Optimizing Cornell’s future geothermal district heating performance through systems engineering and simulation

Cornell University’s intention to lower its carbon footprint has motivated this engineering evaluation of using low-temperature geothermal energy to supply heat to the campus district energy system. Optimal selection and operation of heat pumps can significantly improve system performance. To support this analysis, we model the quantitative relationships between heat pump configurations and source flow, supply and distribution temperatures, facility heating design options, output heat generation, and carbon abatement outcomes. A systems approach is used for analysis, troubleshooting, and improvement of the model. The result of this effort is a dynamic tool that appropriately responds to hourly thermal demand and communicates energy response for techno-economic analysis. Simulations indicate that a single well-pair in the local Basement Contact Zone reservoir can satisfy almost 68% of annual thermal demand at nearly 20 MWth average capacity while remaining financially competitive compared to conventional heating with levelized cost of heating (LCOH) as low as $4.55/MMBTU ($15.53/MWh th ). A direct-use scheme with heat pump augmentation provided more carbon abatement and 50 to 150% more annual heat supply than one without augmentation. Exploration of three and four well-pair scenarios prove the capability to achieve 50 MW th baseload heating capacity with competitive LCOH and significant carbon reductions.

15 GEOTHERMAL ENERGY↗