Engineering topics
Dutta, Soham
Publications and source records attributed to Dutta, Soham.
A Lyapunov-Based Generalized Dc-Side Controller Design for PV-Connected Systems
The objective of this paper is to realize a universal dc-side controller for photovoltaic (PV) systems where the control is agnostic to the downstream converter configuration. To achieve this, the downstream power converter and its controls are manipulated into an effective power control loop that is then cast into a generalized multi-loop design framework. On the dc side, a nonlinear small-signal model of the PV input is realized exclusively in terms of PV datasheet parameters (i.e., open-circuit voltage, short-circuit current, and maximum power point). Finally, a linear controller is used to modulate the dc-side PV system with the generic downstream power controller. A Lyapunov candidate is proposed to analyze the stability of the interconnected system and provide a streamlined approach for the controller design. The proposed design is validated on a 1k VA experimental setup that interfaces a PV module to the grid.
Control Design of Series-connected PV-powered Grid-forming Converters via Singular Perturbation
We report modular architectures that consist of several series-connected dc-ac converters have been a focal point of recent innovations in transformerless medium-voltage applications. In this paper, we consider an architecture consisting of dc-ac modules containing a quadruple active bridge dc-dc converter, which generates three floating dc links that feed grid-side dc-ac inverters. Practical implementation of such a converter module in PV systems requires a variety of controllers that collectively achieve maximum power point tracking, dc-link regulation, and ac-side power control. Design of such multi-loop systems is generally quite challenging due to the potential for destabilizing interactions among loops. Here we propose a design approach where singular perturbation theory is used to decompose the timescales at which each control loop operates and provides a systematic framework for parametric selection. Our approach also ensures system stability of multiple modules with identical controls connected in series across a grid. The paper concludes with experimental results of three 1000 W series-connected converter modules across a stiff grid.
A Lyapunov-Based Generalized Dc-Side Controller Design for PV-Connected Systems: Preprint
The objective of this paper is to realize a universal dc-side controller for photovoltaic (PV) systems where the control is agnostic to the downstream converter configuration. To achieve this, the downstream power converter and its controls are manipulated into an effective power control loop that is then cast into a generalized multi-loop design framework. On the dc side, a nonlinear small-signal model of the PV input is realized exclusively in terms of PV datasheet parameters (i.e., open-circuit voltage, short-circuit current, and maximum power point). Finally, a linear controller is used to modulate the dc-side PV system with the generic downstream power controller. A Lyapunov candidate is proposed to analyze the stability of the interconnected system and provide a streamlined approach for the controller design. The proposed design is validated on a 1-kVA experimental setup that interfaces a PV module to the grid.
1 kV, 10-kW SiC-Based Quadruple Active Bridge DCX Stage in a DC to Three-Phase AC Module for Medium-Voltage Grid Integration
Interfacing low voltage dc to medium voltage three-phase ac grid is often based on series-stackable modular converter architectures. To minimize energy storage requirements, it is advantageous to employ a quadruple active bridge (QAB) stage operating as a "dc transformer" in each stackable module. The QAB stage offers three isolated dc link voltages, which then allow for flexible stacking of three single-phase dc-to-ac inverter stages. Each of the module phases processes a pulsating power having a component at twice the line frequency. This presents a challenge in maintaining zero voltage switching (ZVS) on the secondary sides of the QAB during low-power portions of the line cycle. This article is focused on the design of the QAB stage. A detailed analysis of ZVS switching waveforms is presented, including effects of nonlinear device capacitances. It is shown how ZVS can be achieved at all times using a relatively small circulating current provided by the magnetizing inductance of the high-frequency transformer. Analytical expressions are given for the optimal values of the magnetizing inductance and the dead times of the QAB primary and secondary bridges. This approach is verified by experimental results on a 1 kV, 10-kW SiC-based prototype, demonstrating a relatively flat efficiency curve with a peak efficiency of 97.1% at 75% load.
Levelized Cost of Energy-Oriented Modular String Inverter Design Optimization for PV Generation System Using Geometric Programming
Not Available
Grid-Connected Self-Synchronous Cascaded H-Bridge Inverters with Autonomous Power Sharing: Preprint
Cascaded inverters are widely applied in applications where elevated ac voltages are required while using semiconductor devices with lower voltage ratings. Here, we focus on structures that require localized power transfer between low-voltage sources/loads dispersed across inverter dc links and the inverter ac-sides are series-connected across a three-phase medium-voltage ac grid. To date, decentralized controllers that allow for bi-directional power transfer in such systems are limited. To fill this gap, we propose a virtual oscillator controller which modulates the power processed by each inverter in a purely decentralized manner.
A High-Frequency Planar Transformer with Medium-Voltage Isolation
This paper presents the design of a low-loss, high-frequency planar transformer having medium-voltage (10’s of kV) isolation capability while transformer primary and secondary windings are interleaved to reduce losses. Medium-voltage isolation between adjacent printed circuit board (PCB) layers is extremely challenging using traditional PCB dielectrics. The isolation requirement is met using PCB with 7 kV/mil polyimide (Panasonic Felios RF775) as the dielectric, and by an appropriate layout of the windings and the inter-winding vias. The transformer is used to implement a dual active bridge (DAB) converter in a stackable dc-ac architecture where the dc port is connected to a photovoltaic (PV) string and ac outputs are connected in series to achieve direct PV string-to-medium voltage conversion without the need for low-voltage collection or a bulky line frequency transformer. Since each DAB transformer processes time-varying power, a design methodology is developed to minimize line-cycle-averaged losses. Experimental results are presented for a 1:1 planar transformer in a 7.5 kW SiC-based dc-to-ac module operating at 200 kHz. Isolation of 26 kV between the primary and secondary layers and between the windings and the core is verified using a hipot tester.
A Novel Decentralized PWM Interleaving Technique for Ripple Minimization in Series-Stacked DC-DC Converters
Cascaded dc-dc converters are commonly used in applications where distributed energy sources or loads are connected to elevated voltage levels for power transfer. In such systems, it is advantageous to minimize the ripple on the bus current and voltage by proper phase shifting of the pulse-width modulation (PWM) pulses among the converters via a method known as interleaving. Existing approaches use either a centralized controller or separate communication lines among the stacked converters to control their relative PWM switch transitions. The key drawbacks are that these methods entail significant wiring, the central controller acts as a single point of failure, and implementation on very large numbers of units is impractical. In this paper, we introduce a decentralized interleaving control (DIC) strategy that acts on local current measurements at every converter and achieves communication-free PWM interleaving among the series-stacked converters. The proposed controller is simple in structure and is shown to converge asymptotically to the interleaved state irrespective of clock drifts among the digital signal processors. Experimental results are provided for a system of five series-connected converters showing a 10× reduction in the current ripple compared to normal operation.
A Novel Decentralized PWM Interleaving Technique for Ripple Minimization in Series-Stacked DC-DC Converters: Preprint
Cascaded dc-dc converters are commonly used in applications where distributed energy sources or loads are connected to elevated voltage levels for power transfer. In such systems, it is advantageous to minimize the ripple on the bus current and voltage by proper phase shifting of the pulse-width modulation (PWM) pulses among the converters via a method known as interleaving. Existing approaches use either a centralized controller or separate communication lines among the stacked converters to control their relative PWM switch transitions. The key drawbacks are that these methods entail significant wiring, the central controller acts as a single point of failure, and implementation on very large numbers of units is impractical. In this paper, we introduce a decentralized interleaving control (DIC) strategy that acts on local current measurements at every converter and achieves communication-free PWM interleaving among the series-stacked converters. The proposed controller is simple in structure and is shown to converge asymptotically to the interleaved state irrespective of clock drifts among the digital signal processors. Experimental results are provided for a system of five series-connected converters showing a 10 times reduction in the current ripple compared to normal operation.
A High-Frequency Planar Transformer with Medium-Voltage Isolation: Preprint
This paper presents the design of a low-loss, high-frequency planar transformer having medium-voltage (10's of kV) isolation capability while transformer primary and secondary windings are interleaved to reduce losses. Medium-voltage isolation between adjacent printed circuit board (PCB) layers is extremely challenging using traditional PCB dielectrics. The isolation requirement is met using PCB with $7$\,kV/mil polyimide (Panasonic Felios RF775) as the dielectric, and by an appropriate layout of the windings and the inter-winding vias. The transformer is used to implement a dual active bridge (DAB) converter in a stackable dc-ac architecture where the dc port is connected to a photovoltaic (PV) string and ac outputs are connected in series to achieve direct PV string-to-medium voltage conversion without the need for low-voltage collection or a bulky line frequency transformer. Since each DAB transformer processes time-varying power, a design methodology is developed to minimize line-cycle-averaged losses. Experimental results are presented for a 1:1 planar transformer in a 7.5\,kW SiC-based dc-to-ac module operating at 200 kHz. Isolation of 26 kV between the primary and secondary layers and between the windings and the core is verified using a hipot tester.
2D Ising Model for Adsorption–induced Enantiopurification of Racemates
Mechanisms for the spontaneous transformation of achiral chemical systems into states of enantiomeric purity have important ramifications in modern pharmacology and potential relevance to the origins of homochirality in life on Earth. Such mechanisms for enantiopurification are needed for production of chiral pharmaceuticals and other bioactive compounds. Previously proposed chemical mechanisms leading from achiral systems to near homochirality are initiated by a symmetry–breaking step resulting in a minor excess of one enantiomer via statistical fluctuations in enantiomer concentrations. Subsequent irreversible processes then amplify the majority enantiomer concentration while simultaneously suppressing minority enantiomer production. Herein, equilibrium adsorption of amino acid enantiomer mixtures onto chiral and achiral surfaces reveals amplification of surface enantiomeric excess relative to the gas phase; i. e. enantiopurification of chiral adsorbates by adsorption. Furthermore, this adsorption–induced amplification of enantiomeric excess is shown to be well–describe by the 2D Ising model. More importantly, the 2D–Ising model predicts formation of homochiral monolayers from adsorption of racemic mixtures or prochiral molecules on achiral surfaces; i.e. enantiopurification with no apparent chiral driving force.
Decentralized Control of Cascaded H-Bridge Inverters for Medium-Voltage Grid Integration: Preprint
This paper introduces a fully decentralized control strategy that allows for individualized active and reactive power control of H-bridge inverters connected in series. After formulating a model of the system power flows, we outline a communications-free approach where each inverter can act on independent commands. Inverter-level feedback is accomplished locally via a measurement of current flowing through the stack. A key feature is the lack of any centralized control routines or phase-locked loop. In this framework, the reactive power control loops achieve voltage synchronization among the converters and the grid, and the active power control loops modulate the terminal voltage amplitudes that influence power delivery. Furthermore, pole placement via state feedback is used to ensure stability of voltage synchronization while also enabling tracking of bidirectional power commands. Simulations are presented to validate the proposed approach.
LCOE Design Optimization Using Genetic Algorithm with Improved Component Models for Medium-Voltage Transformerless PV Inverters
For real-world installations of photovoltaic and other renewable energy resources, the critical design metric is the levelized cost of energy (LCOE); however, many power electronics design optimizations are performed with efficiency and power density as the primary design goals. Recent work has shown that a new LCOE-focused optimization approach can yield improved system designs balancing cost and energy generation. This paper expands the LCOE optimization approach by considering comprehensive optimization parameters, adding new modeling of inductor cost, extending the semiconductor model to include effects of losses on housing cost, and implementing a genetic algorithm to improve computation efficiency.
Soft Switching Over the Entire Line Cycle for a Quadruple Active Bridge DCX in a DC to Three-Phase AC Module
This paper is focused on a transformer-isolated quadruple active bridge (QAB) dc-dc converter loaded by three full-bridge dc-ac inverters. The QAB functions as a "DC trans-former" (DCX) in the dc-to-three-phase ac module. The QAB outputs provide time-varying power at twice the line frequency, which presents challenges in maintaining zero voltage switching (ZVS) on the secondary sides during low-power portions of the line cycle. It is shown how ZVS can be achieved in a phase, even at zero-power transfer, using a relatively small circulating current provided by the magnetizing inductance of the high-frequency transformer. The approach is particularly effective in high-voltage applications using SiC MOSFETs, where reductions in switching loss outweigh additional conduction losses due to the circulating currents. A detailed analysis of ZVS switching waveforms at the zero power transfer is presented, including effects of nonlinear device capacitances. Analytical expressions are given for the optimal values of the magnetizing inductance and dead times of the QAB primary and secondary bridges. The approach is verified by experimental results on a 600 V, 4 kW prototype, demonstrating greater than 98.5% efficiency from 1 kW to 4 kW, with a peak efficiency of 99.0%. Compared to conventionally operated prototype, a 54% reduction in total loss is achieved at rated power.
Levelized-Cost-of-Electricity-Driven Design Optimization for Medium-Voltage Transformerless Photovoltaic Converters
Design approaches for power electronics are typically focused on efficiency and power density; however, these strategies do not guarantee cost optimality in any well-defined sense. To overcome this shortcoming, we propose a design framework that yields circuit parameters that minimize the levelized cost of electricity (LCOE) of a generation system. LCOE serves as a meaningful metric since it captures total lifetime costs - including hardware, balance of system, and maintenance costs - and includes the impacts of power conversion efficiency and revenue from harvested energy. To obtain a tractable design problem, we formulate an approximate LCOE improvement model that quantifies the changes in LCOE resulting from a candidate converter design. We apply this framework to a multilevel cascaded topology for low-voltage dc to medium-voltage ac conversion without line-frequency transformers. An example 200 kW commercial-scale system is studied and the solution yields a design with 15 cascaded stages, 98.01% efficiency, and an LCOE reduction of 2.0%.
Levelized-Cost-of-Electricity-Driven Design Optimization for Medium-Voltage Transformerless Photovoltaic Converters: Preprint
Design approaches for power electronics are typically focused on efficiency and power density; however, these strategies do not guarantee cost optimality in any well-defined sense. To overcome this shortcoming, we propose a design framework that yields circuit parameters that minimize the levelized cost of electricity (LCOE) of a generation system. LCOE serves as a meaningful metric since it captures total lifetime costs -- including hardware, balance of system, and maintenance costs\textemdash and includes the impacts of power conversion efficiency and revenue from harvested energy. To obtain a tractable design problem, we formulate an approximate LCOE improvement model that quantifies the changes in LCOE resulting from a candidate converter design. We apply this framework to a multilevel cascaded topology for low-voltage dc to medium-voltage ac conversion without line-frequency transformers. An example 200-kW commercial-scale system is studied and the solution yields a design with 15 cascaded stages, 98.89% efficiency, and an LCOE reduction of 3.6%.