Engineering Papers⌕ Search

Engineering topics

Joe, Jaewan

Publications and source records attributed to Joe, Jaewan.

Grey-box and ANN-based building models for multistep-ahead prediction of indoor temperature to implement model predictive control

Model-based predictive control (MPC) strategies for heating, ventilation, and air-conditioning (HVAC) systems present an opportunity to lower building energy consumption and operational costs. Such approaches rely on the development of a model to precisely forecast building thermal dynamics, such as room air temperature or heating/cooling rate, and make control-related decisions. The control-oriented modeling of building energy systems should be accurate in predicting indoor conditions and present low computational complexity. These features are the key challenge of implementing advanced control methods such as MPC. Extant studies on building modeling for MPC have focused on step-ahead forecasting techniques to forecast building thermal dynamics, while multistep-ahead forecasting is essential. Moreover, machine learning model suitable in case of the domain-based engineering expertise are also not available. To this aim, we perform a comparative analysis of the grey-box model based on a resistance-capacitance (RC) thermal network and a machine learning model composed of an artificial neural network (ANN) for multistep-ahead prediction of building thermal dynamics using current and historical data. Actual experimental data obtained from the Flexible Research Platform (FRP) in Oak Ridge National Laboratory (US) are used for estimation and validation purposes. The average root mean squared error (RMSE) of the grey-box and ANN models are 0.89 °C and 1.02°C, respectively. Finally, the results indicate that the grey-box model outperforms the ANN model in the considered validation periods in terms of accuracy and prediction stability.

42 ENGINEERING↗

Model-based predictive control of multi-zone commercial building with a lumped building modelling approach

Here this study investigates the applicability of a lumped building modeling approach to model-based predictive control (MPC) to alleviate the complex modeling process of the grey-box multi-zone building model. Based on experimental data, two building models were estimated in this study. The detailed model as a reference case and a lumped model were estimated with decentralized and conventional approaches, respectively. Then, simulations were performed with two boundary conditions, including the comfort bound and electricity cost structure. The performances of the MPC with the detailed and lumped models were analyzed compared to the feedback control. More savings was achieved with a larger comfort bound and more aggressive electricity cost structure. The savings potential of the proposed lumped model approach was not as high as that of the detailed model. However, the proposed method yields good control performance, whose savings was approximately 8.6% over that of feedback control. These results suggest that the proposed method can be used to facilitate MPC implementation in multi-zone building applications.

42 ENGINEERING↗

Empirical Modeling of Direct Expansion (DX) Cooling System for Multiple Research Use Cases

This study provides a general procedure to generate a direct expansion (DX) cooling coil system for a roof top unit (RTU), which is a typical heating ventilation and air-conditioning (HVAC) system for commercial buildings in the United States. Experimental data from a full-scale unoccupied 2-story commercial building is used for the HVAC modeling. The regression for identifying the model coefficients was carried out with multiple stages, and the results were validated with measured data. The model’s applicability was evaluated with multiple case studies, including a building energy simulation (BES) program validation, model-based predictive control (MPC), and fault diagnostics and detection (FDD).

42 ENGINEERING↗

Virtual storage capability of residential buildings for sustainable smart city via model-based predictive control

This paper evaluates the virtual storage capability of a residential air-conditioning (AC) system by utilizing the building mass as a thermal storage to enable sustainable cities through model-based predictive control (MPC). The control-oriented building model was developed with a grey-box model structure based on the experimental data to predict the indoor air temperature. Based on the model, the operation cost-saving potential of the MPC was investigated in a single house with different comfort levels, electricity prices, and prediction horizons. The cost-saving of the MPC was approximately 10.6 % compared to the conventional control. The MPC was expanded to a residential building cluster considering the peak demand charge. In an hourly shedding and load-up scenario, the performances of the MPC and the heuristic prior-based control (PBC) are promising. When shedding was enforced all day, the peak demand saving of the MPC was 36~38 %, whereas that of the PBC was 25.7 % compared to the baseline. In addition, the monthly electricity bill, including the operation and peak demand cost, was investigated with different demand charge rates and weather conditions. The total saving decreased with a low demand charge rate and hot conditions, and the operation cost saving was compromised with more aggressive demand shedding.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

EMPIRICAL VALIDATION OF MULTI-ZONE BUILDING AND HVAC SYSTEM MODELS UNDER UNCERTAINTY

This study implemented a framework of empirical validation of building energy models under uncertainty to a set of controlled experiments that aim to validate multi-zone building and HVAC system models. Energy models were created through iterative acquisitions of information and data and uses measurement data from various types of sensors as both inputs and as observations to validate predictions. Experimental and modeling uncertainties were quantified and propagated accordingly, and probabilistic accuracy metrics were used to evaluate the agreement between model predictions and observations under uncertainty. Sensitivity analysis was performed to identify the most influential uncertainties that will be prioritized to be addressed in the next steps. Current results of two cooling tests show an overall good agreement between predictions and observations on a set of HVAC system outputs despite considerable and influential uncertainty in DX cooling coil COP. Agreements on zone-level responses vary notably among individual rooms, likely because of significant uncertainties in room radiation heat gain and system supply air.

Li, Qi↗

DECENTRALIZED APPROACH TO MULTI-ZONE GREY-BOX MODELING FOR MODEL-BASED PREDICTIVE CONTROL

This study aims to improve the easiness of utilizing the grey-box model (i.e., Resistance-Capacitance circuit) for Model-based Predictive Control (MPC). The primary barrier of implementing the MPC is estimating the control-oriented building model that needs to be computationally inexpensive and quick but reasonably precise in predicting building load and indoor conditions. The estimating of the model parameters becomes more complicated when the building scale is larger; e.g., multi-zone building. In this study, a decentralized approach is introduced; each zone is split and individually estimated with measured boundary temperature from adjacent zones integrated into one single system model. The proposed decentralized method is demonstrated with experimental data from a full-scale multi-zone test cell compared with the centralized reference case.

Joe, Jaewan↗