characterization, the next step is the inclusion of these loads in the resilience metrics. To that end, in this report weight-based augmentation of resilience metrics is proposed, where certain customers (the ones that are categorized as critical) are assigned higher weights than others. Though an overview of assigning weights to customers is discussed, there is no one-size-fits-all approach for every power system. The decisions made about assigning such weights to customers vary greatly from one operator to another, based on their unique systems and the current and predicted states of critical customers. This decision-making can include the type of disturbance event, which might only affect certain parts of the system. In general, analyzing critical customers before an event helps understand system vulnerabilities. It also helps in planning and conducting operations during the event, evaluating system performance after the event, and supporting better planning for future events. An alternative to the current practices of managing the grid for outages is an innovative TES, which has the potential to provide a platform for including distributed energy resources for managing CLs. This report also describes how TES qualities can help (1) to maintain power supply to critical customers for uninterrupted operations and (2) to restore lost power supply to the critical customers rapidly.
An electric power grid is one of the complex infrastructures, and because of its complex nature, there is simply no way that outages can be completely avoided. Thus, a modern society that depends on reliable electric supply requires a resilient electric system that can recover from disruptions while integrating emerging smart grid technologies. Here, this article presents a novel approach for service restoration in a modern power distribution system with controllable switches and distributed generation (DG) resources for any kind of outage. The proposed framework supports both the traditional service restoration using feeder reconfiguration and the grid-forming DG-assisted intentional islands that are dynamically sized using algorithms based on the fault scenario, available resources, and priority of loads. The problem is formulated as a mixed-integer linear program that incorporates critical system connectivity and operating constraints. Simulations are performed to demonstrate the effectiveness of the proposed approach using a large-scale four-feeder 1069-bus three-phase unbalanced distribution test system. It is demonstrated that the framework is effective in utilizing all available resources in quickly restoring the power supply to improve resiliency during extreme events and is scalable for a large-scale unbalanced power distribution system.
Not provided.
Distribution grid, in general, is constructionally loopy but a radially operated network. Opening and closing of suitable tie-switches allow transition from one topology to another. Identifying the operational topology of a distribution system is essential for accurate control actions. This paper proposes a non-exhaustive search approach to detect the operational topology of the distribution feeder by estimating the switch statuses. In this work, a mixed-integer linear programming approach is proposed that finds the correct operational topology by identifying the system load demand and power flow variables that are closest to the corresponding measured values. The problem is constrained by distribution power flow and radial structure of the feeder. This formulation allows the inclusion of errors in power/line flow measurements making it more suitable for a practical distribution system. The proposed approach finds the correct operational topology without exhaustively searching for all possible topologies. We thoroughly validate the accuracy and effectiveness of the proposed approach in identifying correct operational topology using IEEE 123-node feeder with the help of numerous simulations studies. It is observed that the approach performs well even at very high percentages of load and flow measurement errors.
Extreme weather events have a significant impact on the aging and outdated power distribution infrastructures. These high-impact low-probability (HILP) events often result in extended outages and loss of critical services, thus, severely affecting customers' safety. This calls for the need to ensure resilience in distribution networks by quickly restoring the critical services during a disaster. This paper presents an advanced feeder restoration method to restore critical loads using distributed energy resources (DERs). A resilient restoration approach is proposed that jointly maximizes the amount of restored critical loads and optimizes the restoration times by optimally allocating grid's available DER resources. The restoration problem is modeled as a mixed-integer linear program with the objective of maximizing the resilience to post-restoration failures while simultaneously satisfying grid's critical connectivity and operational constraints and ensuring a radial operation for a given open-loop feeder configuration. Simulations are performed to demonstrate the effectiveness of the proposed approach using IEEE 123-node feeder with 5 DERs supplying 11 critical loads and IEEE 906-bus feeder with 3 DERs supplying 17 critical loads. The impacts of DER availability and fuel reserve on restored networks are assessed and it is shown that the proposed approach is successfully able to restore a maximum number of critical loads using available DERs.