Engineering Papers⌕ Search

Engineering topics

Lavrova, Olga

Publications and source records attributed to Lavrova, Olga.

At least 37 records · Page 2

Fault Current Control and Protection in a Standalone DC Microgrid Using Adaptive Droop and Current Derivative

This report presents a novel fault detection, characterization, and fault current control algorithm for a standalone solar-photovoltaic (PV) based dc microgrids. The protection scheme is based on the current derivative algorithm. The overcurrent and current directional/differential comparison based protection schemes are incorporated for the dc microgrid fault characterization. For a low impedance fault, the fault current is controlled based on the current/voltage thresholds and current direction. Generally, the droop method is used to control the power-sharing between the converters by controlling the reference voltage. In this article, an adaptive droop scheme is also proposed to control the fault current by calculating a virtual resistance R droop , and to control the converter output reference voltage. For a high impedance fault, differential comparison method is used to characterize the fault. These algorithms effectively control the converter pulsewidth and reduce the flow of source current from a particular converter, which helps to increase the fault clearing time. Additionally, a trip signal is sent to the corresponding dc circuit breaker (DCCB), to isolate the faulted converter, feeder or a dc bus. The dc microgrid protection design procedure is detailed, and the performance of the proposed method is verified by simulation analysis.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Decay Length Estimation of Single- Two- and Three-Wire Systems Above Ground under HEMP Excitation

Here, we analytically model single-, two-, and three-wires above ground to determine the decay lengths of common and differential modes induced by an E1 high-altitude electromagnetic pulse (HEMP) excitation. Decay length information is pivotal to determine whether any two nodes in the power grid may be treated as uncoupled. We employ a frequency-domain method based on transmission line theory named ATLOG - Analytic Transmission Line Over Ground to model infinitely long and finite single wires, as well as solve the eigenvalue problem of a single-,two-, and three-wire system. Our calculations show that a single, semi-infinite power line can be approximated by a10 km section of line and that the second electrical reflection for all line lengths longer than the decay length are below half the rated operating voltage. Moreover, our findings show that the differential mode propagates longer distances than the common mode in two- and three-wire systems, and this should be taken into account when performing damage assessment from HEMP excitation. Furthermore, this analysis is a significant step toward simplifying the modeling of practical continental grid lengths, yet maintaining accuracy, a result of enormous impact.

42 ENGINEERING↗

Evaluating Energy Impacts and Costs from PV Component Failures

The PV Reliability PerformanceModel (PV-RPM) tool is used to simulate the cost and energy impacts of component faults and failures for a hypothetical PV system. This model, originally developed by Sandia National Laboratories, is a new feature in the National Renewable Energy Laboratory's System Advisor Model (SAM), which performs stochastic analysissampling of probability distributions for faults, failures, and repairs. One PV system was created for this analysis to be representative of a portfolio of maintenance data maintained by Sandia National Laboratories. Fault,failure, and repair distributions from this system are varied from current baseline conditions to simulate different reliability and repair scenarios and resulting energy and cost impacts. Results highlight ways to express the uncertainty around PV system performance when considering the probabilistic behavior of components inthe system, and ways the PV-RPM model can be used to explore different failure and repair scenarios.

14 SOLAR ENERGY↗

Evaluating Energy Impacts and Costs from PV Component Failures: Preprint

The PV Reliability Performance Model (PV-RPM) tool is used to simulate the cost and energy impacts of component faults and failures for a hypothetical PV system. This model, originally developed by Sandia National Laboratories, is a new feature in the National Renewable Energy Laboratory's System Advisor Model (SAM), which performs stochastic analysis sampling of probability distributions for faults, failures, and repairs. One PV system was created for this analysis to be representative of a portfolio of maintenance data maintained by Sandia National Laboratories. Fault, failure, and repair distributions from this system are varied from current baseline conditions to simulate different reliability and repair scenarios and resulting energy and cost impacts. Results highlight ways to express the uncertainty around PV system performance when considering the probabilistic behavior of components in the system, and ways the PV-RPM model can be used to explore different failure and repair scenarios.

14 SOLAR ENERGY↗

Simulating PV System Performance with Component Reliability Distributions

A feature developed by Sandia National Laboratories (SNL) for simulating PV system component reliability has been integrated into the National Renewable Energy Laboratory's System Advisor Model (SAM). The PV Reliability Performance Model (PV-RPM) uses fault/failure and repair distributions to estimate impacts to power, energy production and operational costs. Realization results include the number of failures per component, failure rate, O&M costs incurred based on maintenance strategies, and energy lost based on the failure estimates. As the inputs are inherently uncertain and based on probability distributions, the model realizations include statistical confidence intervals to help bracket the probability that the sample interval contains the true mean value of the variable in question. This paper presents the current validation efforts and provides detail on how this feature is utilized in a PV performance model.

14 SOLAR ENERGY↗

Final Project Report: PV Stakeholder Engagement Initiatives

The key objectives of this project were to increase meaningful stakeholder engagement in photovoltaic performance modeling and reliability areas. We did this by hosting six workshop over the past three years, giving conference and workshop presentations and contributing to technical standards committees. Our efforts have made positive contributions by increasing the sharing of information and best practices and by creating and sustaining a technical community in PV Performance Modeling. This community has worked together over the past three years and has improved its practice and decreased performance modeling uncertainties.

14 SOLAR ENERGY↗

Integrated Cyber/Physical Grid Resiliency Modeling

This project explored coupling modeling and analysis methods from multiple domains to address complex hybrid (cyber and physical) attacks on mission critical infrastructure. Robust methods to integrate these complex systems are necessary to enable large trade-space exploration including dynamic and evolving cyber threats and mitigations. Reinforcement learning employing deep neural networks, as in the AlphaGo Zero solution, was used to identify "best" (or approximately optimal) resilience strategies for operation of a cyber/physical grid model. A prototype platform was developed and the machine learning (ML) algorithm was made to play itself in a game of 'Hurt the Grid'. This proof of concept shows that machine learning optimization can help us understand and control complex, multi-dimensional grid space. A simple, yet high-fidelity model proves that the data have spatial correlation which is necessary for any optimization or control. Our prototype analysis showed that the reinforcement learning successfully improved adversary and defender knowledge to manipulate the grid. When expanded to more representative models, this exact type of machine learning will inform grid operations and defense - supporting mitigation development to defend the grid from complex cyber attacks! This same research can be expanded to similar complex domains.

97 MATHEMATICS AND COMPUTING↗

A Conservative Approach to Defining Photovoltaic System Hazards to Firefighters

Sandia National Laboratories performed analysis to develop conservative hazard guidelines regarding firefighters working near photovoltaic (PV) arrays. Assuming implementation of NFPA 70 system shutdown requirements, the analysis focused on DC hazards only. Several different PV variables were considered, including system grounding and DC voltage classes. The hazard scenarios considered the contact conditions, current paths through the body, and PPE. Guidelines for the hazard definitions for men and women were based on the IEC TS 60479-1 guidelines. The importance of PPE was illustrated in the results.

14 SOLAR ENERGY↗