Engineering Papers⌕ Search

Engineering topics

Maitra, Arindam

Publications and source records attributed to Maitra, Arindam.

SOLAr Critical Infrastructure Energization (SOLACE): Leveraging Distributed Energy Resources to Provide Local Power

This document is a technical report based on a large-scale DOE-funded project conducted between 2019 and 2022. The project, called SOLAr Critical infrastructure Energization (SOLACE), is aimed at leveraging distributed energy resources (DERs) to provide local power to communities, feeders, or other regions. The project included a particular focus on high-value critical loads such as municipal water supply, telecommunication hubs, and disaster shelters. The key developments of the project were: (1) A comprehensive pre-event power system analysis methodology that identifies and characterizes the viable local power options. (2) A DMS-based example control system for activating and operating the local power solution during a time of crisis. (3) Grid-forming inverter technology to enable isolated local power operation and black-starting. (4) Cyber-security considerations for isolated systems when wider-area communication may be offline. This report describes the overall process that identifies and assesses the viable DER-based local power solutions for a given facility, region, or community. The report documents the process, including the key analysis steps, tools required, data requirements, and recommended pass/fail criteria for each step. It also provides a sample implementation of this process through a test case. Finally, it provides details of how a viable pre-event plan can be selected and activated at go-time when an event has occurred.

14 SOLAR ENERGY↗

Hardware-in-the-Loop Test Bed and Test Methodology for Microgrid Controller Evaluation

Increasing penetration levels of distributed energy resources are making the deployment of microgrids more feasible. Controllers that operate such microgrids are key to realizing the objectives of the microgrid owner or operator and there is a need to evaluate microgrid controller performance prior to field deployment. This paper describes a controller hardware-in-the-loop and power hardware-in-the-loop microgrid controller test bed that was designed and constructed to evaluate the capabilities of a microgrid controller for a proposed campus microgrid. This paper also presents a test methodology to evaluate microgrid controller functionality, and it describes how the controller was assessed through the application of different test scenarios. Results from the testing are presented to provide insight into the capabilities of the test bed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid Interactive Microgrid Controller for Resilient Communities (Final Report)

The objective of this project was to determine microgrid controller requirements using a use-case approach, then develop, configure and validate the performance of an advanced microgrid controller capable of managing from 1 to 10 megawatts (MW) of aggregated generation capacity to meet the performance targets outlined in DOE Funding Opportunity Announcement (FOA) DE-FOA-0000997 “Microgrid Research, Development, and System Design” and support the expanding deployment of commercial scale microgrid systems. The project aimed to develop and validate a commercially viable and flexible microgrid controller, easily adapted to different end-user community applications and to a range of electric grid characteristics with the primary outcome of the project being a standard operational model that can be deployed at multiple communities, each with unique resources and resiliency requirements. Spirae’s Wave™ microgrid controller was the advanced microgrid controller utilized in this project. The Spirae Wave™ control platform provides a scalable architecture for integrating and managing high levels of renewable and distributed energy resources (DER) at the edge of the grid. The motivation for the project is a result of the increased interest in microgrids resulting from the confluence of a number of important factors 1) Costs of distributed generation of many different types continues to decrease. This includes gas-based generation that has benefited from the lower cost of natural gas as well as renewable generation (solar, wind, hydro), 2) Storage development for many different industries is lowering its cost for the electric power industry. Storage is a key element of a microgrid to provide the flexibility of operation needed, 3) Applications like combined heat and power further improve the economics of local generation and provide the opportunity for local optimization of resources and loads, 4) There continues to be a need for improved resiliency and coordination of local system strategies (e.g. microgrids) with overall grid investments that can result in more optimum overall investment strategies and reduced times to restore power after major events. The increased interest in microgrids as both a system for local energy optimization and for improved resiliency comes with a need for new controller strategies that can help realize these applications. The new controllers should also reflect industry standards and provide a platform for continued innovation. Additionally, the controllers should be flexible to adapt to a wide variety of end-user community applications and to a wide range of electric grid characteristics. The controller should be equipped with standard functions and interfaces that can expand community opportunities for microgrids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Protection Coordination of an Inverter Generation Based Microgrid for an Unbalanced Distribution System

In this paper we examine the protection issues that must be dealt with, to successfully operate a microgrid when the utility experiences a grid outage. Changes in fault current levels within microgrids under grid-tied and islanded conditions present challenges to developing robust and reliable protection schemes. These schemes must provide an effective response in both grid-connected and islanded mode and the transition between these modes. In this study, a section of an actual residential community located in the western part of the United States (U.S.) was considered as part of the microgrid evaluation. A sizing analysis was conducted to select the appropriate sizes of DER; simulated using DER-CAM analysis. The two DERs considered for the study included solar PV and Battery Energy Storage System (BESS). This paper highlights the protection coordination issues when an existing unbalanced distribution system encompassing a residential subdivision is converted into a microgrid with generation sources with low fault contribution. It further explains the strategy to coordinate protection devices during grid connected and islanded microgrid operating regimes.

Bello, Mobolaji↗

Protection Coordination Considerations for a Highly Meshed Urban Microgrid

In microgrid distribution systems, irregular system fault characteristics (with respect to grid-connected mode) and the variability of power flow direction, present challenges to developing a robust and reliable protection scheme that will effective response in both grid-connected and grid-isolation mode. The following investigation captures a meshed network from a larger urban low-voltage (LV) network system in the service area of Consolidated Edison Company of New York (ConEdison), a United States (US) utility that has sufficient customer supplied generation to act as a standalone microgrid. The investigation assesses the viability of differential protection schemes. Protection response has been reviewed with respect to real world application; including, benefits and limitations of selectivity, sensitivity and reliability.

Bello, Mobolaji↗

DMS Advanced Applications for Accommodating High Penetrations of DERs and Microgrids

Efficient and effective management of the electric distribution system requires an integrated approach to allow various systems to work in harmony, including distribution management systems (DMS), distributed energy resources (DERs), distributed energy resources management systems, and microgrids. This study highlights some outcomes from a recent project sponsored by the US Department of Energy, Office of Electricity Delivery and Energy Reliability, including information about (i) the architecture of these integrated systems and (ii) expanded functions of two example DMS applications to accommodate DERs: volt-var optimisation and fault location, isolation, and service restoration. In addition, the relevant DER group functions necessary to support communications between the DMS and a microgrid controller in grid-tied mode are identified.

24 POWER TRANSMISSION AND DISTRIBUTION↗

DMS Advanced Applications for Accommodating High Penetrations of DERs and Microgrids: Preprint

Efficient and effective management of the electrical distribution system requires an integrated system approach for Distribution Management Systems (DMS), Distributed Energy Resources (DERs), Distributed Energy Resources Management System (DERMS), and microgrids to work in harmony. This paper highlights some of the outcomes from a U.S. Department of Energy (DOE), Office of Electricity (OE) project, including 1) Architecture of these integrated systems, and 2) Expanded functions of two example DMS applications, Volt-VAR optimization (VVO) and Fault Location, Isolation and Service Restoration (FLISR), to accommodate DER. For these two example applications, the relevant DER Group Functions necessary to support communication between DMS and Microgrid Controller (MC) in grid-tied mode are identified.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Microgrid Controllers : Expanding Their Role and Evaluating Their Performance

Microgrids have long been deployed to provide power to customers in remote areas as well as critical industrial and military loads. Today, they are also being proposed as grid-interactive solutions for energy-resilient communities. Such microgrids will spend most of the time operating while synchronized with the surrounding utility grid but will also be capable of separating during contingency periods due to storms or temporary disturbances such as local grid faults. Properly designed and grid-integrated microgrids can provide the flexibility, reliability, and resiliency needs of both the future grid and critical customers. These systems can be an integral part of future power system designs that optimize investments to achieve operational goals, improved reliability, and diversification of energy sources.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Measuring the value of microgrids: a benefit–cost framework

This study examines the costs and benefits of microgrids under a variety of business models. Many factors complicate a utility-planning benefit–cost framework when evaluating microgrids. For the purposes of this paper, a ‘microgrid’ is a group of interconnected resources and loads sharing a (usually) single point of interconnection with a larger grid, and capable of balancing load and resources when disconnected from the grid, through dispatch of resources and demand control and/or response. Economically, a microgrid can be examined from a variety of perspectives, and the picture is more complex than for typical utility investments. It is Electric Power Research Institute’s intent to provide unbiased and independent analysis of technology applications, examining economic questions from the perspectives of electricity end-consumers and society as a whole. Among the first steps is determining the point of view the analysis is to assume and narrowing down the set of economic questions to be addressed. Since the nature and major purpose of a microgrid is presumably to provide its internal customers with enhanced reliability and resilience, it is important to ask the question of perspective: For whom is the microgrid an economical choice, and compared with what?

Roark, Jeffrey↗

Ultrafast Power Processor for Smart Grid: Power Module Development

This project’s goal was to increase the switching speed and decrease the losses of the power semiconductor devices and power switch modules necessary to enable Smart Grid energy flow and control equipment such as the Ultra-Fast Power Processor. The primary focus of this project involves exploiting the new silicon-based Super-GTO (SGTO) technology and build on prototype modules already being developed. The prototype super gate-turn-off thyristor (SGTO) has been tested fully under continuously conducting and double-pulse hard-switching conditions for conduction and switching characteristics evaluation. The conduction voltage drop measurement results indicate that SGTO has excellent conduction characteristics despite inconsistency among some prototype devices. Tests were conducted with two conditions: (1) fixed gate voltage and varying anode current condition, and (2) fixed anode current and varying gate voltage condition. The conduction voltage drop is relatively a constant under different gate voltage condition. In terms of voltage drop as a function of the load current, there is a fixed voltage drop about 0.5V under zero current condition, and then the voltage drop is linearly increased with the current. For a 5-kV voltage blocking device that may operate under 2.5-kV condition, the projected voltage drop is less than 2.5 V under 50-A condition, or 0.1%. If the device is adopted in a converter operating under soft-switching condition, then the converter can achieve an ultrahigh efficiency, typically above 99%. The two-pulse switching test results indicate that SGTO switching speed is very fast. The switching loss is relatively low as compared to that of the insulated-gate-bipolar-transistors (IGBTs). A special phenomenon needs to be noted is such a fast switching speed for the high-voltage switching tends to create an unexpected Cdv/dt current, which reduces the turn-on loss because the dv/dt is negative and increases the turn-off loss because the dv/dt is positive. As a result, the turn-on loss at low current is quite low, and the turn-off loss at low current is relatively high. The phenomenon was verified with junction capacitance measurement along with the dv/dt calculation. Under 2-kV test condition, the turn-on and turn-off losses at 25-A is about 3 and 9 mJ, respectively. As compared to a 4.5-kV, 60-A rated IGBT, which has turn-on and turn-off losses about 25 and 20 mJ under similar test condition, the SGTO shows significant switching loss reduction. The switching loss depends on the switching frequency, but under hard-switching condition, the SGTO is favored to the IGBT device. The only concern is during low current turn-on condition, there is a voltage bump that can translate to significant power loss and associated heat. The reason for such a current bump is not known from this study. It is necessary that the device manufacturer perform though test and provide the answer so the user can properly apply SGTO in pulse-width-modulated (PWM) converter and inverter applications.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗